classic | mobile
 

Search...

SA Instrumentation & Control Buyers' Guide

Technews Industry Guide - Maintenance, Reliability & Asset Optimisation

Technews Industry Guide - Wireless 2015

 

Problems in the control of steel reheat furnaces
May 2004, Valves, Actuators & Pump Control


A few months ago I was commissioned to optimise the controls of two large reheat furnaces in a steel manufacturing plant. The client was aware that furnaces were consuming gas at a rate that was very much higher than comparative figures they had obtained worldwide from other manufacturers.

Their plan was to change over the control of the furnaces from an old DCS system to a well-known make of PLC. The technical staff in the plant were mostly of the electrical discipline, and had a rather limited knowledge of feedback control. The changeover was to be conducted over the Christmas period when the furnaces would be shut down for three weeks.

It was decided that components such as valves and regulators would be serviced during the shutdown. Very fortunately (as will be seen later), the plant had installed flowmeters in most air and gas lines, and it was agreed that I would check the valves' performances prior to the shut-down, so that the valve contractors would have a better idea of what to do on them during the service. I was then to return after the shutdown to optimise the actual controls.

Each of the furnaces has three independently controlled zones, each supplied with gas and air mixture. The main controls are the temperature in each zone that operate by varying the flow of air and gas at a certain ratio. There are also several other ancillary controls, the most important being furnace pressure which is controlled by a damper situated before the furnace-stack exhaust fan.

This article will deal with valve problems encountered mostly on the initial visit.

In many of my articles, both in the Case Histories series and in the Loop Signature series, problems caused by poor valves have been described. It was also mentioned that about 86% of problems encountered in control loops are due to valves. Another factor is that plants often use poor valves that are not really designed as proper modulating control valves. One reason for this is because proper control valves are very much more expensive. Poor valves also often used in plants where the personnel do not have much knowledge and experience of control.

It has been stressed that it is extremely difficult to achieve good control with bad valves. In particular, as slow processes can only be tuned slowly to match the dynamics, good performance of the valve is absolutely critical. In 'Cascade control - or how to make a bad valve into a good valve', SA I&C August 2002, it was shown that one way to overcome many of the valve problems on slow processes is to use a cascade flow secondary which acts much quicker than the temperature loop, so that all the temperature controller has to do is to set the setpoint of the flow controller, which in turn because of its faster speed, can overcome many of the valve problems in a relatively short time, and thus ensure that the correct flow of product is fed to the process in accordance with the demands of the temperature controller.

In this particular plant the valves were not really proper modulating control valves, and in fact as will be seen in the figures, most of the valves were so bad that they presented problems that are amongst the worst I have ever encountered in a plant. Fortunately, the plant had installed flowmeters in most loops so that cascade control could be used. Any form of reasonable temperature control would have been virtually impossible without these. Six of the worst examples are shown. All the tests shown in the examples (apart from Figure 5) are open loop tests where equal steps were made on the controller output (PD) in both directions.

Figure 1 shows the test on a heating gas flow control loop. On the first step when opening the valve, it overshot slightly. It oscillated very slightly on the way up on the second step, and took longer getting the flow to the correct place, as it did on the first step.

Figure 1
Figure 1

The loop was then subjected to a series of steps in the closing direction. It can be seen that after the first step in this direction, the valve appeared to oscillate on each step. This got increasingly worse the closer the valve got near its seat. It would appear that the positioner was unable to cope with the forces there, and became increasingly unstable, until it did actually go into complete instability when the process demand signal was zero, and it was actually impossible to stop the flow.

Another thing that can be seen in the test (by observing the relative sizes of the steps of process variable and demand) is that the valve is roughly twice oversized. (This is not too serious. However we recommend that this is about the absolute limit of over-sizing to prevent the possible deleterious effects that can be encountered with badly oversized valves). This valve is very bad and is unable to control at low flows.

Figure 2 is a test on another heating gas flow control loop. The first step down is very much larger than any other step. The flow was then reversed and at the step up to a flow of 75%, a huge overshoot followed by damped cycling was observed. The last two steps were very much smaller than any of the previous ones, and the very last was smaller than the previous. Positioner overshoot is now evident in both these steps. The test illustrates that the valve's performance is inconsistent, and one needs a valve with repeatable behaviour to achieve any sort of reasonable control.

Figure 2
Figure 2

Figure 3 shows a test on an airflow control loop. It can be clearly seen that the valve displays excessive hysteresis (caused by stiction and/or deadband). This measured a vast 28%! The maximum acceptable hysteresis on a control valve is 1%. In addition the valve moved different amounts in a non-repeatable way on most steps, and when the PD was at zero, 40% of the flow was still passing through the valve - really terrible.

Figure 3
Figure 3

A test on another gas heating flow is shown in Figure 4. The valve displays none of the same problems the other valves had, but has very non-linear installed characteristics. This is useless for uniform control action in a cascade secondary loop, which normally has to work over a wide range.

Figure 4
Figure 4

Figure 5 is the gas supply pressure to one of the furnaces. A high frequency oscillation of about 1,5 seconds, with an 11% amplitude can be seen. This was caused by the incoming gas supply pressure regulator being mounted too close to the control valve. There is insufficient capacity in the gas line downstream of the regulator to take up pressure variations, and the regulator is operating in an unstable state. Close coupling of pressure regulators is a fairly common fault found in plants, and it often results in this instability.

Figure 5
Figure 5

Figure 6 illustrates another problem valve that is completely non-repeatable. Nearly every step is a different, random size. The valve jumps and sticks. When the PD is at zero, the valve is still passing 25% flow. I think it is pretty obvious that one could not expect any form of reasonable control with these valves. Remember a valve's job is to translate the demand of the controller into a flow of a fluid. If it cannot do this, one cannot expect decent control. Even a flow controller operates far too slowly to overcome valve problems in an acceptable time. In the case of slow processes like temperature, a controller can literally take many hours to correct for a valve's problems.

Figure 6
Figure 6

The next article in this Case Histories series, which will be published in two months time, will cover some of the control problems encountered on the second visit to this plant where the loops were optimised after the changeover to the PLC system.

For more information contact Michael Brown, Michael Brown Control Engineering, 011 486 0567, michael.brown@pixie.co.za, www.controlloop.co.za

Michael Brown is a specialist in control loop optimisation, with many years of experience in process control instrumentation. His main activities are consulting, and teaching practical control loop analysis and optimisation. He gives training courses that can be held in clients' plants, where students can have the added benefit of practising on live loops. His work takes him to plants all over South Africa, and also to other countries.


Credit(s)
Supplied By: Michael Brown Control Engineering
Tel: (0)82 440 7790
Fax: (0)86 671 9320
Email: michael.brown@mweb.co.za
www: www.controlloop.co.za
Share via email     Print this page  

Further reading:

  • Sliding gate valves optimise airport’s power plant
    September 2015, Macsteel Fluid Control, Valves, Actuators & Pump Control
    Retrofit in power generation reduces gas consumption at Munich airport.
  • Metso receives control valve order for petrochemical project
    September 2015, Metso Automation, Valves, Actuators & Pump Control
    Turkmenistan’s national oil and gas company, Turkmengas, is implementing a USD 3 billion petrochemical plant project expected to be commissioned in 2018.
  • Arca anti-surge valves for Sasol compressors
    September 2015, Valve & Automation, Valves, Actuators & Pump Control
    Arca rounds off its proven series of Ecotrol control valves at the high end with the introduction of the nominal size DN 700 (28”). This valve has been specially optimised for use as an anti-surge valve ...
  • Valve & Automation protects Sasol’s pumps
    September 2015, Valve & Automation, Valves, Actuators & Pump Control
    Petrochemicals group Sasol is spending R8,4 billion to double its production of hard wax in South Africa. Sasol Wax manufactures markets and supplies wax, petroleum jellies and liquefied paraffin. According ...
  • Severe service valves for demanding applications
    September 2015, Mitech, Valves, Actuators & Pump Control
    Severe service control valves are designed for demanding applications where there are high pressure drops, cavitation, high velocities, vibrations, noise and high temperature or sub-zero temperatures. ...
  • New energy saving centrifugal pump
    September 2015, Valves, Actuators & Pump Control
    LEO has introduced the reliable and highly efficient XST series of standard centrifugal pumps with axial suction and radial discharge. Compared with conventional end suction centrifugal pumps, the XST ...
  • Case History 143: Report after optimisation exercise – Part 4.
    August 2015, Michael Brown Control Engineering, Control Systems Design
    This is the fourth article taken from a report which was prepared for various departments in a process company after some optimisation work was performed for them. (The other three articles were published ...
  • Michael Brown’s practical control courses
    August 2015, Michael Brown Control Engineering, Training & Education
    Michael Brown’s well known courses on practical process control are unique and invaluable to novices, as well as to experienced practitioners in the field of regulatory control optimisation. They offer ...
  • Metso valve expertise strong enough for Goliat platform
    August 2015, Metso Automation, Valves, Actuators & Pump Control
    Making its way from the Hyundai yard in South Korea in early 2015 to its home in the Barents Sea, the giant Eni Norge owned Goliat floating, production, storage and off-loading (FPSO) plant is the first ...
  • Rubber lined ball sector valves
    August 2015, Pinnacle Instruments SA, Valves, Actuators & Pump Control
    A sustainable solution to the challenge of handling abrasive fluids in mining applications.
  • Rotex solenoid valves in South Africa
    August 2015, IQ Instruments, Valves, Actuators & Pump Control
    Rotex Automation is a leading manufacturer of solenoid valves and air operated valves. Now available in South Africa through local distributor IQ Instruments, Rotex offers a range of valves to control ...
  • New Emerson metal-seated ball valves
    August 2015, Emerson Process Management SA, Valves, Actuators & Pump Control
    Increased protection for critical assets in severe service applications.

 
 
         
Contact:
Technews Publishing (Pty) Ltd
1st Floor, Stabilitas House
265 Kent Ave, Randburg, 2194
South Africa
Publications by Technews
Dataweek Electronics & Communications Technology
Electronic Buyers Guide (EBG)

Hi-Tech Security Solutions
Hi-Tech Security Business Directory

Motion Control in Southern Africa
Motion Control Buyers’ Guide (MCBG)

South African Instrumentation & Control
South African Instrumentation & Control Buyers’ Guide (IBG)
Other
Terms & conditions of use, including privacy policy
PAIA Manual





 

         
    classic | mobile

Copyright © Technews Publishing (Pty) Ltd. All rights reserved.