Testing operation

A controller responds to input changes with responses dependent on the way the P, the I and the D modules are configured. It is sometimes necessary to perform tests on a controller to ensure it does in fact respond correctly to changes on its input. This is particularly true for controllers in many digital systems, and even more so in the case of many PLCs, where controllers often do not actually respond correctly to input changes. (This may be due to a fault in the controller's software, but more often than not, it is because the user has set up the controller incorrectly.)

Figure 1. Test set-up to determine controller action
Figure 1. Test set-up to determine controller action

A test set-up is shown in Figure 1. To perform the tests, the controller needs to be disconnected from the loop. The input 4 to 20 mA PV signal is fed into the controller from a signal generator. The controller is on local setpoint, and the output (PD) 4-20 mA signal is fed into a recorder, or the Protuner if you have one.

Each test is performed with the controller in automatic. Before starting a test, the controller is switched to manual. The signal generator and the controller's outputs are set to 50% (12 mA.). The setpoint is also set to 50%. When the controller is switched to automatic the output should remain running at a constant 50%. The tests can then be started. These will be discussed later in this series as each type of control action is discussed.

Controller PID algorithms

A controller is essentially a mathematical calculating unit. It is important to know which algorithm (equation) it uses in performing its function. Although control academics are always presenting many specialised algorithms to help in dealing with the control of difficult or specific processes, commercial controllers generally employ one of three algorithms. Some manufacturers allow you to choose between two, or even between all three of these.

All of these three algorithms essentially perform PID control more or less equally well. However, what is not generally known is that different tuning would have to be set in each of them if one was to use P, I and D parameters to control a particular process, and also achieve the identical response from each controller.

The basic format of the three algorithms are:

Where KP is controller gain, TI is integral time in seconds/repeat, TD is derivative time in seconds, and S is the Laplace operator.

Although the names I have used for these algorithms are in fairly common usage, there are as always, no standards, and many of the manufacturers use other, and often confusing nomenclature. The names given here will be used throughout this series to identify a particular algorithm.

Historically it is not quite clear how, and by whom the algorithms were developed, but I suspect that the Ideal was the first, as it appeared many years ago in the Transactions of the ISA. Possibly it was formulated by the famous Nichols. Several articles I have read claim that the Ideal algorithm was not in fact suitable for use to manufacture the pneumatic controllers of that era, which they needed to build in modular form. This was because a full three-term pneumatic PID controller was very expensive, and it was far more cost-effective for users to order controllers with only the control terms that were required for the particular application. If at a later date they did require an additional term or terms, then they could order a kit of parts, which could be easily added into the controller. It was easier to make such a modular controller by slightly modifying the algorithm. This was the Series algorithm.

The Series algorithm effectively became the standard at that time, and with the possible exception of manufacturers of controllers in the electrical power industry, all controllers were made like this. When electronic analog controllers were developed in the 1960s the same algorithm was retained.

Digital controllers appeared on the scene in the 1980s. The old established instrumentation companies were entering the era of the DCS, and PLC manufacturers who up to that time were only interested in digital ON/OFF control, started expanding their products to include analog control capabilities.

The latter in particular had little or no experience of feedback control, and their programmers in many instances probably acquired their knowledge from reading textbooks on PID. They found the Series and the Ideal algorithms, and not fully understanding why the mathematicians of old had bothered to multiply the I and D terms by the P gain, they also came up with the Parallel algorithm. This was termed the Independent algorithm by one of the large PLC manufacturers, who loudly proclaimed it as superior, as the I & D terms were not affected by changing the P term. Although this sounds intelligent, it actually shows that the people who invented that algorithm had little practical knowledge of control. The reasons for this opinion of mine will be explained more fully in later articles in this controller series.

Initially quite a few of the PLC manufacturers used only the Parallel algorithm in their products, but with the exception of only one, the prominent DCS manufacturers stuck to the Ideal or Series algorithms. However, in recent years some of them now also offer it as their default algorithm, or as an alternate. Again in my view, people who program controllers into computers and who offer the Parallel algorithm as a default, again display that they have very little understanding of practical aspects of control.

It is of significance to note that although many of the digital controller manufactures who originally employed the Parallel algorithm, all of them, as far as I am aware, now offer a choice of at least one of the others - mainly because of the unfavourable user reaction to the Parallel.

The main problem with it is in the tuning. The Parallel algorithm is generally much harder to tune by trial and error than Series or Ideal.

To understand this, one must realise that at least 98% of all loops worldwide are tuned by 'trial and error', or if you prefer, playing with the knobs. In general, very few people actually are really capable of achieving good tuning this way, but there are some who have over the years developed a wonderful 'touch' for trial and error tuning, and have become extremely proficient in this art. Now this experience has generally been gained on controllers that are equipped with Series or Ideal algorithms. The tuning for both of these is identical for P + I tuning. It only differs for P + I + D tuning. (An inspection of the equations will explain why this is so, because when D is set to zero the equations become identical.)

If you were to take one of these highly experienced tuning wizards and ask him (or her) to tune a loop that had a controller with a Parallel algorithm, the result would be catastrophic, as the 'feel' that the person had developed using the Series or Ideal algorithm is of no use whatsoever when tuning a Parallel controller. It works completely differently. For example if you had a loop that contained a Series or Ideal controller, and the loop was cycling badly in automatic, you would generally reduce the proportional gain to try and stop the cycle. However, if you were to do this on a loop controlled by a Parallel controller, the loop would actually cycle more.

Reasons for the strange behaviour of the Parallel algorithm and why it is so difficult to use, will be given when the I term is described later in this controller series, and also when tuning is covered, which will be much later in the Loop Signature series.

Michael Brown Control Engineering

(011) 486 0567

[email protected]

www.controlloop.co.za

Michael Brown is a specialist in control loop optimisation, with many years of experience in process control instrumentation. His main activities are consulting, and teaching practical control loop analysis and optimisation. He gives training courses that can be held in clients' plants, where students can have the added benefit of practising on live loops. His work takes him to plants all over South Africa, and also to other countries.



Credit(s)



Share this article:
Share via emailShare via LinkedInPrint this page

Further reading:

Understanding the role of AI in generative engineering design
System Integration & Control Systems Design
When a design engineer sets out to design a new part, component, or assembly, the intent is to meet the design requirements for fit, form and function, and also incorporate a certain degree of innovation and elegance to the overall design. There is no reason to re-invent the wheel by introducing a new design.

Read more...
PCS stays up so you don’t have to
PCS Global System Integration & Control Systems Design
Maybe it’s time to look at a solution that stays online 99,99999% of the time so you don’t have to. This the world of Stratus computer platforms, tailor-made for your critical applications.

Read more...
Loop signature 22: How cyclical disturbances affect a control loop
Michael Brown Control Engineering Editor's Choice
When tuning noisy loops, we recommend in our courses that one should eliminate the noise by editing it out, so the tuning will be done only on the true process response, free of any noise. The controller is controlling the process, and is not controlling the noise.

Read more...
Four ways the global parts shortage has led to innovation and openness
System Integration & Control Systems Design
For those who use automation parts, the unpredictable nature of the supply chain is one of the biggest problems faced today. The shortfall has impacted every industry, but automation components have been especially affected.

Read more...
Case History 191: The weakest link.
Michael Brown Control Engineering Valves, Actuators & Pump Control
Which is the weakest link in a control loop? The answer, without any doubt is that, in most cases, the final control element is the weakest link.

Read more...
Iritron’s year of consolidation
Iritron Editor's Choice System Integration & Control Systems Design
Despite the multiple challenges faced by businesses in South Africa, the buoyancy of the technology sector worldwide has produced some green shoots for automation specialist, Iritron.

Read more...
Five edge opportunities for SIs to maximise revenue in 2024
Editor's Choice System Integration & Control Systems Design
System integrators continue to face the challenge of doing more with less – supporting complex operations, while meeting production schedules with limited resources, and innovating to increase efficiency, maximise safety and reduce risk.

Read more...
Condition monitoring in a forging press retrofit
Beckhoff Automation System Integration & Control Systems Design
Significantly increased vibration on machines can result in many forms of negative impacts such as reduced system performance or damage to the machine and foundation. Using the example of retrofitting a forging press with a maximum press force of 2000 tons, Wölfel Engineering explains how efficiently the process was tailored and implemented with PC-based control and measurement technology from Beckhoff.

Read more...
System integration in the digital age
System Integration & Control Systems Design
To meet the challenges of an increasingly competitive marketplace, many manufacturers (end users) must focus on their core competencies and outsource the rest to experts.

Read more...
Reminiscences of a life in control
Michael Brown Control Engineering SAIMC
Reminiscences from Michael Brown on a long and rich journey in the world of automation together with SAIMC.

Read more...