The rest of this series of Loop Signature articles is devoted to the dynamics of virtually every type of process encountered in industrial control analysis. The purpose is to allow you to identify the dynamics of any process, and then apply the most appropriate tuning for that process. Many people who have attended Part 2 courses have subsequently managed to tune difficult processes in their plant that had previously always been in manual, or working extremely badly in automatic.

To understand this section, a basic understanding of frequency plots is very useful. Most people who have studied control will have encountered frequency plot theory at some stage in their studies. However, very few people really understood what it was about, and even fewer have ever used the theory in real life. This is probably because it is impossible to generate frequency plots without the right loop analytical tools, such as Protuner Loop Analysis software.

The basics of tuning theory were covered in Loop Signature No. 23, on the ‘Basic Trouble Shooting and Loop Tuning’ CD. This section repeats that material.

Frequency response testing

Following the original ideas postulated by the early mathematicians who developed the theory, notably Nichols, one should perform a full frequency response test on a control loop. As illustrated in Figure 1,

a sine wave is generated onto the input to the process (process demand). Initially the sine wave must be at a very low frequency. A sine wave of the same frequency will appear at the output of the loop (process variable). The amplitudes of the input and output sine waves are measured and their ratio calculated. This is called the dynamic gain. The phase difference is also measured. The test is then repeated at a slightly higher frequency, and this procedure is repeated with higher and higher frequencies until the output lags the input by a phase difference of −180°. At this point, if the control loop were closed, the feedback contribution to the process would start pushing the valve in the wrong direction, and instability would result. Figure 2 shows an example of such a test.

The next step in the tuning procedure is to draw a frequency plot from the test data. The various mathematicians came up with slightly different plots. A Bode open loop plot is shown in Figure 3, consisting of two graphs: dynamic gain versus frequency, and phase lag versus frequency.

Bode open loop plot for a first-order process

The first process type to be examined is the simple one already discussed in this series, the first-order lag, deadtime, self-regulating process, which is the type many of the simpler industrial processes more or less conform to.

The Bode open loop plot for this process is shown in Figure 3.

As mentioned above, the Bode consists of two graphs, dynamic gain versus angular frequency in radians per second, and phase lag versus angular frequency. Dynamic gain is expressed in decibels where:

Gain (dB) = 20 × log₁₀ (absolute gain)

The term ‘absolute gain’ is used here for the ratio of the two gains measured in percent of measurement range. The phase lag is in degrees, and the horizontal frequency axis is a logarithmic scale.

For this particular dynamic, working from lower frequencies on the left to higher frequencies on the right, the gain plot starts off horizontally, and then begins dropping until it finishes with a slope of −20 dB/decade at the point where the phase plot reaches −180°. The slope would be −40 dB/decade for two lags, and −60 dB/decade for three lags. Like all self-regulating processes, the phase plot also starts horizontally at 0° and ends at −180°.

Information from the gain plot

The value of the gain where the plot intersects the vertical dynamic gain axis is the process gain, obtained by making a step change on the controller output, and discussed in detail in the Part 1 Loop Signature series. This is logical, because if the frequency is slow enough, the dynamic gain must equal the process gain.

The frequency where the phase lag reaches −180° is known as the crossover frequency, also called the ultimate frequency, which will be discussed later. Moving down by −3 dB from the intersection of the gain plot with the gain axis, and drawing a horizontal line rightwards to intersect, the gain plot gives the corner frequency: ωcorner. The value of the lag time constant can then be obtained from:

TC = 1/ωcorner (seconds)

The last piece of information easily obtained from this plot is the ultimate gain, which will also be revisited later.

This will be continued in the next Loop Signature article.



Michael Brown is a retired expert in control loop optimisation, possessing over five decades of experience in process control instrumentation. His primary focus has been consulting and delivering instruction on practical control loop analysis and optimisation. He has conducted training and optimised control systems at numerous facilities internationally. Mr. Brown continues to author articles reflecting his extensive work, and his courses remain accessible for purchase in PDF format. Additionally, he manages the distribution of Protuner Loop Optimisation software and welcomes inquiries regarding loop-related issues.

Contact details: Michael Brown Control Engineering CC, +27 82 440 7790, michael.brown@mweb.co.za, www.controlloop.co.za




Share this article:
Share via emailShare via LinkedInPrint this page

Further reading:

The rise of software-defined brownfield automation
Schneider Electric South Africa PLCs, DCSs & Controllers
Schneider Electric’s EcoStruxure Automation Expert is enabling brownfield operators to modernise incrementally, decoupling control logic from hardware to bridge legacy equipment and future-ready operations without disrupting production.

Read more...
Upgrading alarm systems for critical industries
Omniflex Remote Monitoring Specialists PLCs, DCSs & Controllers
Omniflex’s OMNI16R alarm annunciator platform provides a direct replacement for legacy CSA systems such as MPAS 90 and SA9100, enabling operators in oil and gas, nuclear and power generation to modernise alarm infrastructure without sacrificing the clarity required for safe operations.

Read more...
How DCS can step off the hardware obsolescence treadmill
Schneider Electric South Africa PLCs, DCSs & Controllers
Schneider Electric argues that virtualising DCS environments breaks the cycle of hardware obsolescence, giving plant operators a smarter path to lifecycle modernisation without production disruption.

Read more...
Loop signature Part 2-6
PLCs, DCSs & Controllers
The Loop Signature series turns to frequency plot theory, explaining Bode open-loop plots and how dynamic gain, phase lag and crossover frequency can be extracted from test data to inform more accurate control loop tuning.

Read more...
PC-based control in surgery
Beckhoff Automation Editor's Choice PLCs, DCSs & Controllers
Researchers at the University of Basel are using Beckhoff PC-based control technology to develop a miniature laser robot for minimally invasive bone surgery.

Read more...
IIoT controller for the field and control cabinet
ifm - South Africa PLCs, DCSs & Controllers
The IIoT controller from ifm is a powerful, communicative and flexible PLC solution in machine and plant digitalisation.

Read more...
How the DCS can step off the hardware obsolescence treadmill
Schneider Electric South Africa PLCs, DCSs & Controllers
Ageing servers and unsupported operating systems are quietly eroding the stability of process plants that rely on distributed control systems. Kobus Vermeulen of Schneider Electric explains how virtualising the DCS environment can break the hardware obsolescence cycle without disrupting operations.

Read more...
Centralised control rooms where growth is elastic, not physical
Schneider Electric South Africa PLCs, DCSs & Controllers
Modernised control rooms feature distributed control system architecture consolidated into centralised compute environments. replacing traditional PCs with thin clients.

Read more...
Advanced DCSs preserve what must not change while enabling
Schneider Electric South Africa PLCs, DCSs & Controllers
Next-generation DCSs, such as Schneider Electric’s Foxboro, are preserving the best of the old while introducing the new in a less disruptive manner.

Read more...
Siemens launches new generation of logic controller
Siemens South Africa PLCs, DCSs & Controllers
Siemens has launched the latest generation of its proven intelligent logic controller, LOGO! 9. This enables simple implementation of small automation projects.

Read more...









While every effort has been made to ensure the accuracy of the information contained herein, the publisher and its agents cannot be held responsible for any errors contained, or any loss incurred as a result. Articles published do not necessarily reflect the views of the publishers. The editor reserves the right to alter or cut copy. Articles submitted are deemed to have been cleared for publication. Advertisements and company contact details are published as provided by the advertiser. Technews Publishing (Pty) Ltd cannot be held responsible for the accuracy or veracity of supplied material.




© Technews Publishing (Pty) Ltd | All Rights Reserved