Loop signatures 20: The great deceivers.

October 2023 Editor's Choice

Noise on the PV signal was discussed in the previous loop signature article, and it was mentioned that it is generally better to live with the noise rather than filtering it out, provided it does not cause the final control element to jump around excessively. This article explains this reasoning.

Normal filters used in process control have a first order lag type dynamic, which is generally preferable to time averaging filters. This is because PID controllers can handle lag dynamics better. A lag type filter is also referred to as a low pass filter, as it passes the lower frequencies and attenuates higher frequency components. Visually, the filtered signal appears to have less noise. Obviously, the greater the filter constant, the smoother the output signal.

In the old analogue days, filters were extremely difficult to implement, and as a result were seldom used. Today, it is extremely easy to implement a simple lag type filter on a digital control machine. Only a few lines of code are needed. Most DCSs and a few PLCs offer filters as a standard block. These filters usually allow one to insert lags in a loop ranging from fractions of a second to literally hours.

When a filter is used in the control equipment, it is usually inserted before the controller and the operator’s display, or the scada. Figure 1 shows the response of a flow signal to a step change on the PD (controller output). The signal has noise of some 2% amplitude on it. The signal is then passed through a filter with a five second time constant, and the output of the filter is shown in the same figure superimposed over the original PV signal. It can be seen that the noise amplitude on the filtered output has been reduced considerably. There are still some fluctuations, due to the lower frequency components present. Apart from that, the signal has not been changed drastically.

In Figure 2 one can see how the situation has changed when a 50 second filter is used. The noise has now been completely eliminated. The filter has certainly achieved its purpose inasmuch as it got rid of the noise. However, the signal response has been really drastically slowed down. The filter has now replaced the flow process as the dominant dynamics in the control loop. In other words, we are now trying to control a filter rather than a flow.

Many learned texts on control have stated that if the time constant of the filter exceeds the dominant time constant of a self-regulating process, the control will be adversely affected. This is not necessarily correct, as you will see in the next example. Tests we have performed show that you can in fact get quite reasonable control on loops with relatively heavy filters. However, there are other really serious effects which are more important, and which make the use of big filters very undesirable.

One of these seriously bad effects is that filters can cause excessive PV overshoots (as high as 300%) on step-changes in setpoint. Such an overshoot is shown in the next example. In previous articles, I have also referred to filters as the world’s biggest liars, as they can distort the response of the process, as seen on scada or DCS screens by the operator. The filter actually tends to reverse the facts, making good things look bad, and bad things look good.

To illustrate this point, Figure 3 is the recording of a control system on a noisy process. The controller has a filter with a 50 second time constant on it. The controller is extremely well tuned. The recording is made with the Protuner analyser connected at the input to the controller (upstream of the filter). A 10% step change in setpoint is followed by a 10% step change in load. An enormous overshoot on the PV response to the setpoint change can be seen. It is really bad. The load change however is well controlled. The controller brings the process back to setpoint speedily, with little overshoot. This is in fact really good. It also shows you can indeed get quite good control, even with a big filter.

Figure 4 shows what the operator sees on his screens with a filtered signal. The setpoint change looks good. There is no sign at all of an overshoot. However, the load change now looks terrible. It only shows as a tiny offset, which seems to take forever to get back to setpoint. Therefore the filter has completely distorted and reversed the true facts. This to me is the most dangerous thing of all, as the operator does not really know what is going on in the plant. It must be remembered that the people doing the tuning are generally also unaware of what filters can do, so they often ruthlessly eliminate noise with enormous filters, and then do tuning whilst looking at the filtered signal, so they have no real idea of the true response.

It is common practice these days for management to use the information available on the scada for management evaluation and control purposes. Therefore it is vital that people should avoid using big filters if they want to have reliable information. This was illustrated on a mine in southern Africa where all the plant accounting and management information was based on a transfer from the scada package into spreadsheets. Large filters were applied on nearly every loop. It was a continuous source of puzzlement to the metallurgists as to why the plant balances never seemed to work out.

Rules for filtering

Sometimes one has to apply filters when the noise is too much and starts moving the final control element around too much. If you apply the following rules of thumb you will find that you cannot go too far wrong.

• If possible, eliminate the noise at its source.

• Use an anti-alias filter on the transmitter (to be discussed in a future loop signature).

• Try tuning without a filter, and check at the actual valve if it is moving due to the noise.

• Avoid using a bigger filter than necessary.

• Biggest filter should be less than 10 x (process deadtime + scan rate of controller).

• Use I-PD controller with filters (see loop signature 16).

• Train the operators and process people on filter effects.

The last point is one of the most important. Unfortunately process personnel are so used to heavily filtered signals in most plants that they are very unhappy when filters are removed. As mentioned in the last loop signature, they mistake noise for instability. It is sometimes very hard to convince them that the control is now much better.

It was mentioned earlier that if you do have to use a filter, then it should be inserted in the control equipment rather than the transmitter. This is because you cannot see the control response at all if you filter in the field. The one exception to this rule is an anti-alias filter, which will be discussed in a future loop signature.


About Michael Brown


Michael Brown.

Michael Brown is a specialist in control loop optimisation, with many years of experience in process control instrumentation. His main activities are consulting and teaching practical control loop analysis and optimisation. He now presents courses and performs optimisation over the internet. His work has taken him to plants all over South Africa and also to other countries. He can be contacted at: Michael Brown Control Engineering CC, +27 82 440 7790.


Credit(s)



Share this article:
Share via emailShare via LinkedInPrint this page

Further reading:

Loop signature 22: How cyclical disturbances affect a control loop
Michael Brown Control Engineering Editor's Choice
When tuning noisy loops, we recommend in our courses that one should eliminate the noise by editing it out, so the tuning will be done only on the true process response, free of any noise. The controller is controlling the process, and is not controlling the noise.

Read more...
High-performance motion control for teabag packaging machine
Beckhoff Automation Editor's Choice
Teepak relies on PC-based control and drive technology from Beckhoff to set new benchmarks for speed and precision in its teabag packaging machines.

Read more...
VEGA takes the pressure out of water pressure measurement
VEGA Controls SA Editor's Choice
Water treatment systems in metropolitan areas require careful monitoring and management processes across widespread networks. However, process plants choosing VEGA for their process automation know that the company offers more than just precise and reliable pressure sensors and instrumentation.

Read more...
Advantages of wireless storage tank and container tank level monitoring
Turck Banner Southern Africa Editor's Choice
Implementing a tank monitoring system that utilises ultrasonic or radar sensors in a wireless network has many advantages.

Read more...
Case History 191: The weakest link.
Michael Brown Control Engineering Valves, Actuators & Pump Control
Which is the weakest link in a control loop? The answer, without any doubt is that, in most cases, the final control element is the weakest link.

Read more...
Bringing Industry 4.0 to a castings foundry for heavy industries
Editor's Choice
Moving to Industry 4.0 takes time and determination, especially for an established company in a heavy industry. Castings foundry, POK in Mexico has moved toward Industry 4.0 in a series of steps over several years, changing from manual to automated systems for more available, immediate and reliable data.

Read more...
SMOM – the future is here now
Iritron Editor's Choice IT in Manufacturing
In his presentation at the recent MESA Africa conference, Neels van der Walt, business development manager at Iritron, revealed the all-encompassing concept of smart mining operations management (SMOM), and why it is inextricably linked to the future of worldwide mining operations.

Read more...
Navigating disruption in manufacturing
Editor's Choice IT in Manufacturing
When considering IT in manufacturing, the underlying assumption is twofold: first, a wave of valuable maturing technologies can be harnessed to create new business value, and second, the environment in which these technologies will be applied will be relatively predictable, with change following a manageable, evolutionary path. However, recent disruptions have shattered these assumptions.

Read more...
The fascination of movement
Editor's Choice Motion Control & Drives
A motor from Faulhaber provides gentle motion for the finest watches in the world.

Read more...
Complete system for transparent energy monitoring
Beckhoff Automation Editor's Choice Electrical Power & Protection
Transparent energy monitoring reduces both machine downtime and the necessity to oversize the corresponding components. Added to these advantages are simplified preventive maintenance, and increased production efficiency. The wide range of PC-based control technology from Beckhoff offers a solution that can be optimally adapted to individual applications.

Read more...