Editor's Choice


Loop Signature 30: Nonlinearity in control loops (Part 1)

October 2025 Editor's Choice Fieldbus & Industrial Networking

Nonlinearity in a control loop can be broadly defined as a change or changes in the process dynamics in the loop. If this occurs, it means that if one is to carry on controlling with the same response to changes in load or setpoint, then the tuning of the controller will also need to be adjusted to meet the new conditions.

Nonlinearity can arise from various causes, and it is important to have linear installed characteristics in your final control element. To summarise this, nonlinear installed characteristics cause changes in process gain as the process moves over the measuring range.

The product of process gain times controller gain (PG x KP) is the main factor that contributes to a controller response to a setpoint or load change. Thus, if the process gain changes, the response will change. This is illustrated in Figure 1, which shows part of an open loop test on a steam flow loop in a large South African petrochemical refinery. As the output of the controller is decreased in equal increments, the steam flow decreases in steps getting smaller and smaller. It is a good example of a non-inear installed characteristic.

The loop was then tuned using the second last step, and placed in automatic. Figure 2 shows the closed loop test where the setpoint is being increased in equal steps. It can be seen that on the lowest step the response is very sluggish, and as the setpoint is increased, it gets faster and faster, until on the last step, the loop is starting to go unstable and is very close to going into an ultimate cycle.

There are many factors as to why nonlinearities may be present in a control loop, and it is sometimes useful to remind oneself about these. Often in our courses we ask delegates to try and list these and then to suggest solutions to them.

The following are some of these solutions:

• Tune in the area of highest process gain and accept sluggish response in areas where the process gain is smaller.

• Use gain scheduling (sometimes referred to as adaptive tuning), i.e., change the tuning via a look-up table to give optimum response as the process gain changes.

• Linearise the characteristics by changing the valve trim.

• Many of the older positioners were supplied with a variety of cams to allow one to change the characteristics by changing the cam. Alternatively, one could machine a cam especially to linearise the loop.

• Many of the modern smart positioners offer various characteristic curves in their software, or one can write a special curve via a polynomial or in a look-up table to do the job.

• It should also be realised that many loops do little work and are really there to deal only with small load changes. These loops do not operate over a wide range. In these cases, it may not be necessary at all to try and linearise them.

Non-linear installed valve characteristics

A valve with nonlinear inherent characteristics like equal percentage is designed to provide linear installed characteristics in the correct applications (where the differential pressure across the valve decreases with increasing load) over the full range of the valve. Therefore, if the valve is largely oversized, there is a good chance that the installed characteristics will not be linear. If such installed nonlinearity is encountered, then solutions would be similar to those mentioned above.

Dynamic non-linearity

Dynamic non-linearity will occur when there is hysteresis in the valve. Every time the valve is reversed, the output of the controller has to move a certain amount (equal to the hysteresis) before the valve actually starts moving. Thus, on open loop step tests, the PV will move a smaller amount on the first step after a reversal, than on subsequent steps.

A case like this is illustrated in Figure 3. This is often the reason that bad tuning is obtained from many of the tuning systems available on the market. Many of them make a single step and then tune on this response. If it is the first step after a valve reversal, and if the valve suffers from hysteresis, then the tuning may be way out. To overcome a problem like this, always tune on a proper step where the valve is in fact moving properly.

Dynamic nonlinearities can also be encountered in processes that respond differently to differing sizes of changes. For example, I have encountered some very strange responses in certain cases of flows of high-density pulp in paper mills. The recording shown in Figure 4 was taken recently during a course at a tissue mill. Equal step changes on the process demand (PD) showed different responses at different places, and also when the valve was moving in different directions. Initially, one would suspect that the valve has severe problems. However, after further tests on the plant, it was decided that the valve was in fact operating properly, and that the strange and differing responses were being caused by consistency changes in the pulp when subjected to step changes. Making very small changes on the PD, and using these for tuning, resolved the problem. This is quite valid because in normal operation the flow is being kept constant, and the control is there to deal with load changes, which on the whole are very small.

This article will be concluded in the next issue of the Loop Signature series.



About Michael Brown

Michael Brown is a retired specialist in control loop optimisation, with over 50 years of experience in process control instrumentation. His main activities were consulting and teaching practical control loop analysis and optimisation. He presented courses and optimised controls in numerous plants in many countries around the world. Michael is continuing to write articles based on the work he has done, and his courses are still available for purchase in PDF format. He is still handling the sales of the Protuner Loop Optimisation software. He is happy to answer questions people may have on loop problems.

Contact details: Michael Brown Control Engineering CC, +27 82 440 7790, [email protected], www.controlloop.co.za


Credit(s)



Share this article:
Share via emailShare via LinkedInPrint this page

Further reading:

Time-sensitive networking
RJ Connect Editor's Choice Fieldbus & Industrial Networking
In this article, we will explore what is driving the rise of time-sensitive networking, how it is reshaping industrial efficiency, the challenges when deploying this technology, and ways to tackle these challenges.

Read more...
Precision in paper processing
VEGA Controls SA Editor's Choice Level Measurement & Control
Paper manufacturing is a demanding process that relies on consistency, precision and control at every stage. The VEGABAR 82 pressure transmitter is well-suited to these harsh environments.

Read more...
Ensuring clean and safe water
Endress+Hauser South Africa Editor's Choice Analytical Instrumentation & Environmental Monitoring
Endress+Hauser’s comprehensive range of disinfection sensors is designed to monitor and control disinfectant levels in water treatment processes.

Read more...
A South African legacy in telemetry
Interlynx-SA Editor's Choice Industrial Wireless
Telemetry is becoming a vital component of industrial strategy, allowing companies to harness real-time data to optimise processes and reduce waste. One company leading this technological shift is Interlynx.

Read more...
Case History 199: Another example of the effectiveness of cascade control
Michael Brown Control Engineering Editor's Choice Fieldbus & Industrial Networking
In my last article I wrote about how cascade control systems can effectively overcome valve problems. This article gives another example of how a temperature control was able to perform well, in spite of really severe valve problems.

Read more...
Upgrading legacy automation
Omron Electronics Editor's Choice Fieldbus & Industrial Networking
Legacy automation is characterised by technology in the later stages of its useful life. As new automation technologies continue to emerge and interconnect at an exponential rate, failing to integrate these technologies can widen the gap between the competitive and the obsolete.

Read more...
Planetary gear units for high torque requirements
SEW-EURODRIVE Editor's Choice Motion Control & Drives
Packing a compact design, along with high torque and low-speed outputs, the new SEW PPK and SEW P2.e planetary gear units from SEW-EURODRIVE offer new capabilities in continuous heavy-duty applications where space is at a premium.

Read more...
These robots crawl into every nook and cranny
DNH Tradeserve t/a DNH Technologies Editor's Choice Motion Control & Drives
Inuktun's small crawler robot magnetically sticks to metal walls and is able to move in all directions. It carries cameras, sensors and tools for inspection or maintenance work in tight pipes and on the outer hulls of tanks or ships. All crawler modules and cameras are equipped with brushed DC motors from Swiss drive specialist, maxon using various motor-gearhead combinations.

Read more...
Swiss watchmaking meets hypercar power
Horne Technologies Editor's Choice
The display of Bugatti’s upcoming luxury model, Tourbillon will be something truly special. Instead of a digital version, the driver will see a genuine Swiss timepiece behind the steering wheel.

Read more...
Reinventing the wheel
Editor's Choice
Once a curiosity in the early automotive age, in-wheel motors are now re-emerging with real promise. From electric cars to commercial vehicles and even aircraft, they are on the verge of transforming transportation engineering.

Read more...









While every effort has been made to ensure the accuracy of the information contained herein, the publisher and its agents cannot be held responsible for any errors contained, or any loss incurred as a result. Articles published do not necessarily reflect the views of the publishers. The editor reserves the right to alter or cut copy. Articles submitted are deemed to have been cleared for publication. Advertisements and company contact details are published as provided by the advertiser. Technews Publishing (Pty) Ltd cannot be held responsible for the accuracy or veracity of supplied material.




© Technews Publishing (Pty) Ltd | All Rights Reserved