Loop signatures 19: Noise – nuisance or enemy?

August 2023 Editor's Choice Fieldbus & Industrial Networking

This Loop Signature series of articles would not be complete without sections on the problems of noise and filtering, which are two of the most misunderstood areas in process control.

For the purpose of this discussion, noise can be defined as a random variation in the process variable (PV) signal around a mean level. There can be various causes for this, but generally it is caused by the process itself, or by the measuring method. Typically, noise in flows may be caused by turbulence, and in tank levels by ripples and disturbances on the surface of the liquid in the tank.

Figure 1 shows a portion of a closed loop test on a coarse ore feed conveyor belt. It can be seen that the signal coming in from the weightometer is extremely noisy. The amplitude of the noise is approximately 25%, and the noise, when put through a spectrum analyser displays more the characteristics of white noise, and does not show any significant individual harmonic frequencies. The noise in this case is mostly caused by the different sizes of rocks passing over the weightometer.

What are the detrimental effects of noise? There are really only two. Firstly, as far as the control itself is concerned, noise can be transmitted through the controller from input to output and may cause the output to start jumping about. If the final control element (e.g. valve) can follow these movements, it will lead to increased wear on the mechanical components in the final control element, leading to a shorter life, and also the control variance itself may be increased. In the example shown in Figure 1 it can be seen that the noise on the output of the controller is so small that it will not cause the ore feed system to respond to it.

Secondly, the noise can create problems for the human beings who are using the control system, like operators, process people and control and instrument personnel.

Generally the more serious of the two problems is the latter – the effect of noise on humans! To understand what I am getting at, refer to Figure 2, which shows two people in the plant looking at a pressure reading. The operator is looking at a digital signal on his screen, and sees the pressure as 3,532 bar. The other man is out in the plant looking at the pressure on the dial of a pressure gauge. He sees the position of the needle on the scale relative to the range, and also that the pressure is about 3.5 bars. The operator reading the digital signal, is completely reliant on the actual value displayed. He has no reference to a relative value, and has no immediate idea if the value is high or low, whereas the person looking at the gauge can immediately see roughly what and where the value is.

For control purposes, on most loops one is not too worried about absolute accurate values. It is generally more important that the process be kept at the setpoint value. In the old days of analogue instruments, operators often used to make a mark with a pen on the PV scale on the controller at the value where they wanted the PV to be controlled. You normally are not interested in controlling to three decimal places, and even with the best control in the world, your PV on most industrial processes is always jumping around a certain amount due to noise and minor load variations going on in the process.

With noisy signals, one has a much better idea of where your measurement is, by reading the information on an analogue indicator, or even better on a trend display or recording. If you try to view it on a digital indicator all you see are numbers jumping around and you have little idea of what is actually happening. In pre-digital days, it was difficult and also expensive to filter signals, particularly with longer time constants, and people accepted noisy displays quite happily.

However in modern times, digital technology allows one to write filters into the software very easily. It takes only a few lines of code. Furthermore, the time constant of the filters can be set to any number you please, even hours. One of the first things people now often do when programming digital control systems, is to suppress the noise by putting large filters onto the PV signal.

To illustrate these points with a real example, refer to Figure 3. This is a portion of a scada display showing the feed control to a milling system on a mine. There is a weightometer on the belt calibrated 0 to 200 tons. The accuracy of this instrument would be at best ±1% FS, which equates to ±2 tons. However, the person who drew the scada screen shows five numerals after the decimal point, which is ridiculous. However, the operator will believe the figure absolutely.

As can be imagined on a really noisy measurement like ore mass, the reading is jumping up and down quite considerably. A typical scada display updates every two or three seconds. In a case like this, the last seven digits of the display will probably be jumping around on virtually every update. To overcome this, the I and C personnel at the mine had put huge filters on the PV, to allow a steady reading.

As is very often the case on feed conveyors, the loop was extremely badly tuned. Figure 4 shows the closed loop ‘as-found’ test with the existing tuning parameters. When a 10% setpoint change was made in the positive direction, it can be clearly seen that the response was almost unstable. When the setpoint was stepped back to the original value, it can be seen how long it took to get the process right back to setpoint. Please note that this recording was made with the Protuner analyser connected upstream of the filters, so the true mass signal is seen.

All the filters were removed and the loop retuned. Figure 5 shows the final test, with setpoint changes of 10% up, 10% down, and then 20% down being made. It can be seen just how good the control now is. The important thing here is that the quality of the control can be clearly judged using the trends, but it would be impossible to do the same using the digital display.

I worked with the operator when this work was performed, and explained to him that he must judge control on trends, and not on digital displays. He understood the reasoning, and was quite happy, particularly as it was the very first time they were able to run the milling system in automatic. Unfortunately he didn’t pass this information onto the night operator, who, when he switched to the milling screen, immediately saw the mass jumping all over the place. What does this mean to an uninformed person who is used to filtered signals? He thinks the control has gone unstable. What does he do then? He puts it into manual, as he knows this is the best way to stop a loop cycling. In this case, to his horror the signal still kept jumping around. He then tripped the plant and called out all the relevant people.

This is in fact one of my biggest problems. I spend a lot of time in plants removing filters and improving the controls. However, although I explain the reasoning to the people I work with at the time, they generally do not pass this information on, and there are always complaints later on that the control was much better before, and it is now worse and quite unstable, as the process people do not understand the difference between instability and noise.

About Michael Brown


Michael Brown.

Michael Brown is a specialist in control loop optimisation, with many years of experience in process control instrumentation. His main activities are consulting and teaching practical control loop analysis and optimisation. He now presents courses and performs optimisation over the internet.

His work has taken him to plants all over South Africa and also to other countries. He can be contacted at: Michael Brown Control Engineering CC, +27 82 440 7790


Credit(s)



Share this article:
Share via emailShare via LinkedInPrint this page

Further reading:

Loop signature 22: How cyclical disturbances affect a control loop
Michael Brown Control Engineering Editor's Choice
When tuning noisy loops, we recommend in our courses that one should eliminate the noise by editing it out, so the tuning will be done only on the true process response, free of any noise. The controller is controlling the process, and is not controlling the noise.

Read more...
High-performance motion control for teabag packaging machine
Beckhoff Automation Editor's Choice
Teepak relies on PC-based control and drive technology from Beckhoff to set new benchmarks for speed and precision in its teabag packaging machines.

Read more...
VEGA takes the pressure out of water pressure measurement
VEGA Controls SA Editor's Choice
Water treatment systems in metropolitan areas require careful monitoring and management processes across widespread networks. However, process plants choosing VEGA for their process automation know that the company offers more than just precise and reliable pressure sensors and instrumentation.

Read more...
Advantages of wireless storage tank and container tank level monitoring
Turck Banner Southern Africa Editor's Choice
Implementing a tank monitoring system that utilises ultrasonic or radar sensors in a wireless network has many advantages.

Read more...
Case History 191: The weakest link.
Michael Brown Control Engineering Valves, Actuators & Pump Control
Which is the weakest link in a control loop? The answer, without any doubt is that, in most cases, the final control element is the weakest link.

Read more...
Bringing Industry 4.0 to a castings foundry for heavy industries
Editor's Choice
Moving to Industry 4.0 takes time and determination, especially for an established company in a heavy industry. Castings foundry, POK in Mexico has moved toward Industry 4.0 in a series of steps over several years, changing from manual to automated systems for more available, immediate and reliable data.

Read more...
SMOM – the future is here now
Iritron Editor's Choice IT in Manufacturing
In his presentation at the recent MESA Africa conference, Neels van der Walt, business development manager at Iritron, revealed the all-encompassing concept of smart mining operations management (SMOM), and why it is inextricably linked to the future of worldwide mining operations.

Read more...
Navigating disruption in manufacturing
Editor's Choice IT in Manufacturing
When considering IT in manufacturing, the underlying assumption is twofold: first, a wave of valuable maturing technologies can be harnessed to create new business value, and second, the environment in which these technologies will be applied will be relatively predictable, with change following a manageable, evolutionary path. However, recent disruptions have shattered these assumptions.

Read more...
The fascination of movement
Editor's Choice Motion Control & Drives
A motor from Faulhaber provides gentle motion for the finest watches in the world.

Read more...
Complete system for transparent energy monitoring
Beckhoff Automation Editor's Choice Electrical Power & Protection
Transparent energy monitoring reduces both machine downtime and the necessity to oversize the corresponding components. Added to these advantages are simplified preventive maintenance, and increased production efficiency. The wide range of PC-based control technology from Beckhoff offers a solution that can be optimally adapted to individual applications.

Read more...