Editor's Choice


Control loop: Case History 180 - Fuel gas pressure control problem

November 2021 Editor's Choice

I was recently asked to sort out a serious control problem on a fuel gas pressure control in a refinery. The loop, the cascade secondary loop to the furnace temperature control, is extremely important because furnace temperature is critical in refinery operation.

A cascade secondary control loop with temperature as the primary control usually has to work quite hard with fairly big movements due to temperature processes often being quite slow and requiring ‘hefty’ tuning.

The problem with the pressure control was that it seemed to work intermittently and sometimes was almost unstable. It also seldom got to setpoint, resulting in large and unacceptable variance on the control.

Testing was extremely difficult to perform on this loop as the operators were insistent that only very small changes could be made, as downstream production could be badly affected if things were moved too much. For this reason, we could not make all the steps I would like to have done.

Closed loop test

Figure 1 shows the closed loop test ‘as found’, which is a test performed with the loop on local setpoint and using the original tuning parameters. It shows two things quite clearly, firstly that the loop was almost unstable and secondly, that the response was slower as the setpoint was moved up, which could indicate non-linear installed valve characteristics.

Further tests also showed that the pressure dynamics were behaving in a strange manner that was not reflective of the actual valve movement, with the pressure PV moving around quite considerably when the controller output was constant. It is not clear as to the cause of this, possibly it was a problem in the measurement, but certainly it would be very difficult to try and get reasonable and consistent control with that behaviour.

Fortunately, it was discovered that there was a flow transmitter in the gas line and it was found that this gave a much better indication of the valve’s performance than the pressure. This is shown in the open loop test of Figure 2, where the difference in the behaviour of the two PVs can be seen. It was therefore recommended that the cascade secondary loop should be changed from pressure to flow. Unfortunately, in this plant as in many others, one cannot just change things like a control strategy immediately. Changes must be approved by a committee comprising process control and instrument engineers. Obviously, the loop would have to be retuned if the change is made.

Open loop test

Figure 3 shows an open loop test with the normal type of steps being made on the PD (controller output) and response of the flow PV being shown. The pressure PV was also recorded as it was needed to try and get a better tune to use in the meantime, but that trace has not been shown in the figure for the sake of clarity.

Figure 3 clearly shows that valve problems also existed. These are:

1. The valve movement is very non-repeatable. It sometimes overshot on being reversed and at other times it stuck quite badly on a reversal.

2. Although the steps made on the PD were all of the same size, the valve seemed to move in smaller steps on opening and much larger steps on closing.

3. At times the valve stuck for a while and then eventually slipped.

4. It looked like the installed valve linearity wasn’t too bad, but it is hard to be sure from this test. It certainly looked like non-linearity in the first ‘as found’ closed loop test shown in Figure 1.

5. Comparing the magnitudes of the steps in PV versus those in the PD, the valve is probably 3-4 times oversized. As mentioned in past articles, oversized valves amplify all problems by the oversize factor.

It is almost impossible to get good control with such a valve. It was therefore recommended that the valve be serviced and preferably replaced with a correctly sized one.

Just in passing, it is interesting to note that I optimised the same loop some 11 years previously and on comparing the then and present tests, it was seen that the process dynamics had changed completely. A subject of frequent discussion is how often one needs to reoptimise a control loop. In general, it is very difficult to answer this question as it depends on many different factors.

Online loop monitoring

My own experience is that dynamics do change on most loops over time and varying process conditions and this to me is an argument for the use of a continuous online loop performance monitoring package. These are often used to highlight badly performing loops. I have found that when used alone these packages can detect some bad loop problems, but often cannot show up other faults and are prone to misinterpreting certain types of loop performance. The best way therefore is to individually analyse and optimise each loop. The online packages really only come into their own after the individual loops have been properly optimised, as they can then immediately give warning of any deterioration in loop performance.


About Michael Brown


Michael Brown.

Michael Brown is a specialist in control loop optimisation with many years of experience in process control instrumentation. His main activities are consulting, and teaching practical control loop analysis and optimisation. He gives training courses which can be held in clients’ plants, where students can have the added benefit of practising on live loops. His work takes him to plants all over South Africa and also to other countries. He can be contacted at Michael Brown Control Engineering cc, +27 82 440 7790, [email protected], www.controlloop.co.za


Credit(s)



Share this article:
Share via emailShare via LinkedInPrint this page

Further reading:

Loop signature 22: How cyclical disturbances affect a control loop
Michael Brown Control Engineering Editor's Choice
When tuning noisy loops, we recommend in our courses that one should eliminate the noise by editing it out, so the tuning will be done only on the true process response, free of any noise. The controller is controlling the process, and is not controlling the noise.

Read more...
High-performance motion control for teabag packaging machine
Beckhoff Automation Editor's Choice
Teepak relies on PC-based control and drive technology from Beckhoff to set new benchmarks for speed and precision in its teabag packaging machines.

Read more...
VEGA takes the pressure out of water pressure measurement
VEGA Controls SA Editor's Choice
Water treatment systems in metropolitan areas require careful monitoring and management processes across widespread networks. However, process plants choosing VEGA for their process automation know that the company offers more than just precise and reliable pressure sensors and instrumentation.

Read more...
Advantages of wireless storage tank and container tank level monitoring
Turck Banner Southern Africa Editor's Choice
Implementing a tank monitoring system that utilises ultrasonic or radar sensors in a wireless network has many advantages.

Read more...
Case History 191: The weakest link.
Michael Brown Control Engineering Valves, Actuators & Pump Control
Which is the weakest link in a control loop? The answer, without any doubt is that, in most cases, the final control element is the weakest link.

Read more...
Bringing Industry 4.0 to a castings foundry for heavy industries
Editor's Choice
Moving to Industry 4.0 takes time and determination, especially for an established company in a heavy industry. Castings foundry, POK in Mexico has moved toward Industry 4.0 in a series of steps over several years, changing from manual to automated systems for more available, immediate and reliable data.

Read more...
SMOM – the future is here now
Iritron Editor's Choice IT in Manufacturing
In his presentation at the recent MESA Africa conference, Neels van der Walt, business development manager at Iritron, revealed the all-encompassing concept of smart mining operations management (SMOM), and why it is inextricably linked to the future of worldwide mining operations.

Read more...
Navigating disruption in manufacturing
Editor's Choice IT in Manufacturing
When considering IT in manufacturing, the underlying assumption is twofold: first, a wave of valuable maturing technologies can be harnessed to create new business value, and second, the environment in which these technologies will be applied will be relatively predictable, with change following a manageable, evolutionary path. However, recent disruptions have shattered these assumptions.

Read more...
The fascination of movement
Editor's Choice Motion Control & Drives
A motor from Faulhaber provides gentle motion for the finest watches in the world.

Read more...
Complete system for transparent energy monitoring
Beckhoff Automation Editor's Choice Electrical Power & Protection
Transparent energy monitoring reduces both machine downtime and the necessity to oversize the corresponding components. Added to these advantages are simplified preventive maintenance, and increased production efficiency. The wide range of PC-based control technology from Beckhoff offers a solution that can be optimally adapted to individual applications.

Read more...