Electrical Power & Protection


Signal isolators and loop interface 101: Part 2

December 2006 Electrical Power & Protection

In Part 1 of this two-part series on loop power isolators four applications were looked at in the November issue. In this issue the final six applications in this series will be covered.

Application 5: Using the LPI's internal clamp with a two-wire transmitter to protect the loop against open circuit

There are cases, when using 4-20 mA inputs to your PLC, RTU or DCS, where it is important that the current loop is not disrupted when the analog input to your PLC or RTU or DCS is unplugged or disconnected.

Application 5
Application 5

In these cases you can use the internal clamp of the LPI to protect the loop from open circuit if your PLC or RTU or DCS input is unplugged or disconnected. This is simply achieved by connecting the input clamp terminal 3 to your 0 V reference. If the analog input to your PLC or RTU or DCS is disconnected, the current will be diverted to 0 V through the clamp, saving the current loop from disconnection.

The voltage across the LPI will be clamped to 6,8 V in this condition - only slightly higher than the normal operating voltage of 1-5 V. This higher clamp voltage should be used when calculating maximum allowable loop resistance.

Note: The 'IN' side of the LPI is always connected to the side of the loop supplying the loop power, so in this application the two-wire transmitter is connected to the OUT terminals of the LPI.

Because of the 2 mm² wire size capability of the LPI terminals, the LPI can also act as the field interface terminals, saving you the extra termination and wiring cost.

To determine the maximum loop resistance of your cabling that you can tolerate in your loop with the clamp in operation, apply the following formula:

where:

RMAX is the maximum resistance in the loop without causing measurement error (in Ω).

VSmin is the minimum voltage of the power supply used to drive the loop (in V).

VTmin is the minimum voltage required by the two-wire transmitter for operation (in V).

For reliable operation over the long term, you should design for less initial cable resistance than this maximum value. This provides a safety factor to account for increase in resistance of terminations and wiring with age or weathering.

A sensible value to use for this safety factor would be 100 Ω (equal to 2 V at 20 mA).

Application 6: Using the LPI's internal clamp with a four-wire transmitter to protect the loop against open circuit

When using 4-20 mA inputs to your PLC, RTU or DCS, there are cases where it is important that the current loop is not disrupted when the analog input to your PLC or RTU or DCS is unplugged or disconnected.

Application 6
Application 6

In these cases you can use the internal clamp of the LPI to protect the loop from open circuit if your PLC or RTU or DCS input is unplugged or disconnected.

In four-wire current transmitter applications this is simply achieved by connecting the output clamp terminal 6 to the current output terminal 4 of the LPI. If the analog input to your PLC or RTU or DCS is disconnected, the current will be diverted through the clamp, saving the current loop from disconnection.

The voltage across the LPI will be clamped to 6,8 V in this condition - slightly higher than the normal operating voltage of 1-5 V. This higher clamp voltage should be used when calculating maximum allowable loop resistance.

Note: The 'IN' side of the LPI is always connected to the side of the loop supplying the loop power, so in this application the four-wire transmitter is connected to the IN terminals of the LPI.

Because of the 2 mm² wire size capability of the LPI terminals, the LPI can also act as the field interface terminals, saving you the extra termination and wiring cost.

To determine the maximum loop resistance of your cabling that you can tolerate in your loop with the clamp in operation, apply the following formula:

RMAX = RT - 500

where:

RMAX is the maximum resistance in the loop without causing measurement error (in Ω).

RT is the maximum load resistance that the current transmitter can drive (in Ω).

For reliable operation over the long term, you should design for less initial cable resistance than this maximum value. This provides a safety factor to account for increase in resistance of terminations and wiring with age or weathering.

A sensible value to use for this safety factor would be 100 Ω (equal to 2 V at 20 mA).

Application 7: Using the LPD to isolate multiple 4-20 mA outputs from a PLC or DCS

In this application, the LPD can be inserted directly into the 4-20 mA output loops between the transmitter and the load.

Application 7
Application 7

Each LPD circuit will consume less than 3 V from the loop. For loop resistance calculation purposes this is equivalent to inserting an additional resistance of 150 Ω into the current loop.

Note: The 'IN' side of the LPD is always connected to the side of the loop supplying the loop power, and so in this application, the transmitter outputs are connected to the IN side of the LPD.

Because of the 2 mm² wire size capability of the LPI terminals, the LPI can also act as the field interface terminals, saving you the extra termination and wiring cost.

To determine the maximum loop resistance of your cabling that you can tolerate in your loop, apply the following formula:

RMAX = RT - RL - 150

where:

RMAX is the maximum resistance in the loop without causing measurement error (in Ω).

RT is the maximum load resistance that the current transmitter can drive (in Ω).

RL is the total resistance of all loads in the loop (excluding the LPI) (in Ω).

For reliable operation over the long term, you should design for less initial cable resistance than this maximum value. This provides a safety factor to account for increase in resistance of terminations and wiring with age or weathering.

A sensible value to use for this safety factor would be 100 Ω (equal to 2 V at 20 mA).

Application 8: Using the LPD to isolate multiple 4-20 mA inputs to a PLC or RTU (with passive inputs)

In this application, the LPD can be inserted directly into the 4-20 mA input loops between the field-mounted two-wire transmitter and the PLC or RTU input.

Application 8
Application 8

Each LPD circuit will consume less than 3 V from the loop. For loop resistance calculation purposes this is equivalent to inserting an additional resistance of 150 Ω into the current loop.

Note: The 'IN' side of the LPD is always connected to the side of the loop supplying the loop power, and so in this application, the two-wire transmitters are connected to the OUT side of the LPD.

Because of the 2 mm² wire size capability of the LPD terminals, the LPD can also act as the field interface terminals, saving you the extra termination and wiring cost.

To determine the maximum loop resistance of your cabling that you can tolerate in your loop, apply the following formula:

where:

RMAX is the maximum resistance in the loop without causing measurement error (in Ω).

VSmin is the minimum voltage of the power supply used to drive the loop (in V).

VTmin is the minimum voltage required by the two-wire transmitter for operation (in V).

RL is the resistance of the PLC/RTU input (in Ω).

For reliable operation over the long term, you should design for less initial cable resistance than this maximum value. This provides a safety factor to account for increase in resistance of terminations and wiring with age or weathering.

A sensible value to use for this safety factor would be 100 Ω (equal to 2 V at 20 mA).

Application 9: Using the LPD to isolate multiple 4-20 mA inputs to a DCS with active (two-wire tx) inputs

In this application, the LPD can be inserted directly into the 4-20 mA input loops between the field mounted two-wire transmitter and the DCS input.

Application 9
Application 9

Each LPD circuit will consume less than 3 V from the loop. For loop resistance calculation purposes this is equivalent to inserting an additional resistance of 150 Ω into the current loop.

Note: The 'IN' side of the LPD is always connected to the side of the loop supplying the loop power, and so in this application, the two-wire transmitters are connected to the OUT side of the LPD.

Because of the 2 mm² wire size capability of the LPD terminals, the LPD can also act as the field interface terminals, saving you the extra termination and wiring cost.

To determine the maximum loop resistance of your cabling that you can tolerate in your loop, apply the following formula:

where:

RMAX is the maximum resistance in the loop without causing measurement error (in Ω).

VSmin is the minimum voltage of the power supply used to drive the loop (in V).

VTmin is the minimum voltage required by the two-wire transmitter for operation (in V).

RL is the resistance of the PLC/RTU input (in Ω).

For reliable operation over the long term, you should design for less initial cable resistance than this maximum value. This provides a safety factor to account for increase in resistance of terminations and wiring with age or weathering.

A sensible value to use for this safety factor would be 100 Ω (equal to 2 V at 20 mA).

Application 10: Dealing with zero loop resistance when using the LPI

The LPI is optimised to minimise the effective inserted loop impedance, but does require a minimum of 100 Ω of load impedance, (or 2 V) on the output to maintain operation.

Application 10
Application 10

In some applications, when using four-wire transmitters, the load being driven is lower than this minimum value, and additional load needs to be inserted into the output loop to bring the minimum load up to the required 100 Ω.

One solution for this is to use the internal 250 Ω resistor to provide this additional resistance. When connected as shown in the diagram, the internal resistor is used in series with the current loop to provide an additional 250 Ω of loop resistance. This brings the LPI back into specification without the need for any additional resistors.

Note: The 'IN' side of the LPI is always connected to the side of the loop supplying the loop power, so in this application the four-wire transmitter is connected to the IN terminals of the LPI.

Because of the 2 mm  wire size capability of the LPI terminals, the LPI can also act as the field interface terminals, saving you the extra termination and wiring cost.

To determine the maximum loop resistance of your cabling that you can tolerate in your loop with the clamp in operation, apply the following formula:

RMAX = RT - RL - 400

where:

RMAX is the maximum resistance in the loop without causing measurement error (in Ω).

RT is the maximum load resistance that the current transmitter can drive (in Ω).

RL is the resistance of the connected load (in Ω).

For reliable operation over the long term, you should design for less initial cable resistance than this maximum value. This provides a safety factor to account for increase in resistance of terminations and wiring with age or weathering.

A sensible value to use for this safety factor would be 100 Ω (equal to 2 V at 20 mA).

For more information contact Ian Loudon, OmnIflex, +27 (0) 31 207 7466.

About Omniflex

Omniflex has accumulated over 40 years of experience in signal conditioning system design and has produced many innovative products in this particular field.



Credit(s)



Share this article:
Share via emailShare via LinkedInPrint this page

Further reading:

Hitachi Energy’s power quality solution
Electrical Power & Protection
Hitachi Energy has announced the deployment of its power quality solution to connect Tanzania’s leading gold producer, Geita Gold Mine (GGML) securely to the national grid.

Read more...
Rail electrification and EV solutions for integrated transport systems
Electrical Power & Protection
A comprehensive range of solutions for rail electrification and electric vehicles is available from leading technology provider ABB, contributing significantly to integrated and sustainable transport systems.

Read more...
PPS delivers containerised distribution board for Western Cape hybrid power project
Electrical Power & Protection
South African electrical enclosure specialist Power Process Systems has successfully completed the design, fabrication and commissioning of a 4000 A containerised distribution board for a wind/PV solar hybrid renewable energy project on a site in the Western Cape.

Read more...
The choice of a thermal carrier is critical for optimal processing
Electrical Power & Protection
Historically steam, fuelled by coal, has been the most prevalent thermal carrier in South African industry. However, times are changing, with the manufacturing and processing sector needing to review the energy reticulation systems and thermal carriers currently in use.

Read more...
ABB’s blueprint for a net zero future
Electrical Power & Protection
ABB’s Mission to Zero is a strategic initiative aimed at achieving a sustainable future characterised by zero emissions, zero accidents and zero waste.

Read more...
How South Africa’s transformer manufacturing industry can fill a gaping infrastructure gap
ACTOM Electrical Machines Electrical Power & Protection
South Africa’s energy transition is accelerating the demand for power transformers. However, this shift toward renewable energy is exposing a critical infrastructure gap: a severe shortage of transformers.

Read more...
General-purpose 350 W AC-DC power supply
Electrical Power & Protection
The TDK-Lambda GUS350 series of compact single-output general-purpose power supplies addresses the need for an economically priced product while maintaining reliability and quality.

Read more...
Ground-breaking battery tester
Comtest Electrical Power & Protection
Midtronics offers the proven MVT handheld battery tester. This revolutionary tool, powered by MDX-AI, is set to redefine the standards of battery diagnostics and testing in the automotive industry.

Read more...
Green hydrogen could be the missing link in powering the future of technology
Electrical Power & Protection
Green hydrogen has numerous applications across multiple industries. It also has the potential to provide a clean energy source to power future technology, with far-reaching implications for both industry and society.

Read more...
Energy audits pave the pathway to sustainability and savings
Schneider Electric South Africa Electrical Power & Protection
Energy audits serve as essential tools for businesses looking to reduce costs and meet environmental targets. By analysing energy consumption across systems such as lighting, HVAC, ICT and water infrastructure, audits identify inefficiencies and quantify carbon footprints, enabling data-driven decisions for operational and financial optimisation.

Read more...









While every effort has been made to ensure the accuracy of the information contained herein, the publisher and its agents cannot be held responsible for any errors contained, or any loss incurred as a result. Articles published do not necessarily reflect the views of the publishers. The editor reserves the right to alter or cut copy. Articles submitted are deemed to have been cleared for publication. Advertisements and company contact details are published as provided by the advertiser. Technews Publishing (Pty) Ltd cannot be held responsible for the accuracy or veracity of supplied material.




© Technews Publishing (Pty) Ltd | All Rights Reserved