Electrical Power & Protection


Signal isolators and loop interface 101 - Part 1

November 2006 Electrical Power & Protection

The ubiquitous problem with every plant is the interface of plant measurement signals to the monitoring and control systems. Unfortunately for many plants this is the single biggest area of weakness and with the success of the organisation depending on these measurements, more attention should be afforded to the integrity of signal conditioning systems.

The problems faced by these systems are numerous:

* Aged cabling.

* Long cable runs.

* Earth loops.

* Interference from other plant devices.

* Floating earth potentials.

* Isolation of signals from PLC, SCADA and DCS.

* Legacy instrumentation.

* Isolate grounded equipment.

* Adding instruments to existing loops.

* Poor design.

* Converting current loops into accurate 1-5 V.

* Protecting against open circuit loops.

* Load dependency calibration.

A compendium of common problems is addressed using loop powered isolators (LPIs) in this two-part article.

In Part 1 four applications will be looked at and in Part 2 in next month's issue, a further six applications will be dealt with.

Application 1: Using the LPI to isolate a powered 4-20 mA transmitter output from a resistive load

This is the basic circuit for inserting a loop powered isolator into a current loop. The LPI can simply be 'cut' into any existing current loop to isolate the current transmitter from the load.

Application 1
Application 1

Note: The 'IN' side of the LPI is always connected to the side of the loop supplying the loop power.

The LPI will consume less than 3 V of the available loop voltage. This is equivalent to inserting less 150 Ω of additional resistance into the current loop.

To determine the maximum loop resistance that you can tolerate in your cabling, apply the following formula:

RMAX = RT - RL - 150

where:

RMAX is the maximum resistance in the loop without causing measurement error (in Ω).

RT is the maximum load resistance that the current transmitter can drive (in Ω).

RL is the total resistance of all loads in the loop (excluding the LPI) (in Ω).

For reliable operation over the long term, you should design for less initial cable resistance than this maximum value. This provides a safety factor to account for increase in resistance of terminations and wiring with age or weathering.

A sensible value to use for this safety factor would be 100 Ω (equal to 2 V at 20 mA).

Application 2: Using the LPI to isolate a field-mounted 4-20 mA two-wire transmitter from a PLC, RTU or DCS

This is the basic circuit for isolating a field-mounted two-wire transmitter from the control circuitry using an LPI. The LPI can simply be 'cut' into any existing two-wire current loop to isolate the transmitter from the panel power supply.

Application 2
Application 2

NOTE: The 'IN' side of the LPI is always connected to the side of the loop supplying the loop power, so in this application the two-wire transmitter is connected to the OUT terminals of the LPI.

Because of the 2 mm² wire size capability of the LPI terminals, the LPI can also act as the field interface terminals, saving you the extra termination and wiring cost. For multiple loops where space is a concern, use the LPD dual module. (See Applications 7, 8 and 9 in Part 2 of this article).

The LPI will consume less than 3 V of the available loop voltage. This is equivalent to inserting less 150 Ω of additional resistance into the current loop.

To determine the maximum loop resistance that you can tolerate in your cabling, apply the following formula:

where:

RMAX is the maximum resistance in the loop without causing measurement error (in Ω).

VSmin is the minimum voltage of the power supply used to drive the loop (in V).

VTmin is the minimum voltage required by the two-wire transmitter for operation (in V).

RL is the total resistance of all loads in the loop (excluding the LPI) (in Ω).

For reliable operation over the long term, you should design for less initial cable resistance than this maximum value. This provides a safety factor to account for increase in resistance of terminations and wiring with age or weathering.

A sensible value to use for this safety factor would be 100 Ω (equal to 2 V at 20 mA).

Application 3: Using the LPI's internal resistor with a two-wire transmitter to provide 1-5 V to your PLC/RTU/DCS

There are many cases when using 4-20 mA inputs to your PLC or RTU or DCS is inconvenient. For example:

1. Your analog input does not support 4-20 mA, and mounting an external resistor is inconvenient.

2. Your analog input has plug in terminals, and you do not want to lose power to your field transmitter or disrupt the loop if the terminal block is unplugged.

Application 3
Application 3

In these cases you can use the internal resistor on the IN side of the LPI to conveniently convert your 4-20 mA signal into a 1-5 V signal. For the most accurate result, ensure that the 0 V reference of the LPI (terminal 8), and the 0 V reference of your analog input are referenced to the same point. Note: The 'IN' side of the LPI is always connected to the side of the loop supplying the loop power, so in this application the two-wire transmitter is connected to the OUT terminals of the LPI.Because of the 2 mm² wire size capability of the LPI terminals, the LPI can also act as the field interface terminals, saving you the extra termination and wiring cost.

The LPI will consume less than 3 V of the available loop voltage. This is equivalent to inserting less 150 Ω of additional resistance into the current loop.

To determine the maximum loop resistance that you can tolerate in your cabling in this application, apply the following formula:

where:

RMAX is the maximum resistance in the loop without causing measurement error (in Ω).

VSmin is the minimum voltage of the power supply used to drive the loop (in V).

VTmin is the minimum voltage required by the two-wire transmitter for operation (in V).

For reliable operation over the long term, you should design for less initial cable resistance than this maximum value. This provides a safety factor to account for increase in resistance of terminations and wiring with age or weathering.

A sensible value to use for this safety factor would be 100 Ω (equal to 2 V at 20 mA).

Application 4: Using the LPI's internal resistor with a four-wire transmitter to provide 1-5 V to your PLC/RTU/DCS

There are many cases when using 4-20 mA inputs to your PLC or RTU or DCS is inconvenient. For example:

1. Your analog input does not support 4-20 mA, and mounting an external resistor to convert the signal to 1-5 V is inconvenient.

2. Your analog input has plug in terminals, and you do not want to lose power to your field transmitter or disrupt the loop if the terminals are unplugged.

Application 4
Application 4

In these cases you can use the internal resistor on the OUT side of the LPI to conveniently convert your 4-20 mA signal into a 1-5 V signal.

For the most accurate result, ensure that the 0V reference to the LPI (terminal 5), and the 0V reference of your analog input are referenced to the same point.

Note: The 'IN' side of the LPI is always connected to the side of the loop supplying the loop power, so in this application the four-wire transmitter is connected to the IN terminals of the LPI.

Because of the 2 mm² wire size capability of the LPI terminals, the LPI can also act as the field interface terminals, saving you the extra termination and wiring cost.

The LPI will consume less than 8 V of the available loop voltage. This is equivalent to inserting less than 400 Ω of resistance into the current loop.

To determine the maximum loop resistance that you can tolerate in your cabling in this application, apply the following formula:

RMAX = RT - 400

where:

RMAX is the maximum resistance in the loop without causing measurement error (in Ω).

RT is the maximum load resistance that the current transmitter can drive (in Ω).

For reliable operation over the long term, you should design for less initial cable resistance than this maximum value. This provides a safety factor to account for increase in resistance of terminations and wiring with age or weathering.

A sensible value to use for this safety factor would be 100 Ω (equal to 2 V at 20 mA).

For more information contact Ian Loudon, OmnIflex, +27 (0) 31 207 7466.



Credit(s)



Share this article:
Share via emailShare via LinkedInPrint this page

Further reading:

No power, no coverage, no problem
Omniflex Remote Monitoring Specialists Industrial Wireless
Remote monitoring expert, Omniflex has delivered a remote monitoring and control solution for an impressed current cathodic protection control system, aiding local authorities in Queensland, Australia in the essential maintenance of roadside culverts.

Read more...
Smart ICCP monitoring for safer tank storage
Omniflex Remote Monitoring Specialists Industrial Wireless
Cathodic protection is critical for combatting corrosion in oil and gas infrastructure. Omniflex explores how to manage CP systems in hazardous and hard-to-reach areas.

Read more...
Unpacking the technoeconomic case for cleaner power in wastewater plants
Schneider Electric South Africa Electrical Power & Protection
Behind every reliable wastewater plant is an electrical system exposed to the effects of harmonics, voltage distortion and overloaded networks caused by fleets of variable speed drives on pumps and aerators.Together, they steadily drive up maintenance demands and elevate the risk of failure.

Read more...
Energy strategy as a competitive advantage for African businesses
Electrical Power & Protection
Energy is no longer simply something that businesses consume. When managed effectively, it becomes a controllable asset that supports resilience and efficiency and sets the foundation for long-term competitiveness.

Read more...
World’s fastest 14 bit arbitrary waveform generator
Vepac Electronics Electrical Power & Protection
The ARB Rider AWG-700 from Vepac is the world’s fastest 14 bit arbitrary waveform generator, with a 20 GS/s real-time update rate and 14 bit vertical resolution.

Read more...
Transformers for mining house in Botswana
ACTOM Electrical Machines Electrical Power & Protection
LH Marthinusen is completing the manufacture of two 30 MVA transformers for a mining house in Botswana.

Read more...
DIN-rail power supplies for reliable and efficient AC/DC conversion
Conical Technologies Electrical Power & Protection
The Claf Power AD75-2BxxS series DIN-rail power supplies are designed for industrial automation, control systems and process environments.

Read more...
Rethinking power for Africa’s data centres
Schneider Electric South Africa Electrical Power & Protection
Africa’s digital economy is scaling faster than its power systems. If it wants resilient, competitive and sustainable data centres, the starting point must be a grid-to-chip architecture rather than a genset-first mentality.

Read more...
The growing decentralisation of power grids
Electrical Power & Protection
The decentralisation of power generation is changing how national grids function. For electrical engineers, several new challenges and opportunities are on the horizon.

Read more...
Custom mini substations for Zambian copper mine
Electrical Power & Protection
Recent orders to supply seventeen specially engineered mini substations for an underground copper mine in Zambia reinforces Trafo Power Solution’s track record in delivering customised electrical solutons for challenging environments.

Read more...









While every effort has been made to ensure the accuracy of the information contained herein, the publisher and its agents cannot be held responsible for any errors contained, or any loss incurred as a result. Articles published do not necessarily reflect the views of the publishers. The editor reserves the right to alter or cut copy. Articles submitted are deemed to have been cleared for publication. Advertisements and company contact details are published as provided by the advertiser. Technews Publishing (Pty) Ltd cannot be held responsible for the accuracy or veracity of supplied material.




© Technews Publishing (Pty) Ltd | All Rights Reserved