Electrical Power & Protection


Power quality at the service panel

October 2023 Electrical Power & Protection

Voltage sags, tripping breakers, overheated electrical panels, and excessive voltage levels indicate possible trouble in an electrical distribution system. Where do you begin the search to isolate the exact cause of these power quality problems? As a common point for branch circuit distribution, the service panel is a convenient place to take the pulse of your electrical system. Several problems can be located right in the service panel itself. For issues elsewhere in the system, measurements at the service panel can tell you where to look next. A quick visual inspection can catch some problems, while others require that measurements to be taken.

This article outlines a step-by-step process for locating and fixing potential trouble spots. Various tools can be used for power quality troubleshooting, from digital multimeters to handheld single- and three-phase power quality analysers that perform many calculations automatically.

Voltage level and stability

The first step in checking to see if voltage levels and stability are the culprits is to measure voltage levels of the branch circuits at the load side of the branch circuit breakers. If voltage levels are low at the breaker, they will be even lower at the receptacle. This could be caused by low tap settings at the transformer. Other likely culprits include loose connections, long feeder runs and overloaded transformers, which create excessively high source impedance.

If intermittent voltage sags are suspected, start at the panel to isolate the cause. Are the sags the result of loads on the same branch circuit, or are they caused by loads elsewhere in the distribution system? We can start isolating the source with a multi-channel recording instrument such as the Fluke power quality analyser, which can monitor trends in voltage and current simultaneously.

Upstream, downstream

What information are you looking for from the trend plots? If a voltage sag occurs simultaneously with a current surge, it is caused by a load on the branch circuit. The cause of the sag is downstream of the measurement point, and therefore can be regarded as a load-related disturbance.

If, on the other hand, the voltage sag coincides with a very small change in current, the sag was likely caused by something upstream of the measurement point and can be thought of as a source-related disturbance. Typically these are heavily loaded three-phase motors started across the line, or sags originating on the utility feed. If the sag approaches an outage, the cause is more likely to be the utility. The event probably reflects a fault and breaker trip, followed by automatic breaker reclosure.

Current balance and loading

To check the current balance and loading, measure each feeder phase and current on each branch circuit. It is critically important to use a true-rms clamp or true-rms digital multimeter with a clamp-on accessory. An average responding clamp-on meter will not provide an accurate measurement, as the combination of fundamental and harmonic current makes this a distorted waveform. A lower cost average-sensing meter will tend to read low, leading you to assume that the circuits are more lightly loaded than they are.

Harmonics

To check for the presence and level of harmonics, measure the current on the feeder neutral. This will typically be in the 80 to 130% range of the feeder current, because the third harmonic will add up in the neutral.

Grounding

Neutral ground bonds in subpanels are a violation of the NEC, and of power quality performance wiring. Neutral ground bonds should be made at the transformer, even though the NEC permits it to be made at the main panel. It should never be made downstream of the main panel, whether at a subpanel or a receptacle. When a neutral ground bond is made at a subpanel or receptacle, the ground path becomes a parallel return path for normal load current, resulting in measurable current on the ground.

Hot spots

Poor connections and the resulting heat losses are the single most significant source of system inefficiency. Loose terminations contribute significantly to excessive source impedance. Fortunately, they are easy to locate with a simple infrared thermometer. Infrared measurements with tools like the Fluke 60 Series are a safe and effective technique for the non-contact detection of panel hot spots.

Circuit breakers

Measurements of circuit breaker voltage drop can help us determine the condition of the breaker. Measure across the line-to-load side of the branch breaker. If the voltage drop exceeds 100 mV, the breaker should be replaced.

In summary, the service panel is the crossroads of the building’s electrical system. From here an experienced electrical troubleshooter can locate and fix any problems.

Product: https://bit.ly/3sQ4GQ4


Credit(s)



Share this article:
Share via emailShare via LinkedInPrint this page

Further reading:

Power supply with scalability optimised
Schneider Electric South Africa Electrical Power & Protection
Schneider Electric has introduced the Easy UPS 3-Phase Modular to the South African marketplace. This robust uninterruptible power supply (UPS) is designed to protect critical loads while offering third-party verified Live Swap functionality.

Read more...
Prioritising arc flash safety
Comtest Electrical Power & Protection
Comtest has developed a range of thermal imaging and wireless testing tools from Fluke, designed to ensure safety is the top priority for engineers working in potentially dangerous arc flash zones.

Read more...
Maximising uptime of AC-powered equipment
Turck Banner Southern Africa Electrical Power & Protection
Providing critical condition monitoring data about AC-powered equipment, Turck Banner’s new Rogowski coil current sensors help maximise machine uptime with ease.

Read more...
New high-power testing solution
Comtest Electrical Power & Protection
Comtest, the local representative of AMETEK Programmable Power, has announced its newest addition to the AMETEK Programmable Power portfolio of high-power testing solutions.

Read more...
Smart and secure way to power IT environments
Electrical Power & Protection
Intelligent power management specialist, Eaton has launched the Eaton 5P Gen 2 UPS, a compact and efficient power solution for edge and informational technology needs. Delivering more output, security, and control than any other device in its class, this new product range also enables fleet management, remote UPS setting, and remote firmware upgrades.

Read more...
A milestone in electrical safety
ABB South Africa Electrical Power & Protection
Celebrating a milestone in electrical safety, ABB proudly marks the 100-year anniversary of its revolutionary Miniature Circuit Breaker.

Read more...
Reshape your footprint
Loesche South Africa Electrical Power & Protection
Calcined clay is an environmentally friendly supplementary cementitious material that has massive potential for reducing CO2 in cement manufacturing. C/Clay is the new label for LOESCHE’s overall process for the production of calcined clay and is part of the company’s CO2 reduction strategy.

Read more...
Heat exchange technology for the oil and gas industry
Electrical Power & Protection
Steinmüller Africa leverages its extensive experience and in-house design and engineering expertise to provide customised industrial shell and tube heat exchangers for sub-Saharan Africa’s oil and gas industry.

Read more...
AI improves energy supply reliability
Schneider Electric South Africa Electrical Power & Protection
Many grids across the globe have a persistent problem in common, ageing infrastructure. This makes a good case for the modernisation of grid infrastructure. Fortunately, there are some almost-immediate steps that can provide a quick win without having to undertake forklift-scale projects.

Read more...
The advantages of overhead power distribution in data centres
Legrand Electrical Power & Protection
With the world becoming increasingly dependent on the internet, the need for additional bandwidth is steadily escalating. This requires more, larger facilities and infrastructure, which demand more power and a dependable electricity supply.

Read more...