Editor's Choice


Loop Signatures 11: Digital controllers – Part 3: The P term.

April 2022 Editor's Choice

Figure 1 shows a simplified P-only controller. The P term may be considered as a pure amplifier that multiplies the input error signal by whatever gain (Kp) is set in the controller to produce the controller’s output signal (PD). The bias allows the output to be manually adjusted either up or down between 50% and 100%.

Figure 2 shows a recording of a test on a P-only controller with Kp = 4, with the controller mounted in the test rig as described in Part 2 of this article series (see www.instrumentation.co.za/14984r). A setpoint (SP) change of 10% has been made, which gives a step change of error of 10% and the PD has immediately stepped up by 40%.

As there are no standards for PID controllers, manufacturers use various units for the P term. Probably the most common is ‘gain’, which, as mentioned above, is the amplifying factor and is defined as the size of the output step divided by the size of the input step.

Another term used by quite a few manufacturers is ‘proportional band’. The relationship between gain and proportional band is:

Proportional Band = (1/Gain) x 100%

Proportional band is sometimes a useful concept to aid one in explaining controller responses, as it may be considered as a graphical representation of the control range. This is illustrated in Figure 3, where a gain of 2 has been entered in a P-only controller. The proportional band works out at 100/2 = 50%. This can be drawn as a band of 50% width lying around the setpoint. Note that the band need not be equidistant around the setpoint, but can in fact move around it. However, in ordinary controllers the band can normally never move away from the setpoint (the position where the setpoint lies within the band is in fact set by the value of the bias).

Assume that, at a particular moment in time, the PV value was sitting on the bottom edge of the proportional band. This would mean that at that time the valve would be at one of its extremities, either fully open or fully closed. If the measurement were then to move up to the top of the proportional band, the valve would have moved through its range to the opposite extremity. Thus, the proportional band represents the control range, as control can only be achievable between the two valve extremities.

This leads to an interesting thought. In the first article in this loop signature series (see https://www.instrumentation.co.za/10379r), it was mentioned that control performance or variance is a measure of error, effectively totalised over a period of time. If we were able to put more gain into a controller and make the proportional band narrower, then it is feasible to believe that the variance would improve, as errors should be smaller and in a narrower proportional band. Therefore, the smaller the band, the better the variance, provided we could in fact achieve control within that band.

Taking this concept to a ridiculous extreme, we could speculate that if we were to put an infinite gain into the controller and make the proportional band infinitely small (i.e., zero), then we should have zero variance, as there should then be no control error. Infinite gain is of course on/off control and as we know, on/off control is in fact in a continuous cycle, either switching the final control element fully on or off, as the PV rises and falls through the setpoint. This results in very poor variance.

In reality, as the gain is increased in the controller, the loop will eventually start reacting to changes in setpoint or load with a cyclical response and this will worsen as the gain is increased. Therefore, for minimum variance, there is a balance between the amount of gain we can insert in a controller and the amount of cycling that we would be prepared to tolerate in any particular control loop. The actual limit in practice would be where the gain in the controller would give rise to a quarter-damped amplitude response on a step change in setpoint.

To explore the limitations inherent in a P-only controller, take the practical case of such a controller that is often still encountered in level controls in plants – the ball valve. The ball valve and level process make up a complete feedback control loop, with the ball as the measuring element. The arm connecting the ball to the valve is the proportional control mechanism and the valve is the final control element.

Imagine the system illustrated in Figure 4 is being used for controlling the level in the reservoir feeding water to our plant. When we examine the system, let us imagine that we find that the inflow and outflow are equal. The level is therefore constant at some particular point; let us call this point our desired level, the setpoint. We then proceed to perform a little experiment and open the manual valve controlling the flow of water to our plant by 10%. As the valve opens, the flow increases and the level starts dropping. As it does so, the ball drops with it and opens up its valve, which in turn increases the flow of inlet water.

Eventually the inflow will equal the outflow, at which point the level stops dropping and will remain constant. The control system is now in equilibrium and the level will remain at the new value, as long as no further changes are made to the manual valve.

The level is again under control, but is no longer at setpoint, and we say that we are now controlling the level with an ‘offset’. Offset is the main drawback to P-only control. There is nothing in a P-only controller that can do anything to permanently eliminate the offset. For practical purposes, one can generally assume that a P-only control system will almost definitely control with offset at some stage or another.

In certain instances, one can tolerate a certain amount of offset, however, the majority of control loops are there to keep the process at the setpoint. The best one can do with a P-only controller is to minimise offset. This can be achieved in two ways.

Firstly, if the controller gain is increased, the offset will decrease proportionally.

Secondly, one can bring the process to the setpoint by adjusting the valve position manually. In the example of the ball valve above, one could physically bend up the arm between the ball and the valve to allow the level to come back up to the setpoint. In a real controller, the same effect can be achieved by adjusting the bias. This adjustment is often called ‘manual reset’. The problem with manual reset is that if you had reset the offset at a particular point in time, then when changes occurred in the process again, another offset would result. In practice, manual reset is used only for initially setting up P-only control systems.

In the real world of industrial process control, P-only control should be used only on processes that are tuned with a large P gain value. It would generally be impossible to use it where the P value is small, as large offsets could result. Therefore, one normally only finds P-only controllers on integrating loops such as level controls where high controller P gain is normal.

Integrating loops are in actual fact better without the I term in the controller. There are two reasons for this. The first is that, as mentioned in previous articles, any hysteresis on a valve in an integrating process that is controlled with P+I control will result in continuous cycling. The second reason is that the I term introduces a second integral term into the combined loop process transfer function and prevents perfect pole cancellation tuning from being achieved. Therefore, the only reason one should technically ever use the I term in the controller on an integrating process is if the possible offset is unacceptable. However, in reality, most people don’t like processes being controlled with offset, even if it is actually acceptable and as a result one finds that the I term is used on most integrating processes.


About Michael Brown


Michael Brown.

Michael Brown is a specialist in control loop optimisation, with many years of experience in process control instrumentation. His main activities are consulting and teaching practical control loop analysis and optimisation. He now presents courses and performs optimisation over the Internet.

His work has taken him to plants all over South Africa and also to other countries. He can be contacted at: Michael Brown Control Engineering CC, +27 82 440 7790, [email protected], www.controlloop.co.za


Credit(s)



Share this article:
Share via emailShare via LinkedInPrint this page

Further reading:

Yokogawa digital plant to accelerate green hydrogen revolution
Yokogawa South Africa Editor's Choice Electrical Power & Protection IT in Manufacturing
Yokogawa explains how a digital plant approach and autonomous operations can integrate the full green hydrogen value chain, from renewable power generation to end-use applications, and why digitalisation and system integration are central to making green hydrogen viable in South Africa.

Read more...
Next-generation autonomous mobile robots from Omron Robotics
Omron Electronics Editor's Choice
The new LD-150 and LD-300 autonomous mobile robots from Omron Robotics offer higher payload capacity and advanced navigation in a compact footprint, with wireless inductive charging and fleet management integration to support high-throughput material transport in demanding production environments.

Read more...
ElectroMechanica reintroduces TechTop to Southern Africa
ElectroMechanica Editor's Choice
ElectroMechanica has officially restored a vital pillar of the southern African motor market, announcing its appointment as the exclusive SADC-wide agent for TechTop.

Read more...
DriveRadar and AI provide smarter maintenance in tough mining conditions
SEW-EURODRIVE Editor's Choice
SEW-EURODRIVE’s DriveRadar system has already embedded AI into predictive maintenance for African mining operations. Jonathan McKey explains how the system monitors external conditions, interprets data and tells operators exactly how much longer a drive can run safely before intervention becomes necessary.

Read more...
Engineering simplicity: shaping the future of valve automation
Festo South Africa Editor's Choice Valves, Actuators & Pump Control
Festo’s VTOP pneumatic assembly offers a streamlined approach to managing pneumatic and electrical interfaces at the valve assembly.

Read more...
XTS for highly efficient end-of-line packaging of beverage bottles
Beckhoff Automation Editor's Choice
Italian machine builder Clevertech used Beckhoff’s XTS linear transport system to help a Dutch distillery double its bottle packaging throughput to 225 bottles per minute while cutting format changeover times from 30 minutes to just seven.

Read more...
Loop signature Part 2-5: Interactive control systems
Michael Brown Control Engineering Fieldbus & Industrial Networking
Feedforward control was explained in the previous loop signature articles. One of the examples used was feedforward control of load changes on a heat exchanger when variations occurred in the flow of the process fluid through the exchanger.

Read more...
Control systems, remote monitoring and human skills in the food sector
Editor's Choice Industrial Wireless
The convergence of specialist skills and advanced technology is becoming critical, a trend underscored by two recent projects completed by Associated Energy Services in the food manufacturing sector.

Read more...
Motion control for flight simulators
Beckhoff Automation Editor's Choice Motion Control & Drives
Turkish specialist, SANLAB is a leader in motion platforms and simulation technologies. At the heart of these platforms are application-specific servo drives, servomotors and industrial PCs for real-time control, which are supplied by Beckhoff.

Read more...
Conductivity sensing as a cornerstone of South Africa’s water smart industry
ifm - South Africa Editor's Choice Sensors & Transducers
South Africa’s engineers operate at the intersection of resource constraint and industrial ambition. Few parameters illustrate this balancing act as clearly as water quality. Whether in municipal treatment works, food and beverage plants or mining operations, the ability to measure water quality accurately and continuously has become non-negotiable.

Read more...









While every effort has been made to ensure the accuracy of the information contained herein, the publisher and its agents cannot be held responsible for any errors contained, or any loss incurred as a result. Articles published do not necessarily reflect the views of the publishers. The editor reserves the right to alter or cut copy. Articles submitted are deemed to have been cleared for publication. Advertisements and company contact details are published as provided by the advertiser. Technews Publishing (Pty) Ltd cannot be held responsible for the accuracy or veracity of supplied material.




© Technews Publishing (Pty) Ltd | All Rights Reserved