Temperature comensation of differential pressure systems

July 2000 Pressure Measurement & Control

Mark Tapson, Manager of Rosemount Measurement Division explains how tuned-systems deliver the most appropriate diaphragm seal installation to compensate for errors caused by temperature variations.

Tuned-Systems contrast significantly to traditional symmetrical configurations; achieving the lowest temperature-induced errors, best time response and lowest installed cost - when measuring level in closed vessels. Differential pressure seal systems have traditionally been specified with identical capillary lengths and seal configurations on both the high and low-pressure process connections. Specifying symmetrical systems was once believed to achieve best total system performance. Actually, the asymmetry of Tuned-Systems compensates for temperature-induced errors. The following discussion will explore how a diaphragm seal system works and prove the theory behind tuned systems.

Tuned-Systems is an asymmetric configuration of a differential pressure diaphragm seal system. The simplest form of a Tuned-System directly mounts the diaphragm seal to the high-pressure process connection. Eliminating excess high-pressure capillary length immediately improves response time and performance, while reducing installed cost. Total system error is dramatically reduced by using diaphragm induced temperature errors to work against head effect temperature errors. Further performance improvements are achieved by adjusting configuration variables as detailed below. Installed cost is reduced by eliminating the excess high-pressure capillary. Because the transmitter is direct mounted to the vessel, neither mounting stand nor mounting bracket are required, further reducing the installed cost.

Seal systems

Diaphragm seal systems respond to changes in both process pressure as the level changes, and in static pressure over the liquid. These variations in pressure are transmitted through an oil-filled capillary to a differential pressure transmitter-sensor. The capillaries and seals are filled with incompressible oil compatible with the process temperature, pressure and media composition. The transmitter is commonly mounted at grade or in close proximity to the high-pressure process connection. For applications under vacuum, the transmitter is mounted below the high-pressure connection to reduce vacuum effects on the transmitter fill fluid. The minimum capillary length is dictated by the distance between the mounting position of the transmitter and the low-pressure connection. All cavities within the assembly are oil-filled including the diaphragm, capillary and transmitter body. Although manufacturing techniques help ensure a high-quality fill, temperature-induced errors are inherent to diaphragm seal systems.

Diaphragm seal system elements

Because the transport mechanism of a diaphragm seal system is the fill fluid, it is important to understand the fill fluid physical characteristics. The fill fluid oil is an incompressible fluid and a change in pressure within the process is directly translated to the transmitter-sensor. Proper fill fluid and assembly preparation are critical to achieve a high quality filled system. Proper preparation requires removing all gases from both the fill fluid and the unfilled transmitter-seal assembly. A successful fill process prevents ambient air from entering the assembly. Air or other gases in the system are compressible fluids and cause erratic transmitter output shifts. Each fill fluid has its own unique physical characteristics and they play the largest role in total system performance. The physical characteristics include: viscosity, coefficient of thermal expansion and specific gravity.

Fill fluid viscosity is a measure of velocity flow rate and dictates the response time of the diaphragm seal system. A temperature increase causes the fill fluid to become less viscous and yields a faster response time, while a decrease in temperature slows the response time. Capillary inside diameter and length also impact system response time. A small inside diameter restricts the fill fluid flow causing slower response time. Capillary length also relates to the time for a change in pressure to reach the transmitter-sensor.

Seal temperature effect error

The fill fluid coefficient of thermal expansion is the rate a fill fluid volume expands or contracts in response to temperature changes. A larger coefficient of thermal expansion factor equates to higher response rate to the change. The fill fluid volume expands to an increase in temperature and contracts to a decrease in temperature. The larger fill fluid volume within the seal system, the greater the total volume expansion or contraction. System volume is dependent on capillary inside diameter, capillary length and seal cavity volume.

Because a diaphragm seal assembly is a closed system, the expanding fill fluid volume presses against the seal diaphragm. The seal diaphragm restricts the expansion causing a back pressure on the fill fluid. The diaphragm back pressure is dependent on diaphragm stiffness or spring rate. Diaphragm spring rate is a function of the diaphragm pattern, thickness, material modulus of elasticity, and diameter. A more flexible diaphragm with a high spring rate minimises the back pressure exerted on the transmitter-sensor. The variations in back pressure exerted on the transmitter-sensor are commonly referred to as seal temperature effect error.

Head temperature effect error

The fill fluid specific gravity is the ratio of the fill fluid density compared to the density of water. As temperature changes, the specific gravity of the fill fluid changes; an increase in temperature lowers the specific gravity while a decrease in temperature increases the specific gravity. The seal elevation exerts pressure on the differential pressure transmitter-sensor and is referred to as head pressure. The fill fluid specific gravity, combined with seal elevation, are the primary variables required to determine the head pressure (head pressure = specific gravity x height). The initial head pressure can be calculated and is zeroed out of the differential pressure system during calibration and commissioning. However, variations in temperature cause changes in fill fluid specific gravity and subsequent variations in head pressure from original commissioning. These variations in head pressure are commonly referred to as head temperature effect error.

Harnessing system elements

Traditional systems apply equivalent seals and capillary lengths to either side of the differential pressure transmitter-sensor; this creates identical (or nearly identical) pressure changes due to seal temperature effect error. Because the pressure changes are equal, and on opposite sides of the transmitter-sensor, the net seal temperature effect error is cancelled. Therefore, the net error is completely a function of the head temperature effect error. The symmetric design was considered to deliver the best total system performance. However, traditional symmetric configurations ignore the largest source of error; head temperature effect error does not realise the opportunity to reduce total system error. Tuned-Systems harness the physical characteristics of the fill fluid and the mechanical design features of the diaphragm seal system to deliver best total system performance.

Both head and seal temperature effect errors occur simultaneously within the system in response to temperature changes. The differential transmitter-sensor cannot differentiate the error type. Therefore, the total system error is the sum of the seal temperature effect plus the head temperature error, and represents the error transmitted to the differential pressure transmitter-sensor. It can be concluded that differential pressure diaphragm seals must be viewed as a system to effectively compensate for total system errors induced by temperature changes.

Consider a Tuned-System that eliminates excess high-pressure capillary and experiences an increase in temperature from original zero. The head temperature error causes a net positive error and is identical in magnitude to a symmetrical system installation, under the same temperature variation conditions. However, the Tuned-System seal temperature effect errors yield a net negative error. The fill fluid volume on the high-pressure side of the system has less volume compared to the low-pressure side of the system. Therefore, the volumetric displacement, and resulting diaphragm back pressure, is dominated by the low pressure side, thus proving total system error for Tuned-Systems that is less than that of traditional systems. The detailed mathematical proof is outlined towards the end of the article.

Minimising total system errors

To take the theory of Tuned-Systems a step further, total system errors can be compensated and in some cases eliminated. Minimising total system errors requires creating seal temperature effect errors that are equal, and opposite in magnitude to head temperature effect errors. In addition to reducing high-pressure capillary fill fluid volume, the following can be varied for additional performance improvements; decrease high-pressure diaphragm stiffness, increase low-pressure fill fluid volume, increase fill fluid expansion coefficient, and/or increase low-pressure diaphragm stiffness. Due to the number of variables, achieving a fully compensated differential pressure seal system requires an automated software tool, such as the Rosemount Instrument Toolkit. Instrument Toolkit has the capability to quickly and easily calculate numerous potential compensated seal systems for any given application condition.

In conclusion: temperature-induced errors are inherent to differential pressure diaphragm seal systems. The errors are caused primarily by the fill fluid physical characteristics responding to a change in temperature. Total system error is also a function of the distance between vessel process connections and the mechanical design of the diaphragm seal system. Total system error is uncompensated in traditional symmetrical system configurations.

The asymmetry of Tuned-Systems compensates total system error by reducing the high-pressure side capillary volume. Further performance improvements can be achieved by varying diaphragm spring rate, system fill volumes, and fill fluid type. The reduced volume and configuration variations compensate for changes in fill fluid specific gravity, thereby providing improved performance in differential pressure diaphragm seal applications.

Mathematical proof

Assumed variables:

D1 = Distance between high-pressure connection and transmitter.

D2 = Distance between low-pressure connection and transmitter.

V1 = Fill fluid volume within high-pressure capillary-seal assembly.

V2 = Fill fluid volume within low-pressure capillary-seal assembly.

dT = Relative change in temperature from original zero.

Sg = Fill fluid specific gravity; assume Sg1 = Sg2.

E = Fill fluid coefficient of thermal expansion; assume E1 = E2.

R1 = Spring rate of seal diaphragm on high-pressure connection.

R2 = Spring rate of seal diaphragm on low-pressure connection.

Note: Spring rate is the fill fluid volume change divided by corresponding change in diaphragm back pressure. Therefore, a diaphragm with a larger R-value is more flexible.

Head pressure error on transmitter sensor

High-side sensor head pressure (H1): H1= (D1 x Sg x E x dT).

Low-side sensor head pressure (H2): H2 = (D2 x Sg x E x dT).

Head Pressure = H1 - H2.

Head Pressure = (D1 x Sg x E x (T) - (D2 x Sg x E x dT) = (D1 - D2) (Sg x E x dT).

D2 > D1 therefore, D1 - D2 = -D.

Head pressure = - D x Sg x E x dT.

Seal pressure error on transmitter sensor

High-pressure seal:

Volumetric displacement = V1 x E x dT.

Pressure change = (V1 x E x dT)/ R1.

Low-pressure seal

Volumetric displacement = V2 x E x dT.

Pressure change = (V2 x E x dT)/ R2.

Total seal pressure error

Seal pressure error = (V1 x E x dT)/R1 - (V2 x E x dT)/R2 = ( V1/R1 - V2/R2) x E x dT.

Total system error (TSE)

Total system seal error is eliminated when head pressure error equals seal temperature error. Therefore, the Tuned-Systems performance improvement is proven by solving the total system error equation below.

TSE = -D x Sg x E x dT - (V1/R1 - V2/R2) x E x dT.

Factoring out like variables and qualitatively compare results of the traditional system scenario versus Tuned-System scenarios:

TSE = - DSg - ( V1/R1 - V2/R2) x E x dT.

Symmetrical system case

If V1 = V2 and R1 = R2 then TSE = - DSgE x dT.

All of the total system error is caused by the head pressure error acting on the transmitter-sensor.

Tuned-Systems case

If V1 < V2 or V1 < V2 or V1 = V2 is possible and if R1 = R2 or R1 > R2 or R1 > R2 is possible then, Tuned-Systems are mathematically proven. All scenarios have improved total system error. Instrument Toolkit provides further proof, quantitatively solving the equation.

In summary, the following basic rules should be applied to provide additional compensation in diaphragm seal systems:

* Apply an asymmetrical system configuration.

* Reduce the high pressure side fill fluid volume.

* Minimise the high pressure diaphragm stiffness (increase spring rate).

* Increase the low pressure side fill fluid volume.

* Increase the low pressure diaphragm stiffness (decrease spring rate).

* Use an instrument such as the Rosemount Instrument Toolkit to optimise total system performance



Credit(s)



Share this article:
Share via emailShare via LinkedInPrint this page

Further reading:

VEGA handles the pressures of water treatment systems
VEGA Controls SA Pressure Measurement & Control
A water treatment system for a major metropolitan area in the Midwestern United States demands careful monitoring and management of processes across its sprawling network. Choosing VEGA for its process automation needs meant more than just obtaining precise and reliable pressure sensors.

Read more...
Pressure sensors for hydrogen applications
Instrotech Pressure Measurement & Control
Keller manufactures isolated piezoresistive pressure sensors. The great advantage of the piezoresistive measuring principle is its high stability.

Read more...
Sensor technology for cartonboard machine for paper and packaging
VEGA Controls SA Pressure Measurement & Control
Paper and packaging specialist, LEIPA undertook a comprehensive modernisation project, combining three stock preparation lines into one, and making investments in new plant components and extensive automation technology. Because of the good experiences the company had already had with VEGA sensors, those responsible for planning and maintenance decided in favour of the VEGABAR 82 pressure transmitter as the standard instrument for level and pressure measurement in the new stock preparation system.

Read more...
Pressure measurement without risk of contamination
WIKA Instruments Pressure Measurement & Control
Injectables are among the most sensitive products in the pharmaceutical industry. Sterility is essential during production. For this reason, a manufacturer of biopharmaceuticals decided to implement the pressure monitoring of its processes with hygienic instruments from WIKA.

Read more...
Pressure monitoring for oil and water tempering machines
Instrotech Pressure Measurement & Control
Temperature plays a significant role in many manufacturing processes. In such cases, a tempering machine is used to maintain the manufacturing process at the desired temperature. Keller supplied PR-21Y piezoresistive pressure transmitters to a client specialising in developing and producing oil and water tempering machines.

Read more...
How to look after your pressure gauge
SA Gauge Editor's Choice Pressure Measurement & Control
Pressure and temperature gauges are very widely used on process plants. Specialising in the design and manufacture of pressure and temperature measuring instruments, SA Gauge believes that all process and ambient factors should be considered when selecting and installing pressure measuring devices. The company recommends that the following guidelines on selection and calibration be followed in order to prevent gauge failure.

Read more...
Process measurement solution for Copper Belt’s Kansanshi Mine
VEGA Controls SA Pressure Measurement & Control
Kansanshi Mine faced measurement challenges in its gland water tanks, slurry, and raw materials in the stockpiles and crusher bins. VEGA was able to offer a suitable solution to resolve these challenges.

Read more...
Pressure and level switches for food production
VEGA Controls SA Pressure Measurement & Control
New compact measuring instruments from VEGA prove that automation in food production can be very simple and economical without compromising on hygiene or safety.

Read more...
Safe pressure measurement in chlorine production
WIKA Instruments Pressure Measurement & Control
Pressure measurement plays a central role in chlorine production, which is a safety-critical process.

Read more...
Interference-resistant pressure transmitters
Instrotech Pressure Measurement & Control
Instrotech offers a pressure transmitter from Keller for temperature compensation and protection from electromagnetic fields (EMC) in the recently approved 21Y Series.

Read more...