Electrical Power & Protection


Outsmarting the DC switch arc

August 2019 Electrical Power & Protection

Electromechanical relays (EMRs) or solid-state relays (SSRs) are used for switching various loads in numerous industrial fields. These switching devices generally operate reliably in the control cabinet at the most commonly used voltage levels 24 VDC and 230 VAC. If, however, DC loads have to be switched at higher voltages, often with higher powers at the same time, the common standard versions of the EMRs and SSRs prove to be unsuitable, and often fail quickly.

Applications for the switching of higher DC loads can be found in numerous industrial sectors. Examples include electric motor vehicles with up to 800 VDC, battery voltages on trains, and photovoltaic systems with up to 1000 VDC. Due to the application-specific switching requirements and the simultaneously occurring high currents, the relay manufacturers have developed special devices for those applications. However, these devices are often unsuitable for the control cabinet applications implemented in automation solutions.

Use of DC voltage from battery systems

For the most part, the control cabinets in industrial automation solutions use the common voltages of 24 VDC and 230 VAC, as well as three-phase systems for mainly motor-driven applications, operating at higher voltages. At a closer look, however, DC voltage systems operating at more than 100 VDC can also be found, normally used as battery-based emergency power supplies in case the mains voltage fails. Such solutions are used in computer centres, airports, in the chemical industry, in process engineering, in power plants for electricity generation, etc.

To maintain uninterrupted operation, even when a malfunction occurs, power plants have emergency power generators. When these also fail, large battery systems need to ensure that the important parts of the power plant can operate in emergency mode for a certain period of time. In Europe, such applications preferably use 220 VDC battery systems, whereas also 110 and 125 VDC solutions can be found in other parts of the world. In order to supply the very high power required, a significant number of individual cells are connected in a large battery system. Numerous loads from the control system, including many switching devices such as contactors and coupling relays, which are conveniently snapped onto standardised DIN rails in the control cabinet, are directly supplied by the DC voltage from these batteries. In contrast, three-phase loads – such as pumps – are supplied indirectly by the batteries via rotating transformers or converters.

No voltage commutation with DC voltages

What are the reasons that cause standard coupling relays in such applications, often installed due to a lack of insight, to fail so quickly? The answer can be found considering the completely different behaviour of coupling relays when switching AC or DC voltage. On that point, a brief digression into the physical basics: almost all of the standard coupling relays available today have contact clearances in the range of 0,3 to 0,4 millimetres. These clearances are perfectly sufficient to switch off loads up to 230 VAC, even at higher currents. Not later than after one half-wave of the sinusoidal mains voltage, the voltage commutates and thus ensures that any electric arc possibly igniting at shutoff is extinguished automatically. Naturally, with DC voltages, there is no voltage commutation, which is why the maximum permissible switching current decreases drastically, especially with higher switching voltages.

Generally, users don’t know about the differences in relay behaviour because the interruptible current turns out to be absolutely identical (10 A for a suitably rated coupling relay) at the voltages of 24 VDC and 230 VAC commonly used in automation solutions. However, in applications where the DC voltage to be switched is significantly higher – 220 VDC, for example, the 10 A coupling relay can only switch off 0,3 A. This is why, unfortunately, misuse occurs frequently, leading to a total failure of the standard coupling relays, sometimes even during the first switching cycle.

Integration of an additional magnetic arc blowout solution

The explanations above emphasise that common coupling relays are not suitable for switching off higher DC loads. Consequently, automation applications also require special solutions. The integration of an additional magnetic arc blowout solution has proven helpful here. The functional principle is simple: a permanent magnet is integrated into the contact gap of such a special relay.

Any electric arc igniting at shutoff will now be deflected in the magnetic field in accordance with physical laws. Instead of, as before, striking directly at the point where the distance between the opened relay contacts is shortest, the electric arc deviates laterally between the contacts. Because this looks like the electric arc is blown out of the gap, the relays are called magnetic arc blowout relays. The electric arc becomes significantly longer, and even the higher DC switching voltage is not sufficient anymore to help maintaining it. Thus, the electric arc extinguishes within a few milliseconds. Usual coupling relays of such type safely switch off loads up to 220 VDC and 10 A – 30 times higher than relays of the same design without blowout magnet.

Purely electronic switching by high-voltage MOSFETs

Another interesting alternative for switching loads at higher DC voltages is the use of modern solid-state relays (SSRs). The key here is the use of high-voltage MOSFETs. So, up to voltages of 300 VDC, switching is done electronically, with no electric arcs ever occurring. Consequently, there is no wear either. Such devices outperform electromechanical relays not only with regard to their service life: they do not bounce, and moreover, switching is fast and completely silent. Even if the solid-state relay can ‘only’ switch loads of up to 300 VDC/1 A, it tops conventional standard relays by a factor of 3 to 5 while offering the above-mentioned advantages. Moreover, the SSR has proven to be space-saving with its overall width of only 6,2 mm.

A third approach to the switching of higher DC loads is the contact series connection of several N/O contacts or N/C contacts of a conventional multi-position coupling relay. Depending on the number of contacts connected in series accordingly, DC switching currents in the low one-digit ampere range can be reached at a switching voltage of 220 VDC. Information on the interruptible current is provided in the relay manufacturer’s load limit curve, if determined for this special type of connection.

Summary

Trouble-free switching even of higher DC loads up to 250 VDC and 10 A can be realised by means of selecting a special coupling relay, preferably with blowout magnet. The use of these powerful devices eliminates the need to expect troubling failures such as those occurring in similar applications with conventional standard relays, where continuous electric arcs occur. In applications with switching voltages of up to 300 VDC as well as maximum currents of 1 A, the high-voltage SSR presented can be an interesting alternative to its electromechanical equivalent. This is because it is only as wide as a terminal block (6,2 mm) and it switches completely wear-free.

For more information contact Sheree Britz, Phoenix Contact, +27 11 801 8200, [email protected], www.phoenixcontact.co.za



Credit(s)



Share this article:
Share via emailShare via LinkedInPrint this page

Further reading:

Rail electrification and EV solutions for integrated transport systems
Electrical Power & Protection
A comprehensive range of solutions for rail electrification and electric vehicles is available from leading technology provider ABB, contributing significantly to integrated and sustainable transport systems.

Read more...
PPS delivers containerised distribution board for Western Cape hybrid power project
Electrical Power & Protection
South African electrical enclosure specialist Power Process Systems has successfully completed the design, fabrication and commissioning of a 4000 A containerised distribution board for a wind/PV solar hybrid renewable energy project on a site in the Western Cape.

Read more...
The choice of a thermal carrier is critical for optimal processing
Electrical Power & Protection
Historically steam, fuelled by coal, has been the most prevalent thermal carrier in South African industry. However, times are changing, with the manufacturing and processing sector needing to review the energy reticulation systems and thermal carriers currently in use.

Read more...
ABB’s blueprint for a net zero future
Electrical Power & Protection
ABB’s Mission to Zero is a strategic initiative aimed at achieving a sustainable future characterised by zero emissions, zero accidents and zero waste.

Read more...
How South Africa’s transformer manufacturing industry can fill a gaping infrastructure gap
ACTOM Electrical Machines Electrical Power & Protection
South Africa’s energy transition is accelerating the demand for power transformers. However, this shift toward renewable energy is exposing a critical infrastructure gap: a severe shortage of transformers.

Read more...
General-purpose 350 W AC-DC power supply
Electrical Power & Protection
The TDK-Lambda GUS350 series of compact single-output general-purpose power supplies addresses the need for an economically priced product while maintaining reliability and quality.

Read more...
Ground-breaking battery tester
Comtest Electrical Power & Protection
Midtronics offers the proven MVT handheld battery tester. This revolutionary tool, powered by MDX-AI, is set to redefine the standards of battery diagnostics and testing in the automotive industry.

Read more...
Green hydrogen could be the missing link in powering the future of technology
Electrical Power & Protection
Green hydrogen has numerous applications across multiple industries. It also has the potential to provide a clean energy source to power future technology, with far-reaching implications for both industry and society.

Read more...
Energy audits pave the pathway to sustainability and savings
Schneider Electric South Africa Electrical Power & Protection
Energy audits serve as essential tools for businesses looking to reduce costs and meet environmental targets. By analysing energy consumption across systems such as lighting, HVAC, ICT and water infrastructure, audits identify inefficiencies and quantify carbon footprints, enabling data-driven decisions for operational and financial optimisation.

Read more...
Passive fire protection for lithium-ion battery risks
Electrical Power & Protection
In response to the growing threat posed by lithium-ion (Li-ion) battery fires, a breakthrough passive fire protection solution is now available in South Africa.

Read more...









While every effort has been made to ensure the accuracy of the information contained herein, the publisher and its agents cannot be held responsible for any errors contained, or any loss incurred as a result. Articles published do not necessarily reflect the views of the publishers. The editor reserves the right to alter or cut copy. Articles submitted are deemed to have been cleared for publication. Advertisements and company contact details are published as provided by the advertiser. Technews Publishing (Pty) Ltd cannot be held responsible for the accuracy or veracity of supplied material.




© Technews Publishing (Pty) Ltd | All Rights Reserved