IT in Manufacturing


New technology automates Modbus routing setup in gateways

October 2017 IT in Manufacturing

For many applications, embracing the IIoT has paid huge dividends. One noticeable trend is the migration of a large number of serial devices to Ethernet-based networks, allowing plant managers to tap the full potential of their legacy devices by unlocking previously unused data.

However, adding value to these serial devices comes at a cost in terms of time and effort, especially when dealing with a large-scale Modbus network. For example, let’s take a look at how the complicated nature of this type of network presents itself in building automation where hundreds to thousands of serial-based temperature controllers communicate via Modbus RTU protocol. These controllers need to be monitored in a control room, which uses Modbus TCP. At this point, the non-interoperability of protocols becomes an issue. A tried and tested solution to overcome non-interoperable protocols is installing high port density Modbus gateways that convert serial to Ethernet, as well Modbus RTU to Modbus TCP, and vice versa. However, designers still have to figure out how many gateways need to be installed and how many serial ports are needed on each gateway. Therefore, planning a network’s topology that involves a large number of Modbus devices to achieve full-fledged connectivity can really test engineers’ mettle.

Reality bites

To engineers, spending too much time and effort on planning a Modbus network’s topology is counter-productive. For example, they find it especially time-consuming to set up a Modbus slave ID routing table, which lists the connections of Modbus devices (Modbus slave IDs) to specific serial ports on a gateway. Adding to the frustration is a high possibility that things might not go according to plan in the field. Connectivity errors at field sites can undo all the meticulous planning in the office within moments, thus, sending engineers back to the drawing table and redoubling their efforts.

A crucial aspect of planning a Modbus network’s topology is to eliminate these connectivity errors when dispatching a large number of Modbus requests to the serial devices that are connected to a Modbus gateway. Life would be so much easier for engineers if they did not have to worry about which serial devices were connected to which serial ports on a Modbus gateway. In an ideal situation, they would be able to just send out Modbus requests to a Modbus gateway, and the latter would automatically find the correct serial port that connects with the target Modbus device. This would iron out many pain points, even when adding new Modbus devices to a system, or connecting existing devices to a different serial port.

The key challenges

Serial-based device response times are generally slower than those of Ethernet-based devices. Their slow response is even more evident when they are connected to a gateway in a daisy-chain topology, as the one-request-one-response nature of a Modbus protocol leads to a longer polling time. In these types of setups, a one-port Modbus gateway delivers better performance because a scada system can communicate independently with each gateway; thus, shortening the communication gap between the large number of Modbus devices and a scada system. However, the management of multiple Modbus gateways is very complicated. Hence, multiport Modbus gateways are more adept at managing a large number of Modbus devices. For example, one 16-port Modbus gateway can replace 16 one-port Modbus gateways. In space-limited applications, it’s a win-win situation that frees up physical space and only requires one power cable and one Ethernet cable. In addition, the large number of IP addresses needed for 16 one-port Modbus gateways can be consolidated into a single IP address. For scada systems, another benefit is lower connection fees as they are normally charged according to the number of connections.

But multiport gateways are not exactly a breeze when it comes to the management of multiple Modbus devices. Engineers first need to segment all the devices into groups and then connect them to a specific port on the gateway. This is why a well-created Modbus slave ID routing table of a gateway’s serial ports is so important, but creating an efficient routing table is time-consuming.

Dispatching a large number of Modbus requests

Unlike Ethernet switches, where routing is accomplished automatically through an ARP table, the routing mechanism for Modbus gateways with multiple ports is much more intricate. Currently, two types of routing mechanisms address the different requirements in Modbus-based networks.

Routing by an IP address or TCP port

Some Modbus gateways perform the serial port mapping functionality via an IP address or TCP port. This mechanism is suitable for engineers who want to monitor field devices in segments. All the Modbus slave devices that are connected to the same serial port through daisy-chain wiring correspond with a specific IP address or TCP port. That is, each serial port on a gateway corresponds with a unique IP address or TCP port. Furthermore, a high-port-density gateway can be used instead of a large number of low-port-density gateways. As previously mentioned, this reduces cabling significantly.

A drawback is that engineers have to manually configure as many IP or TCP connections as the number of serial ports available. In large-scale Modbus environments, systems usually adopt a large number of multiport Modbus gateways, making configuration a time-consuming task – not to mention the extremely high connection fees involved.

Routing by using a gateway’s Modbus-ID routing table

For engineers who care about connection fees and do not need to monitor devices in segments, a more popular option is using a Modbus slave ID routing table. The main purpose of a Modbus slave ID routing table is to indicate which Modbus device (Modbus ID) is connected to which serial port on a gateway. Once a gateway receives a Modbus request for a specific Modbus device, it can dispatch this request via the referring Modbus slave ID routing table to the serial port that connects to the target Modbus device. A scada system benefits by using only one IP address or TCP port to communicate with all the Modbus devices that are connected to a gateway, easing the management of Modbus devices and reducing connection fees considerably.

The Modbus slave ID routing table needs to be maintained for troubleshooting and maintenance, however, creating as well as managing a Modbus slave ID routing table is laborious. Also, it needs to be stressed that when engineers come in contact with a Modbus gateway for the first time, it would be as if they are climbing a mountain as they would be completely unfamiliar with routing table settings. They have to bundle the Modbus slave IDs into groups and then connect each group to a different serial port.

Just one click

A new leading-edge technology that automatically detects the Modbus requests from a scada system and sets up the Modbus slave ID routing table comes in answer to the engineers’ prayers. The Auto-Device Routing function only requires a single click to help the gateway detect which serial port is connected to a target Modbus device, allowing it to automatically dispatch a Modbus request to the correct serial port. It automatically creates the routing table, saving significant time and costs as engineers no longer need to manually create the Modbus slave ID routing table, eliminating possible human error in the process. Furthermore, it eliminates the effort needed to double check the actual connections at field sites. There is no need to refer to a historical Modbus slave ID routing table when adding or removing Modbus devices, saving time and effort.

Conclusion

By automatically creating a routing table, the Auto-Device-Routing technology makes the configuration and maintenance of a gateway’s Modbus slave routing table a thing of the past. This patent-pending function features in Moxa’s MGate MB3000 series, which consists of high-performance Modbus gateways with 2, 4, 8 or 16 serial ports. The series also supports routing by IP address or TCP port.



Credit(s)



Share this article:
Share via emailShare via LinkedInPrint this page

Further reading:

Next-generation road-legal race car.
Siemens South Africa IT in Manufacturing
Siemens Digital Industries Software has announced that Briggs Automotive Company (BAC) will move to the Siemens Xcelerator portfolio of industry software and use it to develop the next generation of its single-seater road-legal race car, Mono.

Read more...
Cybersecurity at a crossroads
IT in Manufacturing
here’s a growing unease in boardrooms, data centres and cabinet offices across South Africa. It’s not just about economic headwinds or political uncertainty, it’s about something quieter, more technical and yet just as dangerous - the rising tide of cyber threats.

Read more...
Enabling a sustainable industrial organisation
IT in Manufacturing
This article explains the top sustainability trends and key actions that you can leverage to become a more sustainable organisation.

Read more...
Navigating discrete manufacturing in South Africa through digitalisation
IT in Manufacturing
South Africa’s discrete manufacturing sector faces mounting pressure from global competition, fragmented supply chains and outdated infrastructure. In this complex environment, digitalisation is a critical lever for survival, resilience and growth.

Read more...
Africa’s pragmatic approach to AI and how data centres are enabling it
Schneider Electric South Africa IT in Manufacturing
In Africa, the current AI momentum is driven by a fundamental need, building a resilient digital infrastructure that addresses the real-world challenges of the continent’s communities.

Read more...
World first simulation of error-correctable quantum computers
IT in Manufacturing
Quantum computers still face a major hurdle on their pathway to practical use cases, their limited ability to correct the arising computational errors. In a world first, researchers from Chalmers University of Technology in Sweden have unveiled a method for simulating specific types of error-corrected quantum computations.

Read more...
Platform to accelerate supply chain decarbonisation
Schneider Electric South Africa IT in Manufacturing
Schneider Electric has launched Zeigo Hub by Schneider Electric, a powerful new digital platform designed to help organisations decarbonise their supply chains at scale.

Read more...
Future-ready data centres
IT in Manufacturing
The white paper ‘Future-Ready Data Centres’ by Black & Veatch outlines how integrating sustainable design principles not only helps meet ESG goals but also ensures reliability, operational efficiency and business continuity in the face of climate change and growing digital demand.

Read more...
Sustainable energy management
Siemens South Africa IT in Manufacturing
Utilising its innovative ONE approach technology, Siemens provides complete transparency on resource consumption and offers data-driven optimisation recommendations for sustainable energy management.

Read more...
Harnessing the power of OT networking
RJ Connect Fieldbus & Industrial Networking
Businesses are increasingly embracing IT/OT convergence to stay ahead and capitalise on advantages such as smarter factories and higher efficiency. This article provides practical insights and guidance to help you navigate these challenges effectively.

Read more...









While every effort has been made to ensure the accuracy of the information contained herein, the publisher and its agents cannot be held responsible for any errors contained, or any loss incurred as a result. Articles published do not necessarily reflect the views of the publishers. The editor reserves the right to alter or cut copy. Articles submitted are deemed to have been cleared for publication. Advertisements and company contact details are published as provided by the advertiser. Technews Publishing (Pty) Ltd cannot be held responsible for the accuracy or veracity of supplied material.




© Technews Publishing (Pty) Ltd | All Rights Reserved