Pressure Measurement & Control


Technical terms used when specifying pressure transducers

July 2002 Pressure Measurement & Control

As it is with all matters technical, it is important that all involved are familiar with the terms used in any discussion or enquiry. This article looks at the data it is customary to quote in technical descriptions of pressure sensors, pressure transducers and pressure measuring converters, with a view to familiarising the reader with what is meant by terms that are used.

Measuring range/measuring span

The measuring range is the span between the start and the end of the measurements. The error limits quoted in the data sheet apply within this measuring range. The type of pressure, eg positive relative pressure (overpressure), negative relative pressure (underpressure), absolute pressure or pressure difference, is also specified in order to define the measuring scope.

Overload range

The overload range defines the pressures to which a pressure-measuring converter can be exposed without it suffering permanent damage, eg zero-point offset. The pressure-measuring converter is allowed to deviate from its specified technical data in this span between the measuring range and overload limit. The overload limit is usually defined by the sensor's principle of operation.

With piezoresistive pressure measuring converters the overload pressure is identical with bursting pressure. In the case of thin-film pressure measuring converters, on the other hand, there are notable differences between overload pressure and bursting pressure. This is owing to the sensor materials silicon and stainless steel. While steels enter a flow phase when they exceed their resilient range, brittle materials display a linear characteristic up to bursting point.

Figure 1. Stress-strain curve of stainless steel/silicon
Figure 1. Stress-strain curve of stainless steel/silicon

Bursting pressure

Bursting pressure defines the pressure range which, if exceeded, can lead to the total destruction of the pressure measuring converter and hence to a loss of process medium.

Auxiliary energy

An auxiliary energy supply is required to operate pressure transducers and pressure measuring converters. The most widespread solution is a direct voltage of 24 V. Thanks to the use of voltage-stabilising components, pressure-measuring converters usually have a bigger supply voltage range of eg 10 to 30 V d.c. Within this range any supply voltage variation has no effect on pressure readings. For example, if the pressure measuring converter is calibrated in the factory with an auxiliary voltage of 24 V d.c. there should be no change of accuracy if the converter is actually operated with just 12 V d.c. The effects of supply voltage variations should not greatly exceed 0,1% per 10 V.

Output signal (analog, digital)

Current and voltage signals have become established as the main alternatives for output signals. Exactly which output signal is selected will depend mainly on the indicating and control devices, which follow on after the pressure-measuring converter. As a general rule it can be said that current signals are more immune to interference during transmission than voltage signals.

Systems with 4 to 20 mA in 2-conductor technology have become very popular in industrial plants. The main feature of this (loop powered) technology is that the auxiliary energy and measuring signal are both carried over the same connection lines, which for elaborate installations signifies a notable saving in wiring costs. At the same time the higher zero point (4 mA) enables the measuring position to be monitored for open circuits and device failure, because in these cases the flow of current would drop below 4 mA. This change can be used in the evaluation units, eg to trigger an alarm.

From the automotive industry there is also an increasing demand for so-called ratiometric voltage signals. This means, for example, that the supply voltage range is defined as 5 V ±10% and the output signal specified as 0,5 to 4,5 V d.c. ±10%. If the supply voltage amounts, for example, to 4,5 V (-10% of the nominal range), the output signal will equal 4,0 V (4,5 V less 10%). This output signal saves several electronic components and enables cheaper pressure measuring converters. With current outputs the permissible load is specified in addition to the output value. This load is called the maximum permissible load impedance.

RA (Ohm) = (UB [V] - UBmin)/0,02 [A]

where:

RA = load impedance in ohms

UB = actual supply voltage in volts

UBmin = minimum permissible supply voltage quoted in the data sheet

In practical applications the actual load used should be far smaller than the maximum permissible load in order to rule out measuring errors due to excessively high contact resistances. There is also a certain demand for frequency outputs in special applications, eg mining. Yet another form of signal now gaining importance is the digital output signal, which with the right software can then be processed directly in microprocessor-controlled systems.

Response time

The response time defines the period of time needed by the output signal when there is a sudden change of pressure. It is usually quoted within a range of 10 to 90% of the measuring range.

With modern sensor principles the response time is very brief because of the slight travel of the diaphragms. When specifying the response time, the user must consider whether he requires a continuous signal or, for example, whether he has to be able to measure at high speed in order to detect any pressure peaks. Normally the necessary damping of the signal is performed by the amplifier electronics.

Class accuracy and conformity error

The conformity error is quoted as a numerical value in percent of the full-scale deflection and usually specifies the maximum deviation of the measured characteristic curve from the ideal line between the start and end of the measurement. This is possible because DIN states that only the maximum single error from linearity, reproducibility and hysteresis is decisive for the conformity error. With modern sensor systems, hysteresis and reproducibility are negligible.

Figure 3. Minimum value calibration
Figure 3. Minimum value calibration

In the case of imported pressure measuring converters, the conformity error is often accompanied by the abbreviation BFSL (best fit straight line). This measuring method, also known as the tolerance band method, calculates the initial lines, which are then applied to the actually measured values to keep the deviations as small as possible. This method is also accepted by DIN16 086 as a specification, but the method of determination must be quoted. Often this is not done, however, which means that it is usually impossible for the user to compare the quoted levels of accuracy. As a rule of thumb it is possible to quote a factor of two for the difference in accuracy between limit point calibration and minimum value calibration (1% with the limit point calibration method equals approximately 0,5% with minimum value calibration in accordance with BSFL).

Figure 4. Hysteresis curve
Figure 4. Hysteresis curve

Hysteresis

Hysteresis is the difference observed in the output signal when the pressure applied is in the process of rising or falling through the value being measured. With diaphragm deflections in the mm-range, today's sensor technologies usually have hysteresis values of significantly less than 0,1%.

Figure 2. Limit point calibration
Figure 2. Limit point calibration

Temperature ranges

Process fluid temperature

The process fluid temperature defines the range of temperature that the process fluid may take on without the pressure-measuring converter departing from its quoted specifications. Pressure measuring transducers with an integrated cooling section are used if the process fluid temperatures are high, eg up to 150°C (Figure 5). Chemical seals need to be fitted for process fluid temperatures of up to 400°C.

Figure 5. Pressure measuring transducer with integrated cooling section
Figure 5. Pressure measuring transducer with integrated cooling section

Ambient temperature

The ambient temperature defines the range to which the pressure measuring converter can be exposed without it departing from its technical specifications and suffering any damage to its casing or electrical connection.

Compensated temperature range

The most important item of data for the permissible temperature limits is the compensated temperature range. The temperature errors with corresponding temperature coefficients quoted in the specifications apply within these limits. This is where mistakes are often made if it is assumed that no additional temperature error occurs in the compensated range. In practice this means having to add the temperature error with its temperature coefficients to the error quoted as class accuracy when operating under changing temperatures. The coefficients depend mainly on the sensor systems used and are conditional on the corresponding internal compensation.

Individual compensation data for each particular pressure-measuring converter can be established by an analog-digital circuit arrangement and be saved in the integrated memory. Compensated pressure measuring converters of this type display no additional temperature errors within a specially defined temperature range.

Forms of electrical connection

Among electrical connections there is a continuing trend toward using 4-pole right-angle plugs in accordance with DIN 43659. Today the most popular choice for low-price pressure measuring converters are 6-4A 1 MMT appliance plus. Installation and replacement is far easier with both of these plug systems than with cable outlets, for example.

Cable outlets are needed if the plug systems are unable to meet the requirements on protection standards. This is nearly always the case with so-called well probes or level probes. Here the demand for water-tightness at submerged depths of up to 250 m can only be met by means of specially designed cable outlets (glands).

For more information contact: Greg Rusznyak, Wika Instruments, tel: 011 621 0000.



Credit(s)



Share this article:
Share via emailShare via LinkedInPrint this page

Further reading:

Rapid, precise pressure control for industrial applications
WIKA Instruments Pressure Measurement & Control
The CPC3050 high-speed pressure controller delivers rapid, precise pressure control for industrial applications, achieving three-point verification in ten seconds.

Read more...
Differential pressure measurement in gas extraction and power generation project
VEGA Controls SA Pressure Measurement & Control
Methane exploration and extraction in Lake Kivu in the East African Rift Valley has primarily focused on gas composition analysis. The VEGABAR 82 pressure transmitter was used for differential pressure measurement, the key to monitoring gas levels within the lake.

Read more...
Unique industrial asset monitoring solution
WIKA Instruments Sensors & Transducers
WIKA WikaPredict offers a unique industrial asset monitoring solution, combining advanced sensors and artificial intelligence. As a leader in predictive maintenance, it helps clients enhance operational performance and increased efficiency.

Read more...
Don’t buckle under pressure
VEGA Controls SA Pressure Measurement & Control
In Africa, urban populations are increasing and infrastructure is expanding at an unprecedented pace. This makes sustainable water management and treatment more crucial than ever. By investing in VEGA pressure instrumentation, water utilities and municipalities are equipping themselves with pressure sensors that facilitate sustainable water management focused on efficiency, reliability and resilience.

Read more...
VEGA handles the pressures of water treatment systems
VEGA Controls SA Pressure Measurement & Control
A water treatment system for a major metropolitan area in the Midwestern United States demands careful monitoring and management of processes across its sprawling network. Choosing VEGA for its process automation needs meant more than just obtaining precise and reliable pressure sensors.

Read more...
Monitoring the health of systems
SA Gauge Pressure Measurement & Control
Pressure and temperature gauges are vital instruments in various industries. However, they are susceptible to failures that can compromise their accuracy and reliability. When these gauges fail, the consequences can be severe.

Read more...
Enhancing beer brewing precision
VEGA Controls SA Pressure Measurement & Control
Brewing beer is a complex process that requires utmost precision in every step. To ensure precision, it is crucial to measure and control the pressure and point levels in the wort kettle and hops dissolver. Using VEGA instrumentation can offer numerous benefits to breweries.

Read more...
Greener mining through water management strategies
VEGA Controls SA Pressure Measurement & Control
Water scarcity is a pressing concern in South Africa, leading to the establishment of stricter regulations on water discharge and management. To promote greener mining operations that minimise environmental impact and optimise resource utilisation, responsible dewatering practices are essential.

Read more...
Pressure sensors for hydrogen applications
Instrotech Pressure Measurement & Control
Keller manufactures isolated piezoresistive pressure sensors. The great advantage of the piezoresistive measuring principle is its high stability.

Read more...
A new approach to milk processing
VEGA Controls SA Pressure Measurement & Control
Ensuring the quality and safety of milk throughout the production process is of the utmost importance in the dairy industry. Process instrumentation plays a vital role in this stage by providing accurate measurements of level, pressure and point level to guarantee optimal storage conditions.

Read more...