Electrical Power & Protection


Power quality at the service panel

October 2023 Electrical Power & Protection

Voltage sags, tripping breakers, overheated electrical panels, and excessive voltage levels indicate possible trouble in an electrical distribution system. Where do you begin the search to isolate the exact cause of these power quality problems? As a common point for branch circuit distribution, the service panel is a convenient place to take the pulse of your electrical system. Several problems can be located right in the service panel itself. For issues elsewhere in the system, measurements at the service panel can tell you where to look next. A quick visual inspection can catch some problems, while others require that measurements to be taken.

This article outlines a step-by-step process for locating and fixing potential trouble spots. Various tools can be used for power quality troubleshooting, from digital multimeters to handheld single- and three-phase power quality analysers that perform many calculations automatically.

Voltage level and stability

The first step in checking to see if voltage levels and stability are the culprits is to measure voltage levels of the branch circuits at the load side of the branch circuit breakers. If voltage levels are low at the breaker, they will be even lower at the receptacle. This could be caused by low tap settings at the transformer. Other likely culprits include loose connections, long feeder runs and overloaded transformers, which create excessively high source impedance.

If intermittent voltage sags are suspected, start at the panel to isolate the cause. Are the sags the result of loads on the same branch circuit, or are they caused by loads elsewhere in the distribution system? We can start isolating the source with a multi-channel recording instrument such as the Fluke power quality analyser, which can monitor trends in voltage and current simultaneously.

Upstream, downstream

What information are you looking for from the trend plots? If a voltage sag occurs simultaneously with a current surge, it is caused by a load on the branch circuit. The cause of the sag is downstream of the measurement point, and therefore can be regarded as a load-related disturbance.

If, on the other hand, the voltage sag coincides with a very small change in current, the sag was likely caused by something upstream of the measurement point and can be thought of as a source-related disturbance. Typically these are heavily loaded three-phase motors started across the line, or sags originating on the utility feed. If the sag approaches an outage, the cause is more likely to be the utility. The event probably reflects a fault and breaker trip, followed by automatic breaker reclosure.

Current balance and loading

To check the current balance and loading, measure each feeder phase and current on each branch circuit. It is critically important to use a true-rms clamp or true-rms digital multimeter with a clamp-on accessory. An average responding clamp-on meter will not provide an accurate measurement, as the combination of fundamental and harmonic current makes this a distorted waveform. A lower cost average-sensing meter will tend to read low, leading you to assume that the circuits are more lightly loaded than they are.

Harmonics

To check for the presence and level of harmonics, measure the current on the feeder neutral. This will typically be in the 80 to 130% range of the feeder current, because the third harmonic will add up in the neutral.

Grounding

Neutral ground bonds in subpanels are a violation of the NEC, and of power quality performance wiring. Neutral ground bonds should be made at the transformer, even though the NEC permits it to be made at the main panel. It should never be made downstream of the main panel, whether at a subpanel or a receptacle. When a neutral ground bond is made at a subpanel or receptacle, the ground path becomes a parallel return path for normal load current, resulting in measurable current on the ground.

Hot spots

Poor connections and the resulting heat losses are the single most significant source of system inefficiency. Loose terminations contribute significantly to excessive source impedance. Fortunately, they are easy to locate with a simple infrared thermometer. Infrared measurements with tools like the Fluke 60 Series are a safe and effective technique for the non-contact detection of panel hot spots.

Circuit breakers

Measurements of circuit breaker voltage drop can help us determine the condition of the breaker. Measure across the line-to-load side of the branch breaker. If the voltage drop exceeds 100 mV, the breaker should be replaced.

In summary, the service panel is the crossroads of the building’s electrical system. From here an experienced electrical troubleshooter can locate and fix any problems.

Product: https://bit.ly/3sQ4GQ4


Credit(s)



Share this article:
Share via emailShare via LinkedInPrint this page

Further reading:

Schneider Electric introduces next-generation BlokSeT switchboard
Schneider Electric South Africa Electrical Power & Protection
Schneider Electric has launched its next-generation BlokSeT low-voltage switchboard in West Africa, offering high reliability, predictive maintenance capability and digital integration for critical infrastructure and industrial applications.

Read more...
Powering South Africa’s renewable energy expansion
Electrical Power & Protection
ACTOM Distribution Transformers, the sole NECRT contract holder for Eskom, is powering South Africa’s renewable energy expansion through robust neutral earthing transformer solutions deployed across solar and wind projects in southern Africa.

Read more...
You can’t digitise a blackout
Schneider Electric South Africa Electrical Power & Protection
Across East Africa, smart meters and AI promise cleaner, more reliable power, but digital tools cannot optimise a grid too weak to carry the load. Schneider Electric’s Symphrose Ochieng sets out why operators should strengthen physical infrastructure first, then add digital capability in phases.

Read more...
Battery energy storage is key to powering South Africa’s manufacturing sector
Electrical Power & Protection
South Africa’s shift to renewables is creating a significant opportunity in battery energy storage, but local manufacturers face an uphill battle against cheap imports and stop-start demand. Richard van Moltke of ACTOM Static Power examines what it will take to build a sustainable local battery storage industry.

Read more...
Decarbonisation is reshaping mining strategy in Africa
Schneider Electric South Africa IT in Manufacturing Electrical Power & Protection
Mining companies across Africa are embedding decarbonisation into operational strategy, driven by investor, regulatory and customer pressure to reduce emissions while improving resilience.

Read more...
How to tell whether your mini-substation is new or refurbished
Electrical Power & Protection
Cosmetically refurbished mini-substations are being misrepresented as new equipment and sold back into the market, posing serious reliability and safety risks for mining, industrial and commercial operations. Trafo Power Solutions explains what to look for and what questions to ask before purchasing.

Read more...
Optimising energy reliability for African manufacturing
Electrical Power & Protection IT in Manufacturing
Unreliable power can cost African manufacturers as much as 31% in sales. Behind-the-meter power offers manufacturers in sub-Saharan Africa control, visibility and resilience in their energy provisioning.

Read more...
Electrical solutions for FMCG manufacturing giant
Electrical Power & Protection
An electrical upgrade at a leading fast-moving consumer goods facility demonstrates how ACTOM Kenya turned a fragile, reactive power infrastructure into a resilient, data-driven backbone for production. The project is also a case study in bridging legacy equipment with modern automation without disrupting operations.

Read more...
Yokogawa digital plant to accelerate green hydrogen revolution
Yokogawa South Africa Editor's Choice Electrical Power & Protection IT in Manufacturing
Yokogawa explains how a digital plant approach and autonomous operations can integrate the full green hydrogen value chain, from renewable power generation to end-use applications, and why digitalisation and system integration are central to making green hydrogen viable in South Africa.

Read more...
Power and energy meter with Modbus RTU interface
Vepac Electronics Electrical Power & Protection
The eCap universal power and net quality meter measures voltages, currents, power, power factor, energy, frequency and total harmonic distortion, with fully galvanically isolated transmission via an integrated Modbus RTU/RS485 interface.

Read more...









While every effort has been made to ensure the accuracy of the information contained herein, the publisher and its agents cannot be held responsible for any errors contained, or any loss incurred as a result. Articles published do not necessarily reflect the views of the publishers. The editor reserves the right to alter or cut copy. Articles submitted are deemed to have been cleared for publication. Advertisements and company contact details are published as provided by the advertiser. Technews Publishing (Pty) Ltd cannot be held responsible for the accuracy or veracity of supplied material.




© Technews Publishing (Pty) Ltd | All Rights Reserved