Electrical Power & Protection


Power quality at the service panel

October 2023 Electrical Power & Protection

Voltage sags, tripping breakers, overheated electrical panels, and excessive voltage levels indicate possible trouble in an electrical distribution system. Where do you begin the search to isolate the exact cause of these power quality problems? As a common point for branch circuit distribution, the service panel is a convenient place to take the pulse of your electrical system. Several problems can be located right in the service panel itself. For issues elsewhere in the system, measurements at the service panel can tell you where to look next. A quick visual inspection can catch some problems, while others require that measurements to be taken.

This article outlines a step-by-step process for locating and fixing potential trouble spots. Various tools can be used for power quality troubleshooting, from digital multimeters to handheld single- and three-phase power quality analysers that perform many calculations automatically.

Voltage level and stability

The first step in checking to see if voltage levels and stability are the culprits is to measure voltage levels of the branch circuits at the load side of the branch circuit breakers. If voltage levels are low at the breaker, they will be even lower at the receptacle. This could be caused by low tap settings at the transformer. Other likely culprits include loose connections, long feeder runs and overloaded transformers, which create excessively high source impedance.

If intermittent voltage sags are suspected, start at the panel to isolate the cause. Are the sags the result of loads on the same branch circuit, or are they caused by loads elsewhere in the distribution system? We can start isolating the source with a multi-channel recording instrument such as the Fluke power quality analyser, which can monitor trends in voltage and current simultaneously.

Upstream, downstream

What information are you looking for from the trend plots? If a voltage sag occurs simultaneously with a current surge, it is caused by a load on the branch circuit. The cause of the sag is downstream of the measurement point, and therefore can be regarded as a load-related disturbance.

If, on the other hand, the voltage sag coincides with a very small change in current, the sag was likely caused by something upstream of the measurement point and can be thought of as a source-related disturbance. Typically these are heavily loaded three-phase motors started across the line, or sags originating on the utility feed. If the sag approaches an outage, the cause is more likely to be the utility. The event probably reflects a fault and breaker trip, followed by automatic breaker reclosure.

Current balance and loading

To check the current balance and loading, measure each feeder phase and current on each branch circuit. It is critically important to use a true-rms clamp or true-rms digital multimeter with a clamp-on accessory. An average responding clamp-on meter will not provide an accurate measurement, as the combination of fundamental and harmonic current makes this a distorted waveform. A lower cost average-sensing meter will tend to read low, leading you to assume that the circuits are more lightly loaded than they are.

Harmonics

To check for the presence and level of harmonics, measure the current on the feeder neutral. This will typically be in the 80 to 130% range of the feeder current, because the third harmonic will add up in the neutral.

Grounding

Neutral ground bonds in subpanels are a violation of the NEC, and of power quality performance wiring. Neutral ground bonds should be made at the transformer, even though the NEC permits it to be made at the main panel. It should never be made downstream of the main panel, whether at a subpanel or a receptacle. When a neutral ground bond is made at a subpanel or receptacle, the ground path becomes a parallel return path for normal load current, resulting in measurable current on the ground.

Hot spots

Poor connections and the resulting heat losses are the single most significant source of system inefficiency. Loose terminations contribute significantly to excessive source impedance. Fortunately, they are easy to locate with a simple infrared thermometer. Infrared measurements with tools like the Fluke 60 Series are a safe and effective technique for the non-contact detection of panel hot spots.

Circuit breakers

Measurements of circuit breaker voltage drop can help us determine the condition of the breaker. Measure across the line-to-load side of the branch breaker. If the voltage drop exceeds 100 mV, the breaker should be replaced.

In summary, the service panel is the crossroads of the building’s electrical system. From here an experienced electrical troubleshooter can locate and fix any problems.

Product: https://bit.ly/3sQ4GQ4


Credit(s)



Share this article:
Share via emailShare via LinkedInPrint this page

Further reading:

Real-time modelling is the key to a resilient, bi-directional energy future
Schneider Electric South Africa Electrical Power & Protection
South Africa’s electrical grid is a classic example of a traditional power system, designed for one-way energy flow. This linear model worked well for decades. Today, however, it is being fundamentally disrupted, as South Africa’s ongoing energy crisis has sparked large-scale investment in distributed energy resources.

Read more...
The value of hybrid microgrids in resolving energy issues
Electrical Power & Protection
Etienne le Roux, business development manager at Aggreko, examines the value of hybrid microgrids in resolving costs, energy expectations and climate compliance.

Read more...
Are South African businesses ready for businesses to go off-grid?
Electrical Power & Protection
South Africa’s energy market is changing fast. For many companies, off-grid is no longer just a backup option or a safety net. It is the strategic choice for energy security, sustainability and predictable costs.

Read more...
Earth leakage relay
Vepac Electronics Electrical Power & Protection
The ELR01PN from Vepac measures highly sensitive currents of 0,06 mA to 1 A and continuously displays them via an LED bar indicator.

Read more...
ABB cuts emissions and advances Mission to Zero in Argentina
Electrical Power & Protection
ABB’s electrification manufacturing plant in Argentina has achieved a major sustainability milestone under ABB’s global Mission to Zero programme.

Read more...
ABB advances low-carbon, energy-resilient manufacturing
Electrical Power & Protection
ABB is advancing its Mission to Zero programme, demonstrating how onsite renewable energy, electrification and digital energy management can deliver meaningful emissions reductions while strengthening energy resilience.

Read more...
Energy efficiency as a service
Schneider Electric South Africa Electrical Power & Protection
Energy efficiency as a service shifts the financial burden from capital expenditure to operational expenditure. This allows commercial property managers and owners to retrofit existing facilities with energy-efficient solutions and monitoring technology without the need for upfront costs.

Read more...
Trafo Power Solutions delivers mobile substation solution to Australian mine
Electrical Power & Protection
Trafo Power Solutions has designed and supplied a robust skid-mounted transformer solution for an opencast mine in Queensland.

Read more...
Rethinking power for Africa’s data centres
Schneider Electric South Africa Electrical Power & Protection
If Africa wants resilient, competitive and sustainable data centres, the starting point must be a grid-to-chip architecture rather than a genset-first mentality.

Read more...
Effective monitoring of solar panels for dust and debris
Senseca Electrical Power & Protection
To assist in the quick monitoring of solar panels for dirt, Senseca has introduced the Dust Fall Monitoring System, which alerts control centre operators at photovoltaic solar farms utilising solar panels when their panels need to be cleaned.

Read more...









While every effort has been made to ensure the accuracy of the information contained herein, the publisher and its agents cannot be held responsible for any errors contained, or any loss incurred as a result. Articles published do not necessarily reflect the views of the publishers. The editor reserves the right to alter or cut copy. Articles submitted are deemed to have been cleared for publication. Advertisements and company contact details are published as provided by the advertiser. Technews Publishing (Pty) Ltd cannot be held responsible for the accuracy or veracity of supplied material.




© Technews Publishing (Pty) Ltd | All Rights Reserved