Control loop: Case History 165 - Interesting tests on loop problems show how much can be deduced from the results.

March 2019 Motion Control & Drives

I have published many articles showing problems in control loops with figures showing the tests conducted to determine the problems. This time, by way of a change, I would like to suggest that readers first study the figures, and try to determine what can be deduced from these.

Figure 1.
Figure 1.

Figure 1

Figure 1 is an ‘as-found’ closed loop test (i.e. a test with the controller in automatic and using the existing tuning parameters) on an air flow loop in a metallurgical plant in Portugal, where I recently did some work. Have a good look at it and see what you think is wrong. Then carry on reading below.

This is what can be determined from the test:

• It can be seen that the PV (process variable) never actually settles at setpoint, and that after the SP (setpoint) changes it still does not get there but slowly ramps it.</i> This is an indication on a fast process like flow that the integral setting is far too slow.

• On the SP changes it can be seen that there is a big kick in the PD (controller output) and then the PV tends to cycle, with about 1,5 cycles on the SP change upwards, and about two full cycles when the SP was stepped back down. This indicates two things are wrong:

1. The proportional gain is far too big and the tuning is actually close to instability.

2. There is a strong possibility that the valve has non-linear installed characteristics, so the response is slower in the higher ranges and faster as the PV gets lower.

• The PV and the PD are working at extremely low values in a region well below 10%, which is in fact the region where they normally operate. Working so low down is very bad practice. Firstly, most flow measuring methods do not work well at very low ranges, and may in fact be terribly inaccurate and possibly give incorrect readings; this obviously depends on the type of flow measurement being used. In this case it was a vortex shedding flowmeter. The specifications for this were not available onsite, but I strongly suspect that the measuring span of the meter is far too wide. Secondly, as far as the valve is concerned, it is a well-known ‘rule of thumb’ that under normal operating conditions the valve should operate above the 20% mark. All sorts of control problems can occur with valves working close to seat. It is also pretty obvious that the valve must be largely oversized, which is a bad thing for various reasons that are covered in other articles.

Figure 2.
Figure 2.

Figure 2

Figure 2 shows an open loop test, on the previous system, with equal step changes in PD being made in both directions with the controller in manual. Unfortunately it is hard to actually determine deadtime and lag times from the figure without being able to zoom in and see more details, but let it suffice to say that if you could you would have found that the deadtime was about five seconds and time constant about nine seconds, which was repeatable on most of the steps. Bearing this in mind, what would you deduce?

This is what you should be able to come up with:

• The response in the first three steps was rather slow compared with subsequent steps, which would indicate that the valve was pretty sticky and then loosened up a bit. The latter steps also gave a rather peculiar response for a flow loop with a sudden change in the PV, which then slowed down taking quite a while to get to the final position. Again, this would indicate stickiness in the valve with the positioner forcing the valve to the final position.

• Normally flow loops with pneumatically actuated valves have deadtimes around 1-2 seconds and time constants about the same. The excessive deadtime and slow time constant in this particular case indicate that the valve is really sticky and that the positioner is working hard to get it to the right place.

• The three steps downwards in the middle of the test confirmed the quite badly installed non linearity of the valve, with the last step being almost three times bigger than the first.

The controller was then retuned using the largest steps at the low end of the range.

The original tuning was P = 3, and I = 120 seconds/repeat. This confirms the original deductions made when looking at the ‘as-found’ closed loop test, i.e. too high a gain, and too long an integral.

New tuning was then set at P = 0,9, and I = 10 seconds/repeat. Figure 3 shows the loop running in automatic with the new values and steady SP. There is a small cycle on the loop. The question is: Is this instability due to bad tuning, or is there another reason?

Figure 3.
Figure 3.

Generally, people with little knowledge of practical process control would say that it is due to bad tuning, and this is probably why the original values were chosen to operate so slowly – so that it did not cycle. However, the integral was then so long that it never got to setpoint, so the person who tuned tried to compensate by increasing the gain.

The cycle is in fact a fairly typical ‘stick-slip’ cycle, which I have discussed in quite a few previous articles. It is caused when the positioner cannot get the valve to exactly the right position. The valve sticks and then the integral action in the controller, now with correct tuning, is relatively fast and so keeps ramping until the valve does actually move. This causes the positioner to push too much pressure into the actuator, which then forces the valve to ‘slip’ and overshoot the set point. The whole thing then repeats in the opposite direction. The stick-slip cycle is immediately identified by the saw-tooth waves on the controller output, which are more or less pure ramps due to the constant integrating error.

In reality, the cycle which looks terrible in the figure due to the expanded scale, has an extremely small amplitude of about 0,5%, and can be completely ignored. It will not affect the life of the valve to any noticeable extent. Also, if the recommendations are followed and if the valve is serviced, the cycle would probably disappear.

It is most interesting how logical conclusions can be deduced from correct interpretation of the results generated by these types of analytical and tuning tests.

Michael Brown is a specialist in control loop optimisation with many years of experience in process control instrumentation. His main activities are consulting, and teaching practical control loop analysis and optimisation. He gives training courses which can be held in clients’ plants, where students can have the added benefit of practising on live loops. His work takes him to plants all over South Africa and also to other countries. He can be contacted at Michael Brown Control Engineering cc, +27 82 440 7790, [email protected], www.controlloop.co.za



Credit(s)



Share this article:
Share via emailShare via LinkedInPrint this page

Further reading:

The opportunity and impact of MEPS electric motor regulations
WEG Africa Motion Control & Drives
South African companies are gearing up for the new Minimum Energy Performance Standards, part of a global trend towards energy-efficient electric motors.

Read more...
Custom mining solutions from Bühler at MTE Richards Bay
Motion Control & Drives
Bühler recently showcased its advanced material handling solutions at the Mining & Technical Exhibitions (MTE) in Richards Bay.

Read more...
SKF’s integrated triple-action solution drives operational value for customer in Cameroon
Motion Control & Drives
SKF has successfully delivered a powerful, integrated solution to a leading metals industry customer in Cameroon, combining advanced condition monitoring and high-performance bearings, underpinned by professional, expert services.

Read more...
Innomotics electrifies major mining operation in Chile
Motion Control & Drives
Innomotics has been awarded a major electrification project to support an important mining operation in northern Chile.

Read more...
Power meets precision
Motion Control & Drives
Swiss drive technology specialist, maxon is presenting the second generation of its compact mid-motor for e-bikes, the BIKEDRIVE AIR S. This new system delivers a high torque of 90 Nm with a motor weight of two kilograms.

Read more...
Referro Systems expands local market
Motion Control & Drives
Referro Systems has achieved notable growth since introducing Advanced Micro Controls (AMCI) products into the African market.

Read more...
Control solution for highly dynamic.
Motion Control & Drives
The motion control specialist, Aerotech is expanding its Auto-mation1-iSMC control solution with a powerful feature for highly dynamic laser drilling with galvo scanners.

Read more...
SEW-EURODRIVE energy audits help farmers drive down irrigation costs
Motion Control & Drives
SEW-EURODRIVE is expanding its support to South Africa’s agricultural sector by leveraging its world class expertise in energy audits for drive systems, helping farmers unlock cost savings and improve operational efficiencies in irrigation applications.

Read more...
Smart automated lubrication
SKF South Africa Motion Control & Drives
A leading customer of SKF in Tunisia’s paper and pulp industry was facing significant challenges with the manual lubrication of its paper machine. SKF had the solution.

Read more...
Driving heavy equipment industry
Motion Control & Drives
Cimolai Technology, a leader in the design, production and installation of lifting and handling equipment, has adopted the Siemens Xcelerator portfolio of industry software. This move aims to deliver innovative, reliable and custom-made solutions to meet the most demanding technical specifications across sectors such as shipyards, infrastructure and heavy industry.

Read more...









While every effort has been made to ensure the accuracy of the information contained herein, the publisher and its agents cannot be held responsible for any errors contained, or any loss incurred as a result. Articles published do not necessarily reflect the views of the publishers. The editor reserves the right to alter or cut copy. Articles submitted are deemed to have been cleared for publication. Advertisements and company contact details are published as provided by the advertiser. Technews Publishing (Pty) Ltd cannot be held responsible for the accuracy or veracity of supplied material.




© Technews Publishing (Pty) Ltd | All Rights Reserved