Alarm systems and their role in abnormal situation management: Part IV of IV

September 2000 Maintenance, Test & Measurement, Calibration

In the last of a four-part article, we look at the correct ranging of transmitters and methods of suppressing redundant alarms.

The importance of correctly ranged transmitters to cover all of the alarm settings is often overlooked, specifically on level applications. If we take for example a level installation, the transmitter must cover the range of any level switches or an additional transmitter used for trip purposes. Typically one would set the low and high level 'control' transmitter pre-trip alarms at say 25 and 75%, with the trip switches at 5 and 95% of the control transmitter range. How often have you seen level switches installed outside of the indicating or control transmitter range? There should always be sufficient time between a pre-trip alarm and a trip alarm setting for the control system or operator to attempt corrective action, if there is not, then there is little point in having a pre-trip alarm. Trip or safety related alarms should always be implemented in a separate measurement loop and system to the normal process control system. This also applies to field instrument process connections in order to eliminate a source of common mode failure. This is a requirement of IEC 61508, for applications above SIL 1. It is good design practice to display the actual trip value on the same control system (DCS) instrument tag faceplate, as the pre-trip alarm setting. This will then always be visible to the operator as the process variable approaches the actual trip point, how much beyond can also be important for equipment stress, not to mention human stress at the time. This actual trip setting is required should the trip protection instrument be on override for test or maintenance, as the operator must know when to safely actuate the Manual Trip, but how often is this trip setting displayed to the operator? It is important to document all alarm settings and relevant information on an alarm/trip schedule, refer to Figure 1 for a typical example. This schedule includes information not normally presented, such as 'operator response' as well as 'consequence of no response' and 'suppression requirements'. This is critical information in assessing the need for alarms and allocating their respective priority. This important schedule must be available for the unit HAZOP and form part of the plant-operating manual; needless to say, it should be kept up-to-date, which raises the thorny issue of 'change management'.

Figure 1. Typical alarm/trip schedule
Figure 1. Typical alarm/trip schedule

Alarm suppression

There are four basic methods for automatically suppressing alarms, which will probably cover 95% of all 'nuisance' type alarms following plant upsets:

* Event based.

* Time based.

* Priority based.

* Applied deadband.

Event based uses a related event to suppress an alarm; it could be the status of operating equipment or in some cases an analog process value. A typical example is that of a low flow alarm which would be suppressed if an associated pump were stopped. When the pump is restarted, a timer holds the alarm off for a short period, until the flow would be expected to have transgressed the low flow switch setting. This type of suppression is common for automatically overriding trip alarms in order to reset and restart a tripped ESD group; it prevents the problems inherent with 'manually' operated start-up overrides. This action is shown graphically in Figure 2a.

Time based uses a set time to suppress a repetitive alarm, sometimes referred to as 'auto-shelving'. If an alarm attempts to repeat itself within a set period, say 5 minutes; it is suppressed for a further 20 minutes or whatever period is suitable to cover the specific process dynamics. An optional variation is to reduce the suppression time, but to automatically reset the suppression period, should any subsequent alarm attempt occur within the suppressed period. This is a useful alarm filter used where the process cycle following a large upset, has a medium to long time constant. This action is shown in Figure 2b, where the initial alarm is processed but the following five in the specific time period are suppressed.

Figure 2b. Time based suppression
Figure 2b. Time based suppression

Priority based suppresses all new low priority four alarms should a priority one or two alarm occur. This eliminates all subsequent low priority alarms during this critical operating period, which are mostly responsible for the undesirable alarm flooding phenomena. If a manual unit trip is operated, then all associated priority two pre-trip alarms ie priority three alarms, are also suppressed, as there is no need following a 'manual' trip to have both alarms. These low priority alarms remain suppressed until a trip reset (not restart) is initiated or the higher priority alarms return to normal. The trip reset action may well release a number of previously suppressed alarms, but they are not at a critical phase of plant operation and can be calmly accepted. This action is shown in Figure 2c.

Figure 2c. Priority based suppression
Figure 2c. Priority based suppression

Applied deadband is a form of suppression, which requires the process alarm to fall below a set differential or deadband before the alarm is automatically reset. A typical application is on a short time constant or 'noisy' signal such as with some level measurements. The deadband is normally set at about 5% eg if the high level alarm is set at say 75%, it will have to fall below 70% before it is reset and the alarm extinguished. This action is shown in Figure 2d, the initial alarm is processed and the following six alarms are suppressed.

Figure 2d. Applied deadband
Figure 2d. Applied deadband

Internal damping can also be applied electronically within current transmitters. This is easily implemented if the signal is analog, digital inputs from level switches are not quite as easy. There is however, some inherent mechanical deadband (sometimes adjustable) with process switches, also, if the signal has a short cycle frequency (less than 10 s) a 5 s timer can be used to delay the alarm from resetting.

This article has highlighted a number of topics on the causes and subsequent management of abnormal process situations. The enormous benefits in the use of these AMS applications can be realised on most existing plants, within their current control systems, provided that they are DCS/PLC based. They complement recognised advanced process control (APC) strategies, as tools to minimise lost opportunities by maximising equipment and process safe operating duration and hence company profitability. Greater production and operating efficiency with increased safety protection, should be an objective of any company business plan, can we compete against world-class organisations and 'not' afford to implement such ASM practices?





Share this article:
Share via emailShare via LinkedInPrint this page

Further reading:

Oils don’t die, they degrade
Wearcheck Maintenance, Test & Measurement, Calibration
WearCheck explores the main ways lubricants degrade in service and how these degradation modes affect oil performance and machine reliability.

Read more...
Real-time spectrum analyser
Vepac Electronics Maintenance, Test & Measurement, Calibration
The PXE series real-time spectrum analyser covers frequencies up to 20 GHz with a 100 MHz analytical bandwidth and ultra-fast sweep speed, supporting spectrum monitoring, interference finding and RF test and measurement functions.

Read more...
Preserving a French heritage landmark
Omniflex Remote Monitoring Specialists Maintenance, Test & Measurement, Calibration
Omniflex supplied a remotely monitored impressed current cathodic protection system for the Perret Tower in Grenoble, a protected French heritage site, combining 24/7 corrosion protection with integrated surge protection against lightning strikes.

Read more...
Operational efficiencies and safety compliance with preventive maintenance programmes
Maintenance, Test & Measurement, Calibration
Konecranes explains how its Lifecycle Care Preventive Maintenance programme reduces unexpected downtime, improves safety compliance and delivers measurable financial benefits for operators of cranes and lifting equipment across any make or sector.

Read more...
Portable appliance tester
Vepac Electronics Maintenance, Test & Measurement, Calibration
Vepac Electronics’ new portable appliance tester enables precise safety testing of electrical appliances in accordance with DGUV regulation 3 and BetrSichV, with simple three-button operation and battery-powered mobility.

Read more...
Why lubrication fails in mining and what to do about it
Maintenance, Test & Measurement, Calibration
Lubrication Engineers explains the recurring failure points behind mining lubrication problems and how the right product, storage and application practices can improve equipment reliability.

Read more...
When digital twins move from concept to critical tool
IT in Manufacturing System Integration & Control Systems Design Maintenance, Test & Measurement, Calibration
Digital twins are moving out of the lab and onto the mine, the factory floor and the transport network where they predict failures before they happen. Amritesh Anand looks at where they earn their keep, the data and integration work behind them, and the security questions every organisation should ask before switching one on.

Read more...
Why asset level intelligence is now essential for resilient wastewater plants
Schneider Electric South Africa Maintenance, Test & Measurement, Calibration
Sub-Saharan Africa’s wastewater operators face mounting pressure to keep ageing plants running smoothly and meet tougher environmental standards, all while lacking visibility into the health of their medium-voltage (MV) drives and other critical rotating assets. Adding predictive analytics, digital twins and enterprise dashboards enables optimisation across multiple sites, ensuring every drop moves safely and efficiently through the water cycle.

Read more...
How multiple boilers can minimise costly downtime
Maintenance, Test & Measurement, Calibration
Associated Energy Services explains how multi-boiler systems reduce downtime risk for South African manufacturers, covering redundancy planning, fuel source diversification and the strategic management of backup boiler capacity.

Read more...
Field calibration made easy
Instrotech Maintenance, Test & Measurement, Calibration
Instrotech’s locally designed and manufactured Calog calibrator range feature a rugged IP54-rated housing, backlit display with data logging via SD card, and a lithium-ion battery with approximately eight hours of run time.

Read more...









While every effort has been made to ensure the accuracy of the information contained herein, the publisher and its agents cannot be held responsible for any errors contained, or any loss incurred as a result. Articles published do not necessarily reflect the views of the publishers. The editor reserves the right to alter or cut copy. Articles submitted are deemed to have been cleared for publication. Advertisements and company contact details are published as provided by the advertiser. Technews Publishing (Pty) Ltd cannot be held responsible for the accuracy or veracity of supplied material.




© Technews Publishing (Pty) Ltd | All Rights Reserved