Fibre optic temperature monitoring of switchgear

June 2018 Maintenance, Test & Measurement, Calibration

AP Sensing’s passive fibre optic cable provides accurate temperature measurements along the length of equipment such as a conveyor belt, or inside switchgear. The system enables cost-effective monitoring along extended or short distances, allowing overheating to be quickly detected and localised to within one-metre accuracy.

Case study

With all the possibilities that the AP Sensing FO DTS (fibre optic distributed temperature measurement) has to offer, a simple but very important question arises: Can it be used to detect hot spots within a switchgear cabinet? Can the DTS detect the change in temperature inside the cabinet caused by a hot component with a temperature between 100°C and 150°C? And, can it detect such a hot spot within 48 hours of the component reaching the specified temperatures?

Purpose of the test

The purpose of the test was to investigate if the DTS system is able to detect a typical hot contact/conductor anywhere inside a switching cabinet, even without the sensing cable touching the hot component.

Setup

• A cabinet was placed inside an air-conditioned room to keep the ambient temperature between 22°C and 24°C.

• The dimensions of the cabinet were 2620 x 500 x 2320 mm, with six ‘buckets’ varying in sizes between 200 and 600 mm.

• The top two buckets were closed off on the sides of the cabinet to simulate a real installation and to prevent convection to influence the result.

• A 100 W heat source 20 x 20 x 10 mm, with a surface temperature between 120°C and 150°C was placed at the bottom bucket inside the cabinet to simulate a hot connection point.

Conclusions

The results showed that the heat source caused a very small but detectable rise in the average internal temperature of the cabinet. Since the buckets were not completely isolated from each other, hot air could rise in the cabinet due to natural convection.

Detecting a hot contact/component inside the switchgear cabinet is not only a function of the source temperature, but also of the available power from the heat source. As long as the temperature sensing happens at a higher location than the source, any location inside the cabinet will suffice to detect a difference in temperature. If the cabinets are stacked end-to-end and isolated from each other, the sensing cable only needs to be inside the top most bucket. If the cabinets are not isolated from each other, the sensing cable needs to be inside the cabinet, running vertically for the height of the cabinet.

The closer the sensing cable is to the source the faster it will respond, but it is important to note that the development of a hot contact is gradual and the entire cabinet temperature will change over an extended period of time.

Questions and answers regarding the test results

Why did the system only register 35°C when the heat source was at 120°C?

• The system measures the temperature of the actual glass molecules of the optical fibre. Any change in temperature must be conducted from the outside of the cable to the glass cores inside. If the cable is not in direct contact with the heat source, the measured temperature will always be lower than the source temperature.

• The cable is sensitive to radiated heat (infrared radiation heating up the surface) as well as ambient heat (hot air surrounding the cable).

• The internal components of a typical electrical cabinet will be an optical (line-of-sight) obstruction to most of the fibre cable, thus the detection cannot rely on radiation only.

• The heat source will warm the air surrounding it and natural convection will transport the hot air to where the cable is located.

• The test proved that the 120°C source with a heating power of 100 W, sufficiently heats up the air to cause a temperature rise of more than 10°C at the top edges of the bucket where the source is located.

• 35°C was the air temperature leaving the bucket by natural convection.

How long will it take to detect a hot contact within a bucket?

• The test results show that a significant change in temperature is evident within 30 minutes, with the temperature stabilising after three hours.

• The suggestion is to have a fibre cable running vertically for the entire height of the cabinet.

• Any heat source similar or more powerful than the test source will cause hot air to escape the problem bucket and come into contact with the cable.

How should the alarm parameters be configured to detect a change in temperature?

• The best alarming method to use will be rate-of-rise. The entire length of the fibre cable inside the cabinet will be allocated to one detection zone. The system allows for up to three separate rate-of-rise parameters per zone, usually implemented as short term, medium term and long-term parameters. (A detailed copy of the test results is available on request.)

Fibre optic sensing technology offers multiple measurement solutions for measuring operating conditions in the mining and industrial sectors. It performs exceptionally well in harsh conditions and is virtually maintenance free, offering the user reliability and low cost of ownership.

For more information contact Marihette Hattingh, Sperosens, +27 (0)12 665 0317, marihette.hattingh@spero.co.za, www.spero.co.za



Credit(s)



Share this article:
Share via emailShare via LinkedInPrint this page

Further reading:

Remote monitoring for CP systems
August 2021, Omniflex Remote Monitoring Specialists , Maintenance, Test & Measurement, Calibration
PowerView iREF8 allows businesses to add remote monitoring to existing cathodic protection (CP) systems.

Read more...
Online monitoring of haul trucks
August 2021, SKF South Africa , Maintenance, Test & Measurement, Calibration
IMx-16 Multilog online monitoring systems on two mobile mining haul trucks at a leading copper mine in Zambia predict critical component failures and allow for planned predictive maintenance procedures to be carried out.

Read more...
Monitoring oil and gas pipelines
August 2021, RJ Connect , Maintenance, Test & Measurement, Calibration
Moxa’s MDS-G4020 series offers a modular platform that can be fitted with fibre interfaces to connect pipeline subsystems to a control centre over long distances.

Read more...
Non-contact meter for voltage measurements
August 2021, Comtest , Maintenance, Test & Measurement, Calibration
The new Fluke 377 FC and 378 FC Non-Contact Voltage True-RMS AC/DC Clamp Meters can measure voltage and current simultaneously without touching a live wire.

Read more...
Lubrication oil filtering and monitoring with Hydrasales
July 2021, Hydrasales , Maintenance, Test & Measurement, Calibration
The viscosity of oil in a lubricating system and its impact on bearings if not appropriately filtered, can adversely impact on system performance and even have catastrophic consequences.

Read more...
Five considerations when creating a wastewater machine monitoring plan
July 2021, TANDM Technologies , Maintenance, Test & Measurement, Calibration
In a water scarce country like South Africa, handling wastewater correctly is not a luxury but an essential service.

Read more...
Monitored cathodic systems
July 2021, Omniflex Remote Monitoring Specialists , Maintenance, Test & Measurement, Calibration
Omniflex partners with IEV to bring remotely monitored cathodic protection systems to South East Asia.

Read more...
Wide range of bonding adhesives available from BI
July 2021 , Maintenance, Test & Measurement, Calibration
Bearings International carries a wide range of instant and structural bonding adhesives throughout its extensive branch network in South Africa.

Read more...
Thermal camera with IR-Fusion technology
August 2021, Comtest , Maintenance, Test & Measurement, Calibration
Comtest has introduced the Fluke TiS60+ with Fluke IR-Fusion technology that allows users to see things that are invisible to the eye and reveal problems that cannot be detected with other tools.

Read more...
Industry first for pump testing laboratory
June 2021, Instrotech , Maintenance, Test & Measurement, Calibration
When a local fire pump test facility needed to eliminate human error from its test procedures, it contacted Instrotech for advice.

Read more...