System Integration & Control Systems Design


Control loop: Case History 139 - The importance of measurements and dynamics.

November 2014 System Integration & Control Systems Design

One of the first laws of process control states that you cannot control what you cannot measure. However, although instrument practitioners all know this they very often forget it.

I think this is largely due to the fact that most modern measuring instrumentation falls into the ‘smart’ category, which means it is computerised. One of the most common fallacies I find in the world of instrumentation and control is the apparent belief that anything working with a computer inside it must be right.

An even bigger fallacy is that if a control loop is not working properly then all you have to do is tune the controller. Many people booked on my courses tell me on arrival that they have come to attend the tuning course. I immediately tell them that they are in the wrong place as my courses deal with loop optimisation, and tuning is only a tiny part of that. In fact, in about 50% of problem loop cases, tuning is a complete waste of time without a thorough analysis of the components and a full understanding of all the control requirements, Furthermore, it is essential that one uses proper analytical and tuning software if one is to perform optimisation properly and efficiently.

Measurement

The measurement is one component in the loop, and it is the one that is most frequently ignored. I have come across cases where a person spends over six hours trying to tune a controller to get the control working, when in fact there was a blocked impulse line leading from the orifice plate to the transmitter. Another memorable case was a group of control engineers who spent several days installing feed-forward on a boiler drum level control system to overcome a particular problem, only to find out at a little later that the drum level measurement was completely wrong due to incorrect installation of the measuring instrument.

Another pet distrust of mine is the use of ultrasonic level transmitters in certain applications for which they are not suitable.

I find that many users have very little idea of how their measuring instruments work and invariably have received no training on them. I have lost count of the times I have asked plant personnel to show me the instruction manual on certain instruments, only to be told that they have lost it or do not have a manual.

Another thing I find fairly often is that people have forgotten really basic things about correct usage and installation of basic measuring devices – in particular orifice plate flow measurement. This is something that goes back hundreds of years when the theory was first published by Bernoulli in 1738. Orifice plate measurement is still regarded as one of the primary methods of flow measurement and is used as a standard for metering in custody flow applications. The reason for this is that many countries and authorities have standards relating to this method of measurement based on many years of empirical research of the basic theory.

It is however not always very accurate and installation has to be performed according to strict rules. For example British Standard 1042 states that a properly installed and calibrated orifice plate measuring system is accurate to ±2% of full scale over a 3:1 range. In practice over many decades, people in the control field use it with confidence up to a 4:1 range. However, it is a well known fact that the readings can be completely unreliable below the lower limit of 25%, and should not be used or relied on.

Many plants, particularly in the oil and chemical industries, make extensive use of orifice plate measurement due to the fact they deal with non-conductive fluids and thus cannot use the more popular and far more accurate magnetic flowmeter type measurements. These plants usually use high end grade measuring transmitters and control equipment and do not skimp on cheaper alternatives. They also usually have relatively high grade technical staff.

In spite of this, I often find flow controls in these plants working way below the 25% mark. Figure 1 shows a closed loop test performed recently on a flow loop in a refinery. This is one of the worst cases I have seen of incorrect use of the measuring system. The set-point was usually at 8% of the measuring range. It is amazing that nobody in these plants seemed to be aware that measurements like this are probably completely incorrect, and yet there is always consternation when plant balances do not correlate.

Figure 1.
Figure 1.

Dynamics

The second example in this article emphasises the importance of identifying the dynamics in a process when tuning a controller. This is one of the six most important points I always stress in my courses on loop optimisation.

One of the most interesting types of dynamics that can occur on some integrating processes is a first order lead/lag. Full information on this can be found in articles LSp2-20 and LSp2-21, published in my collection of articles entitled ‘Dynamics of More Complex Processes’.

The main characteristic of these dynamics is that there is an initial fast response to a step change on the input of the process, before the process settles into the normal constant ramp typical of integrators. This type of response is most typically found on the pressure control of drier stages on paper machines. However, it can also occur in places where you least expect it.

In general, these processes are usually terribly badly tuned and instability can arise with incorrect tuning because of the lead. This tends to frighten people and I have often heard operators express unease when we optimise loops with leads, whether positive or negative. They say: “Be careful. This loop can run away quickly!” As a result the tuning is usually extremely slow with long integrals that are typically needed for integrating processes.

In fact, these processes actually exhibit both self-regulating and integrating characteristics. On a change the response reacts initially as a relatively fast self-regulating process and it then changes into an integrating process. There are various reasons for this depending on the type of process, which is discussed fully in the above referenced articles.

The trick with positive lead integrators is to tune them on the initial self-regulating response and ignore the integrating part that follows after.

Practical examples

The particular process that will be discussed here is the pressure control at the top of a distillation column. It is an extremely important control as the performance of the column is influenced by the pressure. The process people were complaining that the pressure did not remain constant under load changes, and also took an extremely long time responding to such changes.

Figure 2 shows a closed loop test with the original tuning. Only very small set-point changes were allowed so as not to disturb the column too much. The test confirms that the response of the control was extremely slow. Also of interest it can be seen that in the latter part of the test the pressure was slightly above set-point and the controller was ramping up the output without being able to bring the pressure back down.

Figure 2.
Figure 2.

The tuning in the controller was P = 22,5 and I = 10,1 minutes/repeat.

Figure 3 shows a portion of the open loop step test. The first order positive lead, although not very large, is seen by the initial relatively fast rise in pressure followed by the typical integrating ramp. (The lead is actually about 20 seconds.) What is not shown in the figure is that it was found that when the controller output moved up past about 75% the control had no further effect on the pressure. This is a serious problem as control of higher pressures is not possible.

Figure 3.
Figure 3.

Tuning the controller over the first self-regulating portion of the test gave a tuning of P = 11 and I = 0,2 minutes/repeat. Note the integral has now been reduced by an amazing factor of 55 from the original tuning!

The new tuning worked amazingly well, being so much faster than the old. However, in final closed loop testing over a period of some 16 hours it was observed that there was a load cycle with a period of approximately 28 minutes affecting the column, and causing an increase in pressure past the point where the valve could no longer control. Figure 4 shows the pressure control operating over this period. During ‘normal’ periods it can be seen that the control was absolutely amazing, keeping the pressure at set-point with almost zero variance. However, when the load peaked the control could not hold the pressure.

Figure 4.
Figure 4.

The main point I wish to stress in this example is how important it is to recognise dynamics present in a process so that the correct type of tuning can be applied for best control.

Michael Brown’s next course series in Johannesburg will take place on 14 November.

Michael Brown is a specialist in control loop optimisation with many years of experience in process control instrumentation. His main activities are consulting, and teaching practical control loop analysis and optimisation. He gives training courses which can be held in clients’ plants, where students can have the added benefit of practising on live loops. His work takes him to plants all over South Africa and also to other countries. He can be contacted at Michael Brown Control Engineering cc, +27 (0)82 440 7790, michael.brown@mweb.co.za, www.controlloop.co.za



Credit(s)



Share this article:
Share via emailShare via LinkedInPrint this page

Further reading:

Case History 191: The weakest link.
Michael Brown Control Engineering Valves, Actuators & Pump Control
Which is the weakest link in a control loop? The answer, without any doubt is that, in most cases, the final control element is the weakest link.

Read more...
Iritron’s year of consolidation
Iritron Editor's Choice System Integration & Control Systems Design
Despite the multiple challenges faced by businesses in South Africa, the buoyancy of the technology sector worldwide has produced some green shoots for automation specialist, Iritron.

Read more...
Five edge opportunities for SIs to maximise revenue in 2024
Editor's Choice System Integration & Control Systems Design
System integrators continue to face the challenge of doing more with less – supporting complex operations, while meeting production schedules with limited resources, and innovating to increase efficiency, maximise safety and reduce risk.

Read more...
Condition monitoring in a forging press retrofit
Beckhoff Automation System Integration & Control Systems Design
Significantly increased vibration on machines can result in many forms of negative impacts such as reduced system performance or damage to the machine and foundation. Using the example of retrofitting a forging press with a maximum press force of 2000 tons, Wölfel Engineering explains how efficiently the process was tailored and implemented with PC-based control and measurement technology from Beckhoff.

Read more...
System integration in the digital age
System Integration & Control Systems Design
To meet the challenges of an increasingly competitive marketplace, many manufacturers (end users) must focus on their core competencies and outsource the rest to experts.

Read more...
Reminiscences of a life in control
Michael Brown Control Engineering SAIMC
Reminiscences from Michael Brown on a long and rich journey in the world of automation together with SAIMC.

Read more...
Loop signatures 21: You cannot control if your measurement is incorrect.
Michael Brown Control Engineering Editor's Choice
The first law of process control could be stated as saying that you cannot control if your measurement is incorrect. We all know this law. However do we all remember it in the heat of the moment?

Read more...
Choosing a system integrator
Editor's Choice System Integration & Control Systems Design
Automation is an essential part of manufacturing today. Whatever the size, an upgrade or migration project can be complex, and the risks can be high. This is where system integrators (SIs) can help. They can bring together complex subsystems or components of a larger system and make them operate as a whole.

Read more...
Case History 190: Measurement problem ruins level control.
Michael Brown Control Engineering Editor's Choice Fieldbus & Industrial Networking
The widely held belief in many plants that tuning will solve all base layer control problems is completely fallacious. Bad tuning is generally not the main reason for loops to perform badly. It is important when performing optimisation that all elements in a loop are considered, in addition to the control strategy, before even thinking of tuning.

Read more...
Loop signatures 20: The great deceivers.
Michael Brown Control Engineering Editor's Choice
It is generally better to live with noise rather than filtering it out, provided it does not cause the final control element to jump around excessively.

Read more...