South African Instrumentation And Control South African Instrumentation And Control
 
   
 





























 
 

Control loop case history 125
May 2012, Control Systems Design


In the previous Case History article 124, I promised to show some more interesting things taken from the amazing ‘problem free plant’. However, before doing this I would like to show a very interesting tuning performed on the steam drier section on a paper machine.

The vagaries of positive lead integrators

The controls for the steam drying sections on a paper machine are extremely important as they regulate the amount of moisture in the paper. The moisture content is measured when the paper leaves the machine and a sophisticated advanced control system determines the set-points of the steam pressure regulatory control loops on the inlet of each drying section further back down the machine.

These controls are required to follow the set-points as quickly as possible so as to keep the control variance to an absolute minimum. The set-points are usually moving around slowly, so, if the controllers cannot keep the process variable on set-point, bad moisture control will result that can cost the plant a lot of money.

Back pressure controls on steam driers have very interesting dynamics being positive lead integrators. This was dealt with in great detail in my Loop Signature articles LSp2-20 and LSp2-21. As mentioned there, most people find them extremely difficult to tune as they can go unstable quite easily – they are usually tuned really badly and extremely slowly. This is mainly due to the fact that very few people know how to recognise the dynamics of a positive lead integrator, and those that do have not been taught how to tune them. Once tuned correctly, these loops follow set-point extremely quickly and with virtually no variance at all, as the correct tuning is in fact extremely fast and very stable.

An example in practice

In this particular case I was called in to sort out some serious control problems on the paper machine. In particular, the pressure controls were terribly bad; it could take over an hour after a paper break or a grade change to get the pressures back within acceptable limits.

It was a very interesting assignment. The paper machine was being controlled by a well known German PLC/scada system. This in itself is unusual, as generally controls on sophisticated plants like paper machines are DCS based, since these are much more versatile and refined than PLCs. As I have written many times, I generally find in at least 85% of cases that the control blocks on PLC systems are set up incorrectly making scientific tuning and correct operation impossible.

In this particular case the control blocks were programmed so badly that it was decided to rewrite and change them over as we optimised each loop. An extremely difficult and challenging operation to perform on a plant running at full load, however, we managed it without actually tripping the machine.

The first loop in the steam controls that needed to be optimised was the main supply pressure regulating control that fed all the drier sections on the machine. This is an important control the purpose of which is to keep the downstream steam pressure supply constant. If it is not tuned correctly and as fast as possible, then all the downstream drier pressure controls can interact badly.

As suspected, it was found that the tuning of all the pressure controls was terrible. An example of one of the drier pressure control loops running in automatic with the original tuning is shown in Figure 1. A 10% set-point step change was made. It took over 4 minutes for the PV to get to the new set-point, which it then overshot and took roughly another 10 minutes to settle.

Figure 1
Figure 1

Figure 2 is the open loop test which shows the initial big and fast kick of the lead, before the pressure settles into the typical integrator ramp. Please note that the steps in the PV as seen in the recording are due to the OPC data exchange information system which we were using to record the test. Typically most OPC systems have a 1 second scan rate which explains the badly aliased signal seen in the test.

Figure 2
Figure 2

The final tuning is seen in the closed loop test in Figure 3 – it is spectacularly faster than the original. Again a 10% set-point change was made, this time the process got to set-point within 20 seconds and had completely settled a few seconds later.

Figure 3
Figure 3

We often call this dramatic tuning of positive lead integrators our ‘party trick’, because people who witness can hardly believe how quickly and accurately the PV follows subsequent set-point changes. In this case, the work on this paper machine was really successful and the plant personnel were astounded at the improvements in machine performance.

More ‘party trick’ tuning

Returning now to the previous Case History Article 124 where the bad performance of a fuel oil pressure control loop, which was the secondary cascade to the temperature control of a furnace, was discussed. I promised that the tuning of the primary cascade temperature loop would be given in the next (this) article, so here it is: the original tuning parameters on this very slow temperature process were:

P = 0,35.

I = 0,7 minutes/repeat.

D = 0,6 minutes.

Figure 4 shows the response to a small 2% step change in set-point, it took almost 3 hours for the process to settle.

Figure 4
Figure 4

An open loop tuning test was then performed with the following new tuning parameters inserted in the controller:

P = 15,0.

I = 4,0 minutes/repeat.

D = 0 (not used).

The almost miraculous improvement in response to a 2% step change can be seen in Figure 5. It now took only 25 minutes for the process to respond and get exactly on set-point.

Figure 5
Figure 5

To be fair, even if we ignore the terribly badly tuned secondary pressure loop, it is extremely difficult for anyone to tune really slow temperature processes without the right equipment. The famous Greg McMillan, a retired senior fellow from Solutia/Monsanto where he worked in engineering technology on process control improvement, wrote an article recently where he said that it is beyond the capability of the average human being to tune a slow temperature control loop by trial and error – they do not have a long enough life span.

Luckily I use the Protuner loop analytical and tuning software, which does all the maths and hard tuning calculation work for you. The actual open loop test from which the tuning was done is shown in Figure 6. The test took approximately 1 hour to complete and there are a couple of extremely interesting points:

Figure 6
Figure 6

Due to the extreme importance of this control and the effect it can have on downstream units, the operators would only allow us to move the temperature by 2°C, which is equivalent to 0,4% of the temperature span! That really is tuning on an almost imperceptible change, so it is incredible what good results were obtained by the software – almost miraculous!

Note the large size of the change of PD (controller output) compared with the small size of change in the PV (temperature) in the figure. Calculating the process gain (PV/PD) we get a figure of 0,065. This is absolutely tiny for a self-regulating process, where for example on flow loops it is normally between 0,5 and 2,0. This alone means that one has to use a very high controller proportional gain to compensate. (Refer Loop Signature article LSp1-3 for a detailed discussion on process gain).

I believe this tuning also falls into the ‘party trick’ category.

Note: Michael Brown’s next practical control course series starts on 17 August in Johannesburg.

Michael Brown is a specialist in control loop optimisation, with many years of experience in process control instrumentation. His main activities are consulting, and teaching practical control loop analysis and optimisation. He gives training courses which can be held in clients’ plants, where students can have the added benefit of practising on live loops. His work takes him to plants all over South Africa, and also to other countries. He can be contacted at Michael Brown Control Engineering cc, +27(0)11 486 0567, michael.brown@mweb.co.za, www.controlloop.co.za


Credit(s)
Supplied By: Michael Brown Control Engineering
Tel:
Fax: +27 (0)11 646 2385
Email: michael.brown@mweb.co.za
www: www.controlloop.co.za
Share via email    

Further reading:

  • Control loop: Case history 130
    April 2013, Michael Brown Control Engineering, Control Systems Design
    The purpose of the integral term in the controller is to eliminate the control error. However, the problem with the integrator is that it never stops trying to eliminate the error even in circumstances ...
  • Plant-wide Metso DNA automation
    April 2013, Metso Automation, Control Systems Design
    For years now, Metso has delivered first class crushers and equipment to its customers for processing aggregates. Crushers, stationary or mobile, typically come with a well-proven machine automation IC ...
  • Automated fire protection solutions
    April 2013, Alien Systems & Technologies, Control Systems Design
    Automation and amalgamation of technology driven services can streamline processes to make a business operate far more efficiently. The South African Police Service 10111 Centre in Port Elizabeth is a ...
  • 4 Bytes Automation: Product and system knowledge is critical
    February 2013, Control Systems Design
    4 Bytes Automation was formed in 2008 when its founding members – Sarel Theron and Christo Coetzer – committed to providing the food and beverage industry with a superior systems integration offering. ...
  • New autonomous robots overcome previous limitations
    February 2013, Control Systems Design
    In the mobile solutions space, robots are gaining traction against traditional AGV and fixed conveyor solutions.
  • Michael Brown Control Engineering has moved
    February 2013, Michael Brown Control Engineering, News
    Michael Brown Control Engineering has moved. The new details are:    Phone: +27 (0)82 440 7790    Fax: +27 (0)86 671 9320    E-mail and url remain the same as:    E-mail: michael.brown@mweb.co.za    Website: http://www.controlloop.co.za/...
  • Control loop case history 129: Incorrect level control strategies cause instability
    January 2013, Michael Brown Control Engineering, Control Systems Design
    I was asked recently to sort out some control problems in a chemical plant. One of the problems of concern was an important process where it was desired to control the flow of a liquid, split into four ...
  • Tellap racks up higher production with Festo
    December 2012, Festo, Control Systems Design
    Tellap is a company that supplies recyclable plastic sleeves to replace the wooden pallets generally used to stack 1 ton bags of product with. The alternative is necessary as wooden pallets cannot be ...
  • Control loop case history 128
    November 2012, Michael Brown Control Engineering, Control Systems Design
    Advanced process control (APC) is the ‘in-thing’ in the modern control world with many plants in numerous industries applying it. The potential benefits to production and the financial bottom line are ...
  • Invensys' real-time energy usage monitoring solution
    November 2012, Invensys Operations Management, Control Systems Design
    Dynamic performance measurement system improves energy and electricity consumption at Sasol.
  • Automation and information solution for Morupule Colliery
    November 2012, Royal HaskoningDHV Consulting Engineers, Control Systems Design
    Royal HaskoningDHV overcomes the problems of limited space and access during colliery upgrade in Botswana.
  • PC and EtherCAT-based control for wind turbines
    November 2012, Beckhoff Automation, Control Systems Design
    Automation technology from Beckhoff has proven itself in use worldwide in wind turbines up to a size of 5 MW. PC-based automation technology offers powerful controllers that unite all components of a ...

 
 
 
Search...

Electronics Buyers' Guide

Process Expo

         
 
Contact:
Technews Publishing (Pty) Ltd
1st Floor, Stabilitas House
265 Kent Ave, Randburg, 2194
South Africa
Publications by Technews
Dataweek Electronics & Communications Technology
Electronic Buyers Guide (EBG)

Hi-Tech Security Solutions
Hi-Tech Security Business Directory

Motion Control in Southern Africa
Motion Control Buyers’ Guide (MCBG)

South African Instrumentation & Control
South African Instrumentation & Control Buyers’ Guide (IBG)
Other
Terms & conditions of use, including privacy policy
PAIA Manual





 

 
             
   
      Classic | Mobile

Copyright © 2012 Technews Publishing (Pty) Ltd. All rights reserved.