Room integrity testing in fire extinguishing systems

November 2014 IS & Ex

All gas extinguishing system standards require a certain concentration of extinguishant to be maintained in an area for a minimum time period, generally 10 minutes for clean agents.

Discharge testing on electrical and mechanical fire extinguishing systems was originally performed to test reliability and validate extinguishing concentrations. However, as installation and equipment manufacturing standards became more stringent and quality management systems became the norm, it was found that reliability of the systems began improving; and statistical measurement techniques as required by ISO 9000 highlighted problem areas sufficiently to implement timeous corrective actions should problems occur.

Meanwhile the discharge test only verified a design for that particular system configuration at that particular point in time. Also when performing a discharge test, only a few seconds are available to establish where a problem may have occurred if the design concentration is not reached, and further expensive discharge testing is then required. Concerns over depletion of the ozone layer and global warming further curtailed the use of halon and other synthetic gas systems. As a result, enclosure integrity acceptance testing was adopted in its place.

Room integrity testing

Room integrity testing is a mandatory requirement of gas extinguishing standard SABS/ISO 14520. This standard also states that the testing must be carried out every 12 months to validate the enclosure integrity. Failure to perform the initial room integrity test is a violation of the SABS design and installation code, and places system performance responsibilities clearly on the installation contractor. Failure to perform annual testing places system performance responsibilities on the shoulders of the end-user.

The test consists of pressurising the enclosure with calibrated fans that provide specific airflows at specific flow pressures. In addition, the exterior and interior pressures of the enclosure are monitored so as to determine air leakage from the room. The earlier NFPA 2001 standard only requires a single measurement to be performed, while the SABS/ISO standard requires multiple sets of test data to be recorded. The SABS/ISO requirement is therefore more accurate and can highlight equipment errors and prevent operator manipulation of the results, since the minimum correlation factor and allowable standard deviation is specified.

The test result is provided as an equivalent leakage area (ELA) in square metres. This is the sum total of leakage paths in the room. By utilising a computer model of the gas extinguishing agent properties and knowing the ELA, the gas extinguishing retention times for the minimum design concentration can be determined.

If the retention time is greater than 10 minutes, then the room passes. If a room fails, it is easy to locate the leakage paths using smoke pencils and seal the leaks. Enclosure integrity and the fire resistance thereof is also a requirement of BS 6266. This standard is implicitly referred to in BS 5839, which has also been adopted in South Africa as SABS 0139 (now SANS 10139).

Why perform room integrity testing?

1. Room integrity testing is a mandatory requirement of the SABS/ISO clean agent standard. This applies to all gases and all systems.

2. Although not mandatory, it is highly recommended that room integrity be performed on CO2 installations. CO2 has one of the highest densities of any extinguishing gas and so has one of the highest column pressures. This means that it is one of the most difficult gases to maintain at the correct concentration and the retention times are typically 20 minutes – twice as long as clean agents.

3. Extinguishing concentration measurements in a discharge test generally overestimate the actual extinguishing concentration by a substantial margin. The results can easily create a false sense of security.

4. Room integrity testing allows the total room leakage to be identified and if this leakage is too great, remedial action can be taken immediately and the results of the remedial work checked.

5. One of the most important design aspects of all clean agent systems is correct room venting. This is especially true of CO2 systems. High discharge rates of the synthetic gases and high air displacement of the inerts (±40%) make venting a key issue. With too little venting the room can be subjected to overpressurisation, which will result in structural failure. With too much venting the gas extinguishing concentration may not be achieved for the prescribed time period. Room integrity testing allows the venting requirements to be verified by on-site testing.

6. There are major savings in the running costs of air conditioners.

For more information contact Sam Wright, Alien Systems and Technologies, +27(0)11 949 1157, [email protected], www.astafrica.com



Credit(s)



Share this article:
Share via emailShare via LinkedInPrint this page

Further reading:

Cathodic protection system for hazardous environments
Omniflex Remote Monitoring Specialists IS & Ex
When NSW Ports in Australia embarked on a two-year programme to rehabilitate the structures and combat corrosion levels at its Bulk Liquid Berth 1, it commissioned Melbourne-based consultancy Infracorr to deliver a bespoke cathodic protection) system. To deliver the system safely, Infraccor engaged cathodic protection specialist Omniflex to support the hazardous area and remote monitoring aspects of the CP system design.

Read more...
Leading the way in PDS technology
IS & Ex
Booyco Electronics, an original equipment manufacturer specialising in mine safety equipment, has witnessed a surge in demand for its proximity detection systems (PDS) and collision prevention systems (CPS) since the Mine Health and Safety regulation focusing on trackless mobile machinery was promulgated. These systems offer crucial vehicle-to-pedestrian and vehicle-to-vehicle detection capabilities.

Read more...
Ensuring lone worker safety
IS & Ex
The Conextivity Group’s startup – Wearin’ – has developed a solution connecting the lone worker with the control centre. This was commissioned by concrete producer, Pro Beton to ensure the safety of its teams of machine operators and cleaners working on production sites during the day, night, and weekends.

Read more...
Safety breakthrough in live testing of large equipment
IS & Ex
While essential to effective maintenance, the live testing of mining vehicles and equipment can be hazardous and time consuming; but this has all changed with the SafeGauge range of digital testing systems. Developed in Australia, SafeGauge is now distributed in South Africa by Booyco Electronics, known for its leading role in promoting safety on mines through its proximity detection systems.

Read more...
Explosion-protected control units
Pepperl+Fuchs IS & Ex
The new range of control units from Pepperl+Fuchs offers a clever solution for switching and controlling circuits in hazardous areas that are designated ATEX/IECEx Zones 1/21 and 2/22.

Read more...
The importance of understanding SIL ratings
Omniflex Remote Monitoring Specialists IS & Ex
Major industrial accidents around the world, like the Bhopal chemical plant disaster, have occurred due to insufficient and poorly designed safety systems. Gary Bradshaw, director of alarm and safety system specialist Omniflex, explains how SIL ratings work and the dangers of the misconceptions that exist around them.

Read more...
The importance of understanding SIL ratings
Omniflex Remote Monitoring Specialists IS & Ex
Major industrial accidents around the world, like the Bhopal chemical plant disaster, have occurred due to insufficient and poorly designed safety systems. Gary Bradshaw, director of alarm and safety system specialist Omniflex, explains how SIL ratings work and the dangers of the misconceptions that exist around them.

Read more...
Mobile workers 4.0
Pepperl+Fuchs IS & Ex
Intrinsically safe smart devices enable lone mobile workers to work seamlessly throughout the plant with the help of digital support. The significant increase in production efficiency and reliability is noticeable.

Read more...
Functional safety over EtherCAT
Eagle Africa Technology IS & Ex
HMS Networks has released a new version of the Ixxat SafeT100 module, allowing users to implement safe I/Os for FSoE (Functional Safety over EtherCAT), which was previously available only for PROFIsafe and CIP Safety.

Read more...
Overcurrent protection for explosion-protected areas
Phoenix Contact IS & Ex
The customisable Caparoc circuit breaker system from Phoenix Contact now also offers modules for explosion-protected areas, thereby extending the range of possible applications.

Read more...