Tech tips: Comtest Distribution - Using thermal imaging for MCC maintenance

August 2007 Maintenance, Test & Measurement, Calibration

Thermal imaging can be used to evaluate the operating condition of the components within motor control centres (MCCs) by comparing the relative temperatures of components under load.

Thermal imagers can indicate the operating condition of the components within MCCs by comparing their relative temperatures under load.

Key components to be monitored include bus bars, controllers, starters, contactors, relays, fuses, breakers, disconnects, feeders and transformers.

Caution

Only authorised and qualified personnel using the appropriate personal protective equipment should open electrical panel covers. When a panel is open and energised, because of the possibility of arc-flash, all unprotected personnel should be kept behind a calculated and clearly delineated arc-flash boundary.

What to check?

* To keep the task manageable, begin by scanning only MCCs associated with critical assets - those whose failure would threaten people, property or product.

* Scan all components and connections within MCCs with the enclosures open and the equipment running.

* Measure the load at the time of each scan to properly evaluate the measurements against normal operating conditions.

What to look for?

* Look for components that are hotter than similar components under similar loads.

* Look for components that are cooler than similar components under similar loads.

* Doing this may identify broken or undersized wires, defective insulation, faulty (corroded, too loose or over tightened) connections and electrical unbalance among phases.

* Connection related hot spots usually (but not always) appear warmest at the spot of high resistance, cooling with distance from that spot. One source1, reports that 25% of all miscellaneous electrical apparatus failures are caused by loose electrical connections.

* Unbalance, whether normal or out of specification, will appear equally warm throughout the phase or part of the circuit that is overloaded. Harmonic unbalance creates a similar pattern.

* A cooler-than-normal circuit or leg might signal a failed component.

* All electrical currents produce some heat. Heat alone, then, is not an indicator of problems. Equally warm conductors in all three phases represent a 'good' pattern. Differentiation between phases should be investigated.

Record keeping

* Create regular inspection routes that include all key electrical panels, including MCCs.

* Save a thermal image and associated temperature data of each one on computer and track measurements over time.

* This will provide a baseline for comparisons in order to determine whether a hot spot is unusual or not, and to help verify a repair's success.

What represents a red alert?

* Equipment conditions that pose a safety risk should receive the highest repair priority.

* Guidelines provided by the NETA (InterNational Electrical Testing Association) say that when the difference in temperature (DT) between similar components under similar loading exceeds 15°C immediate repairs should be undertaken.

* The same organisation recommends the same action when the DT for a component and ambient air exceeds 40°C.

* Another approach is to treat the imminent failure of any piece of critical equipment as a red alert.

* The same key operations, maintenance and safety personnel who determine which production assets are critical should play important roles in quantifying 'warning' and 'alarm' levels for those assets.

* Set alarm levels for specific equipment on your thermal imager.

The potential cost of failure

* Since MCCs vary so much in complexity, it is difficult to put firm figures on costs for repairs and replacements. However, one European source2 says that the average MCC repair is between 10 000 Euros (R90 000) and 70 000 Euros (R630 000) with replacements costing 80 000 Euros (R720 000) to 100 000 Euros (R900 000).

Follow-up actions

* When a problem is discovered using a thermal imager, use the associated software to document the findings in a report that includes both a digital photograph and a corresponding thermal image of the equipment.

* Following corrective action, use a new thermal image to assess a repair's effectiveness and evaluate the materials and techniques used.

Sources:

1: The website of the Academy of Infrared Thermography at www.infraredelectrical.com/ infraredelectrical_15.html.

2: Ibid.

The information for this Tech Tip was provided by Comtest Distribution.

For more information contact Val Verwer, Comtest Distribution, +27 (0)11 254 2200, [email protected], www.comtest.co.za



Credit(s)



Share this article:
Share via emailShare via LinkedInPrint this page

Further reading:

Prioritising arc flash safety
Comtest Electrical Power & Protection
Comtest has developed a range of thermal imaging and wireless testing tools from Fluke, designed to ensure safety is the top priority for engineers working in potentially dangerous arc flash zones.

Read more...
Seaward testers power PV specialists
Comtest Electrical Power & Protection
One of Asia’s leading clean energy specialists, Solarvest, uses the latest electrical safety test equipment to ensure the solar photovoltaic (PV) installations it services and maintains operate at peak performance levels.

Read more...
Cable locator for failsafe cable fault diagnostics
Comtest Electrical Power & Protection
Accidentally hitting a power cable during a project can lead to costly repairs and create seriously hazardous safety situations. The Amprobe UAT-600 series locating kit from Comtest comes complete and ready for use with a transmitter, receiver, test lead kit, batteries and additional fuses, all in a mobile, protective duffle bag.

Read more...
Collect data three times faster
SKF South Africa Maintenance, Test & Measurement, Calibration
SKF has extended its renowned Microlog Analyzer family of data collection devices with the addition of the Microlog Analyzer dBX. Currently SKF’s most powerful diagnostic tool, this cutting-edge device redefines diagnostic capabilities, enabling users to take measurements three times faster than its predecessor.

Read more...
The criticality of maintenance in the water and wastewater segment
Schneider Electric South Africa Maintenance, Test & Measurement, Calibration
In a time of water shedding, climate change and ageing infrastructure, the importance of maintenance and support in the water and wastewater segment cannot be overstated.

Read more...
How dry ice blasting is revolutionising the mining industry
Maintenance, Test & Measurement, Calibration
Dry ice blasting has emerged as a game-changing technology for the mining industry, offering a range of advantages that are reshaping traditional cleaning methods.

Read more...
Precision acoustic imagers
Comtest Sensors & Transducers
To help users identify and localise ‘mechanical areas of interest’ within short timeframes, Comtest has added a unique new feature to Fluke’s ii910 precision acoustic imagers.

Read more...
Finding energy waste with power quality management
Comtest Electrical Power & Protection
Saving energy and minimising energy waste are two of the most critical aspects of energy use. Energy saving means looking at your power consumption rates, and developing a power quality management energy-saving plan.

Read more...
Quality test tools save costs at pulp and paper mill
Comtest Editor's Choice Maintenance, Test & Measurement, Calibration
A case study on how preventive maintenance and a few good test tools avoided unnecessary motor replacements at a pulp and paper company.

Read more...
Precision shaft alignment
Comtest Motion Control & Drives
The powerful Fluke 831 Laser simplifies precision shaft alignment and saves thousands in downtime and energy waste by making it practical to align most machines in a facility.

Read more...