Calculating intrinsically safe loop approvals – Part 2

July 2013 IS & Ex

Subsequent to my previous article published in SA Instrumentation and Control on the subject of calculating an intrinsically safe loop approval (www.instrumentation.co.za/7571a), I will now consider the impact of Exic and how to handle long cable runs in IS loops.

ExnL (Energy Limiting) was a technique used for Zone 2 which was effectively ‘intrinsic safety in normal operation’ i.e. with no safety factor required. ExnL has been reassigned as Exic in IEC/SANS60079-11 and IEC/SANS60079-25. Previously, although not spelt out in the standards, it was generally accepted practice to run ExnL loops in the same trunks as IS loops. With the new standards, it is clear that Exic loops can be run in the same multi-core or trunk as other Exi loops. This means that single multi-core (or trunk) can be used for IS instruments in Zone 0, 1 and 2. NOTE : Shared multicore must be Type A or B in accordance with system standard IEC/SANS 60079-25, that is not subject to faults.

Figure 1.
Figure 1.

Further on this topic: CENLEC standard and subsequently the IEC standard changed the capacitive reference curves because of some tests done in Germany. This reduced the allowed cable capacitance from 2002. This impacts plants built between 1995 and 2002 based on earlier ATEX standards where longer cable runs were required.

For a standard 24 V loop (Uo = 28 V) this changed the Co from 130 nF to 83 nF, reducing the maximum cable length allowed. When these plants require a DCS upgrade and a new isolator is to be fitted, the IS loop calculation now fails.

How can we handle this? Firstly, and importantly, there is a misconception that the Co values are defined by the design of barrier/isolator. The Co value is actually defined in IEC/SANS60079-11: 2012 Table A.2 page 96 (102 of 149). So any barrier/isolator with 28 V safety description will have Co = 83 nF (Zone 0/1; IIC). In practice this parameter will define the maximum allowable cable length.

Figure 2 shows an Exia loop with a Co=83 nF. The max cable capacitance Cc=63 nF. With a typical cable capacitance of 95 nF/km, this would equate to a maximum cable length of 660 metres.

Figure 2.
Figure 2.

If the loop were Exic, the Co=272 nF, so Cc=252 nF would theoretically allow 2,5 km of cable i.e. no longer a limiting factor. (The limiting factor in this system is likely to be the operating voltage at the end of the cable still being high enough to allow the transmitter to work). In Figure 3, the system is Exic certified.

Figure 3.
Figure 3.

Conclusions

1. For new installations requiring long cable runs, classifying the area as Zone 2 offers significant benefit.

2. For upgrading existing plants where the new loop approval fails, there are two options:

* Reclassify the hazardous area as Zone 2, then use Exic and make use of the higher Co value. If this is possible it is the simpler option.

* If it is not possible to reclassify, there is an alternative to be defined in the new ARP0108 due out shortly i.e. there is the availability of a ‘Risk Assessment’ for these loops (Reference in A.10). Note: If a change to loop apparatus results in incompatible safety parameters in accordance with the certification standard, the ATL may consider the use of risk assessment methods and a concession may be issued.

In both cases, Exic offers some flexibility and for upgrades allows for upgrades of old control systems improving safety.

Additional note on equipment for Zone 2: In Europe the ATEX directive allows for Cat 3 self certification (e.g. ExnA non-arcing). Due to the low risk of ignition and high skills proficiency (suppliers and end-users) this is acceptable. Most ExnL ATEX certified products were also Cat 3 self-certified. However with changing to Exic, this is now covered by the third party Exi certification (with minimal extra work or cost), making it an accepted practice in SA.

For reference to Part 1 see October 2012, pages 74 and 75, or refer to www.instrumentation.co.za/7571a

For more information contact Gary Friend, Extech Safety Systems, +27 (0)11 791 6000, gary@extech.co.za, www.extech.co.za



Credit(s)



Share this article:
Share via emailShare via LinkedInPrint this page

Further reading:

Cathodic protection system for hazardous environments
Omniflex Remote Monitoring Specialists IS & Ex
When NSW Ports in Australia embarked on a two-year programme to rehabilitate the structures and combat corrosion levels at its Bulk Liquid Berth 1, it commissioned Melbourne-based consultancy Infracorr to deliver a bespoke cathodic protection) system. To deliver the system safely, Infraccor engaged cathodic protection specialist Omniflex to support the hazardous area and remote monitoring aspects of the CP system design.

Read more...
Leading the way in PDS technology
IS & Ex
Booyco Electronics, an original equipment manufacturer specialising in mine safety equipment, has witnessed a surge in demand for its proximity detection systems (PDS) and collision prevention systems (CPS) since the Mine Health and Safety regulation focusing on trackless mobile machinery was promulgated. These systems offer crucial vehicle-to-pedestrian and vehicle-to-vehicle detection capabilities.

Read more...
Ensuring lone worker safety
IS & Ex
The Conextivity Group’s startup – Wearin’ – has developed a solution connecting the lone worker with the control centre. This was commissioned by concrete producer, Pro Beton to ensure the safety of its teams of machine operators and cleaners working on production sites during the day, night, and weekends.

Read more...
Safety breakthrough in live testing of large equipment
IS & Ex
While essential to effective maintenance, the live testing of mining vehicles and equipment can be hazardous and time consuming; but this has all changed with the SafeGauge range of digital testing systems. Developed in Australia, SafeGauge is now distributed in South Africa by Booyco Electronics, known for its leading role in promoting safety on mines through its proximity detection systems.

Read more...
Explosion-protected control units
Pepperl+Fuchs IS & Ex
The new range of control units from Pepperl+Fuchs offers a clever solution for switching and controlling circuits in hazardous areas that are designated ATEX/IECEx Zones 1/21 and 2/22.

Read more...
The importance of understanding SIL ratings
Omniflex Remote Monitoring Specialists IS & Ex
Major industrial accidents around the world, like the Bhopal chemical plant disaster, have occurred due to insufficient and poorly designed safety systems. Gary Bradshaw, director of alarm and safety system specialist Omniflex, explains how SIL ratings work and the dangers of the misconceptions that exist around them.

Read more...
The importance of understanding SIL ratings
Omniflex Remote Monitoring Specialists IS & Ex
Major industrial accidents around the world, like the Bhopal chemical plant disaster, have occurred due to insufficient and poorly designed safety systems. Gary Bradshaw, director of alarm and safety system specialist Omniflex, explains how SIL ratings work and the dangers of the misconceptions that exist around them.

Read more...
Mobile workers 4.0
Pepperl+Fuchs IS & Ex
Intrinsically safe smart devices enable lone mobile workers to work seamlessly throughout the plant with the help of digital support. The significant increase in production efficiency and reliability is noticeable.

Read more...
Functional safety over EtherCAT
Eagle Africa Technology IS & Ex
HMS Networks has released a new version of the Ixxat SafeT100 module, allowing users to implement safe I/Os for FSoE (Functional Safety over EtherCAT), which was previously available only for PROFIsafe and CIP Safety.

Read more...
Overcurrent protection for explosion-protected areas
Phoenix Contact IS & Ex
The customisable Caparoc circuit breaker system from Phoenix Contact now also offers modules for explosion-protected areas, thereby extending the range of possible applications.

Read more...